background image

CT70   V7.0  09/10 

Test 3: Voltage Drop Measurements 

To determine voltage drop, the CT70 measures line voltage, factors in the load, measures 
the loaded voltage, and then calculates the voltage drop. Results for 12A, 15A, and 20A 
loads are provided. For nominal efficiency, a voltage drop of 5% is the maximum 
recommended by the National Electrical Code (NEC) board. When a voltage drop 
measurement of less than 5% is made, the meter’s display backlight turns blue in color. If 
the voltage drop is higher than 5%, the meter display appears in red. 
An efficient branch circuit should have less than 5% voltage drop at the furthest receptacle 
from the breaker panel at the termination of the cable run. A steady decrease in the voltage 
drop should then be measured for each receptacle tested in sequence towards the breaker 
panel. 
If the voltage drop is higher than 5% and does not noticeably decrease as the testing 
moves closer to the first device on the circuit, then the problem lies between the first device 
and the breaker panel. Visually check the terminations at the first device, the wiring 
between the device and the panel, and the circuit breaker connections. 
High resistance points can be identified as hot spots using an infrared (IR) thermometer or 
by measuring the voltage across the breaker. If a voltage drop measurement exceeds 5% 
but noticeably decreases as the testing moves closer to the panel, then the circuit may have 
an undersized wire, too long of a cable run, or excessive current on the circuit. Check the 
wires to ensure that they are sized per code and measure the current on the branch circuit. 
If a voltage drop reading changes significantly from one receptacle to the next, then the 
problem could be a high impedance point at or between two the receptacles. It is usually 
located at a termination point, such as a bad splice or loose wire connection, but could also 
be a faulty receptacle. 
 

Voltage Drop Measurement Troubleshooting Suggestions 

Problems Likely 

Causes 

Possible Solutions 

Voltage drop > 5% 

Overloaded circuit 

Redistribute loads 

Wrong wire gauge size for 
length of cable run 

Check code and rewire if 
necessary 

High resistance connection 
in the circuit or at the panel 

Locate bad connection and 
rewire or replace 

 

Test 4: ASCC Measurements 

The CT70 calculates the ASCC (Available Short Circuit Current) that a branch circuit can 
deliver through a breaker in a dead short circuit condition. 

 

The ASCC is calculated by dividing the line voltage by the circuit’s line impedance. See 
equation below: 

ASCC = Line Voltage / Hot imp Neutral impedance 

Use the 

 button to simulate a situation where all three conductors (hot, neutral, and 

ground) are shorted together. Note that this second test will trip a GFCI. 
 

 

 

Summary of Contents for Extech Instruments CT70

Page 1: ...User s Guide AC Circuit Load Tester Model CT70...

Page 2: ...increase power quality performance This meter is shipped fully tested and calibrated and with proper use will provide years of reliable service Features True RMS measurements Voltage drop measurements...

Page 3: ...ton 8 GFCI test button Display Description A Amperes Current V Voltage Vd Voltage Drop Percent Voltage Drop VL Voltage load Z Impedance Hz Hertz cycles per second Ohms Resistance mS Milliseconds ASCC...

Page 4: ...ment Results Important note The CT70 is a microprocessor controlled device that prioritizes its tasks Taking a reading and analyzing the results are its top priorities This is why at times the keypad...

Page 5: ...uctor impedances Use the button to move through the sub menu Note that testing ground impedance will trip a GFCI circuit The ASCC window indicates the Available Short Circuit Current that the branch c...

Page 6: ...tage reading Ground to neutral voltage should be less than 2 VAC in which case the display backlight will appear blue in color if ground to neutral voltage is greater than 2 VAC the backlighting appea...

Page 7: ...he voltage across the breaker If a voltage drop measurement exceeds 5 but noticeably decreases as the testing moves closer to the panel then the circuit may have an undersized wire too long of a cable...

Page 8: ...unding to adequately protect against transient voltages Note A small amount of current is applied to the ground conductor during impedance measurements and can trip a GFCI circuit High Impedance Troub...

Page 9: ...time specified by UL recommendations the meter s display will switch off because the power has been removed by the GFCI circuit 6 When the GFCI circuit is reset the CT70 will display the elapsed time...

Page 10: ...normally be used to test a standard GFCI 6 to 9mA A good EDP GFCI circuit will sense this imbalance and switch off the power The CT70 displays the current value in mA To test an EPD GFCI circuit 1 Pl...

Page 11: ...1 mm Weight 11 2 oz 317 5g Safety approvals CE ETL General safety For indoor use and in accordance with the requirements for double insulation to IEC1010 1 2001 EN61010 1 2001 Overvoltage Category II...

Page 12: ...210 for authorization or visit our website www extech com for contact information A Return Authorization RA number must be issued before any product is returned to Extech The sender is responsible fo...

Reviews: