background image

Kabelanschlusskasten Typ KPK   Technisches Handbuch, Rev. 1.01   September 2016 
Junction Box             Type KPK  Technical Manual

 

Seite / Page 8/8  

O

UTPUT 

C

ABLE 

C

ONNECTION

 

The signal cable (connection between junction box and the following electronics) should be a 6 

– wire 

shielded cable and has to be kept as short as possible. Because this cable usually has a larger diameter than 
the load cell cable, you should use the larger cable gland in the middle of the box. Depending on type and 
manufacturer signal cables may have different colours. Therefore make your own choice. 

 

Cable colour, example 

Description / Terminal designation 

outer cable screen 

=  Shield 

pink 

=  Signal 

–  (Output –) 

white 

=    () 

grey 

=  Sense 

– 

brown 

=  Excitation 

–  (Input –) 

yellow 

=  Sense + 

green 

=  Exci (Input +) 

 

C

ORNER 

C

ORRECTION AT 

S

CALES WITH 

F

LINTEC 

L

OAD 

C

ELLS

 

Flintec load cells are manufactured with rather tight tolerances, so in most cases an additional corner 
correction is not required. The best conditions are achieved if you use load cells of the same class 
(Designation is done with capital letters A to I on the load cell package besides the type label). 
Hint: Corner errors can have a mechanical background, e.g. sloped mounting surface of the load cell. 

 

Procedure: 
8.  The jumpers JP1 to JP4 should stay installed. This will disable the potentiometers. 
9.  The 0 Ohm jumpers instead of the correction resistors must be in place (shipment status). 
10.  Get the display value for each corner. Use the highest possible display resolution (e.g. factor 10 or higher) 

or, if this is not possible, measure the the digital weight increment using corresponding weights. 

11.  The corner with the lowest display value is the starting point for the corner correction. The differences of 

the other corners are calculated with reference to th

is “basic corner”. 

12.  Calculate the correction resistance as follows: 

 

Correction resistance 

[

]  =

 

Deviation in [kg] 

 X  Input resistance of the load cell [

] * 

Test load in [kg] 

 

* 1100 

 input resistance for: 

BK2, SB4, SB5, SB6, SB14, SLB, ZLB, UB1, UB5, UB6, PB, RC3 

    400 

 input resistance for: 

RC1, SB2 

 

Example 1:

  1100 

 load cell 

0.1 kg corner error with 500 kg test load 

0.1 kg 

1100 

 

0.22 

 

500 kg 

 

Example 2:

  400 

 load cell 

10 kg corner error with 5000 kg test load 

10 kg 

400 

 

0.8 

 

5000 kg 

 

 

13.  Install the correction resistor into the junction box instead of the 0 Ohm jumper for the corresponding load 

cell excitation OR adjust the potentiometer (see below). 

14.  Check the corners again. If required repeat the procedure. 
 
Hint: 50 ppm resistors for corner correction are available as a set of 14 values from 0.22 

 to 4.7 

 (10 pcs. 

for each value; article no. 5200-030). 

 

Correction by Potentiometer Adjustment 
The calculated correction resistance is also used as the starting point when the correction is made with the 
potentiometers P1 to P4 (25 turns, 10 Ohm Cermet- precision trimmer). When shipped all potentiometers are 
in the middle position (appr. 5 Ohm) and disabled by the jumpers JP1 to JP4 (short-circuit). If a potentiometer 
shall be enabled, the corresponding jumper JPx has to be removed. 
First you have to turn the potentiometer to the clockwise end position (clicking noise). Afterwards you turn the 
potentiometer counterclockwise until the computed correction resistance is adjusted. 

 

Hints for Poti 
adjustment: 

 

Use suitable screwdriver ! 

 

One turn corresponds to appr. 0.4 Ohm 

 

Clockwise end position = 0 Ohm 

 

Counterclockwise end position = 10 Ohm 

 

 

 

0 Ohm jumpers instead of correction resistors must stay in place 

 

In the junction box you can also find a dry tablet in a plastic bag. Open the bag and leave the tablet in the 
junction box. This will absorb moisture up to a certain degree. Check the cover sealing and install the cover of 
the box. 

 

Summary of Contents for KPK-4

Page 1: ...Kabel Anschlusskasten Junction Box Typ KPK 4 Type KPK 4 Technisches Handbuch Technical Manual Flintec GmbH Bemannsbruch 9 74909 Meckesheim GERMANY www flintec com...

Page 2: ...echanische Installation 4 Elektrische Anschl sse 4 Anschluss der W gezellenkabel 4 Anschluss des Ausgangskabels 5 Eckenabgleich bei Waagen mit FLINTEC W gezellen 5 Table of contents RIGHTS AND LIABILI...

Page 3: ...ungsanleitungen angefallen sind FLINTEC kann nicht haftbar gemacht werden f r Sch den oder Probleme die durch die Anwendung von Zubeh r oder anderen Verbrauchsg tern enstanden sind die nicht als origi...

Page 4: ...es ist eine elektrisch leitende Verbindung zu den W gemodulen herzustellen Potentialausgleich Die Anschlussreihenfolge der W gezellen sollte mit den Ecken der Waage bereinstimmen also Ecke 1 W gezelle...

Page 5: ...t ist der Ausgangspunkt f r die nun anschlie ende Korrektur Dementsprechend wird die Differenz der anderen Ecken in Bezug auf diese Basisecke errechnet 5 Berechnung des Korrekturwiderstandes wie folgt...

Page 6: ...duct or failure to strictly comply with FLINTEC operating and maintenance instructions FLINTEC shall not be liable against any damages or problems arising from the use of any options or any consumable...

Page 7: ...ectrical connection to the weigh modules for potential equalisation The connection sequence of the load cells should correspond to the corners of the scale i e Corner 1 Load cell 1 Corner 2 Load cell...

Page 8: ...re calculated with reference to this basic corner 12 Calculate the correction resistance as follows Correction resistance Deviation in kg X Input resistance of the load cell Test load in kg 1100 input...

Reviews: