HMI MANUAL
www.flowair.com
14
• Wires must be finished with cord end terminals.
• Wires size should be chosen by the designer.
• Dimension of supplying wire is min. OMY 2 x 1 mm
2
.
• Close the cover before start–up.
9 10
8
7
N
N
L
A/+ B/-
RS485
230V/50Hz
Fan
Hi Med.
Lo.
Valv
e
external NTC
(optional)
6
5
4
3
2
1
9. BMS COMMUNICATION
The controller allows to connect to BMS. Register addresses are
available on www.flowair.com.
Communication parameters:
Physical layer
RS485
Protokol
MODBUS-RTU
Transmission speed [bps]
2400
Parity
None
Data bits count
8
Stop bits count
1