PRE INSTALLATION  CHECKLIST  -  ALL  INSTALLATIONS

 

1.   Check to be sure your power source is capable of 

handling the voltage requirements of the motor, as 

indicated on the pump name plate.

2.   Vent hole purpose.  It is advisable that all submersible 

sump pumps be of the bottom intake design to reduce 

clogging and seal failures. If a check valve is incorporated  

in  the  installation,  a  vent  hole  (approx. 3/16") must 

be drilled in the discharge pipe below the check valve 

and pit cover to purge the bottom intake unit of trapped 

air. Trapped air is caused by agitation and/or a dry 

basin. This vent hole should be checked periodically 

for clogging. Water stream will be visible from this hole 

during pump run periods.

3.   Maximum continuous operating water temperature for 

standard model pumps must not exceed 104°F (40°C).

Note

: Pumps with the "cCSAus" mark are tested to UL Stan-

dard UL778 & CSA Standard C22.2 No. 108.

FW1260

0719

Supersedes

1018

DO NOT USE FOR PUMPING OILS, 

GASOLINE OR ANY PETROLEUM  

BY-PRODUCTS.

Notice to Installer:  Instructions must remain with installation.

Product information presented 

here reflects conditions at time 

of  publication. Consult factory 

regarding discrepancies or 

inconsistencies.

1.  Inspect your pump.

 Occasionally, products are damaged during shipment. If the unit is damaged, contact your dealer 

before using. 

Do Not

 remove the test plug in the cover.

2.  Carefully read the literature

 provided to familiarize yourself with specific details regarding installation and use. 

These materials should be retained for future reference.

1.   To reduce the risk of electric shock, install only a circuit 

protected by a ground-fault circuit-interruptor (GFCI).  All 

pumps are furnished with provisions for proper grounding to 

help protect you against the possibility of electrical shock.

2.   Make certain that the ground fault receptacle is within the 

reach of the pump’s power supply cord DO NOT USE AN 

EXTENSION CORD.  Extension cords that are too long or 

too light do not deliver sufficient voltage to the pump motor.  

But, more important, they could present a safety hazard if 

the insulation were to become damaged or the connection 

ends were to fall into the basin and become wet.

3.   Make sure the pump electrical supply circuit is equipped 

with fuses or circuit breakers of proper capacity.  A separate 

branch circuit is recommended, sized according the 

National Electrical Code for the current shown on the pump 

name plate.

4.   TESTING FOR GROUND. As a safety measure, each 

electrical outlet should be checked for ground using an 

Underwriters Laboratory Listed circuit analyzer which will 

indicate if the power, neutral and ground wires are correctly 

connected to your outlet. If they are not, call a qualified 

licensed electrician.          

5.   Installation and checking of electrical circuits and hardware 

should only be performed by a qualified licensed electrician.

6.   FOR YOUR PROTECTION, ALWAYS DISCONNECT PUMP 

FROM ITS POWER SOURCE BEFORE HANDLING.

7.   These pumps are supplied with a 3-prong grounded plug to 

help protect you against the possibility of electrical shock.  

DO NOT UNDER ANY CIRCUMSTANCES REMOVE THE 

GROUND PIN.  The 3-prong plug must be inserted in a 

mating 3-prong fault interrupter receptacle.  If the installation 

does not have such a receptacle, it must be changed to the 

proper type, wired, and grounded in accordance with the 

National Electrical Code and all applicable local codes and 

ordinances.

8.   Risk of electric shock. This pump has not been investigated 

for use in swimming pool or marine areas.

9.   According to the state of California (Prop 65), this product 

contains chemicals known to the state of California to cause 

cancer and birth defects or other reproductive harm.

SEE BELOW FOR LIST OF CAUTIONS

SEE BELOW FOR LIST OF WARNINGS

INSTALLATION INSTRUCTIONS

These installation instructions are applicable for Model 50TCPPC, ECP552PC, ECP752PC