background image

outlet

pressure

inlet

pressure

blue hose

red hose

knob

Step 3:

Valve Connection and Disconnection 

1. Connect the FlowCon FBT hoses via the p/t  

  needles to the p/t plugs on the valve. Connect  

  the red hose to plus side / inlet pressure and 

  blue hose to minus side / outlet pressure. 

 

2. Finger-turn the knob counter-clockwise until  

  end position, i.e. P=0, to release air inside the  

  hoses, needles and probe and wait a few se- 

  conds. Then finger-turn the knob clockwise  

  until end position, i.e. measurement icon. The  

  FBT is now properly air vented.

3. Take readings via FlowCon App.

4. Before moving on to the next valve reading,  

  finger-turn the knob clock wise  to  disconnect  

  the FBT from system pressure (this will ensure 

  that water will not flow through the tubes and  

  the FBT and safeguard no water leakage) 

 

NOTE: Water may eject if the FBT is not dis- 

  connected from system pressure.

5. Remove the p/t needles from the valve and  

  finger-turn the knob counter-clockwise to re- 

  lease pressure.

6. Repeat steps 1-5 until all valve readings are  

 performed.

7. Once completed, turn off the FBT and Blue- 

 tooth

®

 connection by pushing the 

 for 3 se- 

  conds. LED will switch off.

Battery Re-placement

The FlowCon FBT is supplied with 2 pcs. 1.5V 

AAA batteries. Once battery life (up to 32 hours 

of battery operation) runs out, simply open the 

battery cover on the backside of the handle 

and replace the batteries. Alternatively, 2 pcs. 

900mAh AAA NiMH rechargeable batteries can 

be used. 

Cleaning, Service and Disposal

Clean the FlowCon FBT after each use with a dry, 

lint-free cloth. If necessary, use a damp cloth to 

remove difficult dirt. No kind of cleaning agent 

is allowed.

The FlowCon FBT must be serviced by the 

manufacturer or an authorized service point at 

regular intervals. 

Dispose the FBT in compliance with applicable 

directives, standards and safety regulations. 

Electronic components and batteries must not 

be disposed as normal household waste.

This paper is a supplement to the

 FlowCon General Instruction 

Latest release of any FlowCon material is available on

 

www.flowcon.com

FlowCon FBT - Bluetooth Commissioning Meter

1A95130 - 04/2021

Page 2 of 2

FlowCon International assumes no responsibility for mistakes, if any