Flomatic CYCLE GARD I C152E Installation Instructions Download Page 1

 

Cycle Gard® I 

Installation Instructions 

Model C152E  ½” thru1-¼” 

Flomatic Corporation

 

Flomatic Corp, 15 Pruyn’s Island, Glens Falls, New York 12801 

Phone: 518-761-9797           Fax: 518-761-9798        www.flomatic.com 

C152E 

Rev. 10 (10/17) 

 

ADJUSTING SCREW

JAM NUT

COVER

FRICTION RING

SPRING

BODY

CARTRIDGE ASSEMBLY

UNION END

UNION DISC

UNION NUT

SPRING BUTTON

FLOMATIC 

VALVES

 

NOTICE:  Annual inspection and maintenance is required of all plumbing system 
components.  To ensure proper performance and maximum life, this product 
must be subject to regular inspection, testing and cleaning. 
Regulators in series:  Where the desired pressure reduction is more then a 4 to 1 
ratio (i.e.. 200psi to 50psi), multiple regulators in series should be installed. 
DIAPHRAGM WARNING:  Loosen jamb nut and adjustment screw slowly.  Look 
for any trapped water pressure under the diaphragm.  Relieve pressure before 
removing cover. 
CAUTION:  Anytime a reducing valve is adjusted, a pressure gauge must be used 
downstream to verify correct pressure setting.  To properly adjust the 
downstream pressure there needs to be flow through the valve in the direction of 
the flow arrow on the body.  Do not bottom out adjustment screw on cover.  
Valve may be installed in any position. 
 
NOTE:  Motor manufacturers recommend using a flow sleeve to be sure the 
motor is properly cooled at low flow rates.  Do not exceed 125 psi pressure 
differential across the valve. 
 
INSTALLATION INSTRUCTIONS: 
 

1. Before installing reducing valve, flush out line to remove loose dirt and scale which might damage disc and seat and 
turn power off.  Install valve in line with arrow on valve body pointing in direction of flow.  If the valve is equipped with (2) 
union ends if only one is required, install the union end on the downstream side regulated pressure side of valve. 
 
2.  Install the valve downstream of the 
pump and before the pressure switch 
and tank.  

Note:  If there are any 

water outlets such as yard hydrant 
of supply between the pump and 
Cycle Gard ® I install a by-pass with 
a check valve around the valve.  

Warning- This pressure will be 
unregulated pressure. Not 
recommended for high capacity and 
pressure pumps.  

The check valve 

shall be installed with flow going in 
the opposite direction of the Cycle 
Gard® I. this allows for free flow 
around the Cycle Gard® I unit to 
provide tank pressure to the yard 
hydrant or outlet (see illustration). 

 
3.  Pre-charge pressure in the tank should be 5 to 10 psi lower than pressure switch turn on pressure.  All valves are 
factory pre-set to 50 psi.  To re-adjust reduced pressure loosen outer jam nut and turn adjustment screw clockwise (into 
cover) to increase downstream pressure, or turn counterclockwise (out of cover) to lower downstream pressure.  Valve 
may be installed in the horizontal or vertical position.  Open a line downstream and allow pump to turn on, then slowly 
close supply valve downstream until demand is roughly around 2 to 3 GPM.  Then adjust the valve until the downstream 
pressure is constant, at about 10 psi lower then the cut off pressure of the pressure switch setting.  Close off 
downstream valve and the pressure tank will fill up at about 1 GPM at 50 PSI differential, 1.5 GPM at 100 PSI differential 
for the 

1” and 1-1/4” only.

 

 
Note:  In systems using a small tank with 5 gallons or less of drawdown, adjust the regulated downstream valve 
pressure to the same as the cut in (pump on) pressure setting of the pressure switch.  For example if your system is 
using a 40/60 pressure switch setting set your regulated downstream valve pressure at 40 psi.  For longer run rimes set 
your regulated pressure closer to the cut on (pump on) pressure setting on the pressure switch. 
 

NOTE:

   All Cycle Gard® type of 

valves need to be located within 
close proximity to the tank and 
pressure switch