Troubleshooting Guide
CN-IC1-09
Title
:
i-Controller REV.200 Alarms (Troubleshooting)
EXTERNAL
9
1-19MAY2021
Heat Reclaim Notice (if equipped)
A heat reclaim or reheat notice is generated when
the supply temperature has not increased at least 5˚F after heat reclaim
or reheat has been enabled for 15-minutes.
When a heat reclaim notice is generated, “
YES
” will be displayed next to
“
Reclaim Proof
” on the
Alarms
screen.
When heat reclaim has been disabled, the heat reclaim notice will automatically reset.
Heat Reclaim
Notice Present
Reclaim Active?
•
Verify compressors operation
•
Verify unit is equipped with heat
reclaim
•
Verify heat from refrigeration
system is available to unit
•
Verify supply temperature
sensor is present
•
Verify supply sensor is installed
•
Verify supply sensor connection
to input
Yes
No
•
Verify the alarm input points
on the board or controller
•
Verify the unit is in DEHUM
•
Check wiring and connections
Alarm cleared?
Contact Tech
Support
1-888-598-1198
No
Issue resolved
Check to see if unit is in
Dehumidification
Mode
Yes