Flomatic FDHC-100 Configuration And Operation Manual Download Page 9

Flomatic Smart Card

TM

 

Model FDHC-100 (Digital High-Resolution Controller) 
Configuration and Operation Manual 

 

 
 
 

FDHC-100 Configuration & Operation Man. Rev 0 

August 16, 2010 

9 of 14

 

Flomatic Corporation 
Glens Falls, NY 12801 
Phone (518) 761-9797 
Fax (518) 761-9798 

when the FDHC-100 detects a motion greater than 1.5° in either direction. The fault can be cleared if 1) 
the command signal commands a Motor 2 operation, 2) manual operation with the adjust buttons results 

in a motion greater than 1.5°, or 3) a mechanical manual override forces the 1.5° motion, provided the 

mechanical motion is monitored by the feedback pot. 

 

MOTOR 2 STALL - A fault is detected when no actuator motion is detected while the Motor 2 output is 
turned on.  The fault can be cleared in the same manner as a Motor 1 Stall (see above). 

 

DOUBLE STALL - If the FDHC-100 detects no actuator motion in either direction, both motor outputs will 

be disabled. The command signal cannot clear this condition; only manual operation or a mechanical 
override can clear the fault. Alternatively, the FDHC-100 can be powered off and then on to temporarily 

clear the fault; however, this practice should be avoided without permanently correcting the cause of 

such a fault. 

 

STALL DETECTION FEATURE  

The Stall Detection feature of the FDHC-100 (see FAULT INDICATOR) essentially performs a similar 

function as commonly used torque switches; however, the differences should be considered before 

eliminating the torque switches. The FDHC-100 feature does not measure torque, but rather motion; if 
the load is sensitive to excessive torque, the torque switches may be desirable. Since common torque 

switches are mechanical devices, they can provide a fail safe feature in the event of electrical failures 

(Such as shorted wires or damage to the FDHC-100). The Stall Detection feature is useful for detecting 

when any of the motor wires become disconnected. However, limit switches employed in actuators 
essentially disconnect one of the motor windings. The FDHC-100 will detect this as a motor stall. To 

avoid this condition, the limit switches must be set outside of the operating range set by the CLOSE and 

OPEN functions. 

 

ELECTRONIC BRAKE FEATURE  

The Electronic Brake feature of the FDHC-100 provides highly reliable and accurate braking of the 

motor, and it is a key element in achieving high resolution. A mechanical brake can still be implemented 

without interfering with the FDHC-100 operation. Mechanical brakes can be useful for providing a holding 
brake in the event power to the actuator is lost.  Since the Electronic Brake feature provides the 

primary braking of the motor, the life of a mechanical brake is dramatically extended. Additionally, the 

Adaptive Control feature of the FDHC-100 automatically compensates for changes in a mechanical 

brake’s performance due to temperature or age.  Note that the actuator’s limit switches should be set 
outside of the operating range set by the CLOSE and OPEN functions. The Electronic Brake feature 

degrades in performance if a limit switch is engaged. Limit switches exhibit wide variations, and the 

FDHC-100 can position the actuator more precisely at 

closed 

and 

open 

than the limit switches. A limit 

switch serves better as a fail safe device to protect against electrical failures in the actuator. 

 

DUTY CYCLE CONTROL FEATURE  

The Duty Cycle Control feature of the FDHC-100 allows actuators rated at 25% duty or more to be 

safely used in automated valve applications. The FDHC-100 accurately monitors the relative heating of 
the motor and automatically duty cycles the unit at a safe level when a process becomes unstable, or if a 

control loop is not properly set. While the thermal switch in the motor protects the motor from 

overheating, thermal switches can shutdown the actuator for ten minutes or more. Further, typical 

thermal switches do not activate until temperatures inside the actuator become too high for other 

components in the actuator.  The Duty Cycle Control feature allows continuous operation of the motor 

Summary of Contents for FDHC-100

Page 1: ...lt relay contact or digital communications A wide range of data is accessible through a digital communications module providing additional control or information The unit is of single solid construction and is easily mounted with two screws The FDHC 100 is interchangeable with the AMC and LRC standard size controllers and can be used to upgrade performance for those applications FEATURES Positions...

Page 2: ... Operation Manual FDHC 100 Configuration Operation Man Rev 0 August 16 2010 2 of 14 Flomatic Corporation Glens Falls NY 12801 Phone 518 761 9797 Fax 518 761 9798 Digital High Resolution OUTLINE FDHC 100 FDHC 100C 117VAC CE ready FDHC 100A FDHC 100D 234VAC FDHC 100B FDHC 100E 24VAC CE ready ...

Page 3: ...mes in three versions to accommodate different voltage applications The FDHC 100 and FDHC 100C are rated for 117 VAC 10 the FDHC 100A and FDHC 100D are rated for 234 VAC 10 and the FDHC 100B and FDHC 100E are rated for 24 VAC 10 The unit is easily mounted with 2 screws and is equipped with removable screw terminals that provide for easy field wiring The unit s size mounting and screw terminals are...

Page 4: ...rovides an auxiliary 5V output which can be used to connect a command potentiometer By connecting one end of a potentiometer to pin 7 the other end to pin 4 and the wiper to pin 6 a local control knob can be implemented Pin 8 provides an auxiliary 15VDC output which can be used to power an input or output 4 20mA transmitter ACTUATOR J1 The actuator motor and feedback potentiometer are connected to...

Page 5: ...l Pot Cal indicator will turn on steady to indicate that the unit is being controlled by the Override Input Shorting J7 pin 1 to pin 2 returns the unit to normal operation and the previously selected mode Note that earlier models may not have connector J7 and therefore do not have the OVERRIDE mode feature Controlling the FDHC 100 from the Override Input is accomplished by connecting a specific re...

Page 6: ...ed when using one of the analog command types and can be used to override the analog command The AUTO indicator will flash whenever the unit is being controlled by the communications module MANUAL FB POT CAL The MANUAL FB POT CAL function allows manual operation of the actuator by using the adjust buttons and without affecting any other settings within the FDHC 100 When the button is pressed the m...

Page 7: ... used to drive an alarm or merely act as an auxiliary limit switch Upon selecting the AUX CLOSE OUTPUT function the FDHC 100 will begin moving the actuator to the previously set position It is not necessary to make an adjustment if the unit has been previously set to the desired position AUX OPEN OUTPUT The AUX OPEN OUTPUT function is used to set an optional output setting that is associated with ...

Page 8: ... can be adjusted using the adjust buttons to any value from 0 to 10V for a voltage output or 0 to 20mA for a current output The new setting is then associated with the closed position Pressing the MODE button again will leave the unit in the AUX POSITION OUT CAL function except that the OPEN indicator will flash and the output voltage or current associated with the open position will appear at the...

Page 9: ...hes employed in actuators essentially disconnect one of the motor windings The FDHC 100 will detect this as a motor stall To avoid this condition the limit switches must be set outside of the operating range set by the CLOSE and OPEN functions ELECTRONIC BRAKE FEATURE The Electronic Brake feature of the FDHC 100 provides highly reliable and accurate braking of the motor and it is a key element in ...

Page 10: ...resume continuous operation The duty cycle period is approximately 2 seconds with an on time that automatically various depending on the heating of the motor While this operation slows down the actuator s operation it does not impact the resolution performance of the FDHC 100 and it prevents disruption of a process due to a thermal switch shutdown OPTION MODULES Various option modules can be plugg...

Page 11: ... 8 125mA maximum not including option module 5V OUT J2 7 5mA maximum NOTE Do not connect these outputs to other power supplies AC MOTOR OUTPUTS Off state Leakage Current 15mA Maximum Load Current 60 C 5A ENVIRONMENTAL Operating Temperature Range 0 C to 60 C Storage Temperature Range 40 C to 85 C Relative Humidity Range 0 to 90 non condensing CE CERTIFICATION FDHC 100D only EN55011 Class A RF Emiss...

Page 12: ...roller Configuration and Operation Manual FDHC 100 Configuration Operation Man Rev 0 August 16 2010 12 of 14 Flomatic Corporation Glens Falls NY 12801 Phone 518 761 9797 Fax 518 761 9798 FDHC 100 FDHC 100 FDHC 100 FDHC 100 WIRING DIAGRAMS Input Signal Configurations ...

Page 13: ...roller Configuration and Operation Manual FDHC 100 Configuration Operation Man Rev 0 August 16 2010 13 of 14 Flomatic Corporation Glens Falls NY 12801 Phone 518 761 9797 Fax 518 761 9798 FDHC 100 FDHC Series FOTR 100 Option Module WIRING DIAGRAMS Special Applications ...

Page 14: ...er Configuration and Operation Manual FDHC 100 Configuration Operation Man Rev 0 August 16 2010 14 of 14 Flomatic Corporation Glens Falls NY 12801 Phone 518 761 9797 Fax 518 761 9798 FDHC Series FDHC Series FAMM 100 FAMM 100 WIRING DIAGRAMS Special Applications continued ...

Reviews: