background image

1

INSTRUCTIONS

67589 01/16 (LOA)

English

The thermostat is an electronic on/off thermo-

stat for temperature control of electric under-

floor heating by means of an NTC sensor. 

The thermostat has a built-in two-pole ground 

fault circuit interrupter (GFCI, Class A). The 

thermostat and GFCI are suitable for 120-240 V 

(incl. 208 V) 50/60 Hz power supplies.

The thermostat is for flush mounts in a wall 

socket.

Product programme 

FLK30-120/240GA (UTN-4991) 
Non-programmable thermostat incl. floor sensor

Warning

 To avoid electric shock, disconnect 

the heating system power supply  

at the main panel before installation 

and maintenance of the thermostat. 

Keep thermostat air vents clean and free from 

obstruction. This thermostat is an electrical 

device and must be installed in compliance with 

national and/or local electrical codes. Instal-

lation must be performed by qualified personnel 

where required by law.

The thermostat is designed for resistive load 

only. The resistive load must not exceed 15 A 

(1800 W at 120 Vac / 3120 W at 208 Vac / 3600 

W at 240 Vac).

Warning

Do not loosen the terminal screws  

further than the mechanical stop.  

Otherwise this will damage the termi-

nal (fig. 2).

Mounting of thermostat 

Temperature sensor

1. 

 Use a screwdriver to release the catch and 

remove the front cover (fig. 1).

2. 

 Connect the floor sensor to the terminals 

marked “sensor”, terminals C and D (fig. 5).

3. 

Mount the thermostat in the wall socket.

4. 

 Carefully replace the front cover by first 

positioning its upper edge and then clicking 

it into place.

Line cable

Delivers power from the service panel (breaker 

panel or fuse box) to the thermostat.

This cable must only be connected to the ther-

mostat’s line terminals, marked L1 and L2.

1. 

Connect power cable to terminals 2 and 3 

on the back of the thermostat (fig. 2).

Load cable

Delivers power from the thermostat to the heat-

ing cable.

This cable must only be connected to the ther-

mostat’s load terminals, marked load 15 A.

1. 

Connect heating cable to terminals 1 and 4 

on the back of the thermostat (fig. 2).

2. 

The detachable cover on the back of the 

thermostat (fig. 1) is designed to prevent 

uninsulated ground wires from dropping 

onto the terminals after installation has been 

completed.

Mounting of floor sensor (fig. 3)

Floor sensor is supplied from SELV (Safety 

Extra low Voltage) Circuit, allowing the sensor 

to be placed as close to the floor surface as 

desired without having to take special account 

to the risk of shock at the damage to the sensor 

cable. It is not intended that the temperature 

sensor wire shall enter through the wall socket 

mounting box. The sensor cable shall be sep-

erated from LINE and LOAD cables.  Can be 

separated in conduite, inside or outside the 

wall. (see fig. 6) 

Recommended placed in an non conductive 

installation pipe, which is embedded in the 

floor. (fig. 3). The pipe must be sealed in the end 

and placed as high as possible in the concrete 

layer. The sensor cable shall be placed in a sep-

arate pipe or be separated from power cables.

The floor sensor must be centered in between 

the heating cable. 

The sensor cable can be extended up to 90 ft 

(30 m) by means of a separate two-core cable. 

Two remaining cores of a multi-core cable 

which, for example, supplies current to the floor 

heating wires, must not be used. The two-core 

cable must be placed in a separate pipe or be 

separated from power cables.

Other approved floor sensors may be used if 

they comply with the technical specifications 

(see fig. 4).

Operation

The actual temperature setting is shown and the 

thermostat is ready for use.

Checking the GFCI

It is important that the GFCI is checked for cor-

rect installation and function upon installation 

and monthly thereafter.

To check the GFCI:

Press the “TEST” button.

The test is successful if the red LED on the 

right of the thermostat flashes once every two 

seconds and “GROUND FAULT” appears on 

the display. If this does not occur, check the 

installation.

Press the “Standby/Reset” button to reset the 

GFCI.

The red LED will stop flashing and the display 

returns to its normal appearance.

If the test fails, repeat the test. If it continues to 

fail, ask an electrician to check the installation.

If, during normal operation, the GFCI/ trips 

without the “TEST” button being pressed, there 

could be a ground fault! To check whether it 

is a ground fault or nuisance tripping, press 

“Standby/Reset”. If this causes the red LED to 

stop flashing and stay off, it was nuisance trip-

ping and the system is operating correctly. If 

this does not occur, there is a ground fault! In 

case of a ground fault, it is important to have 

the installation checked by a qualified electri-

cian according to local and national regulations.

The red LED on the right of the thermostat can 

indicate four different GFCI states:

1.  LED off – NORMAL state.

2.  LED flashing slowly (once every two sec-

onds) – TRIGGERED state. Try pressing the 

“Standby/Reset” button to reset the GFCI.

3.  LED flashing quickly (five flashes per sec-

ond) – ERROR state. Try switching the pow-

er off and then back on again. If the thermo-

stat re-enters the ERROR state, either the 

wiring is wrong (a GN exists) or the unit is 

defective and must be replaced.

4.  LED lit constantly – Internal microprocessor 

malfunction or abnormal fault in hardware! 

Try switching the thermostat off and then 

back on again. If the LED is still constantly 

lit, the GFCI is defective and the thermostat 

must be replaced.

Note: The LED lights up briefly without flashing 

during every power-up.

Fault location

If the sensor is disconnected or short-circuited, 

the heating system is switched off. The sensor 

can be checked against the resistance table 

(fig. 4).

Error codes

E0: Internal error. The thermostat must be 

replaced.

E2: External sensor short-circuited or discon-

nected.

UL Listed for the US and Canada

According to the following standards: 

Thermostat:  

UL 60730-1

 

UL 60730-2-9

 

CSA E60730-1:13

 

CSA E60730-2-9

UL file number:  E157297 

GFCI:  

UL 943 4th ed.

 

CSA C22.2 No. 144.1-06

Classification

The product is a class II device (reinforced insu-

lation) and must be connected to the following 

leads:

Phase L1 (L) 

120V 

Neutral L2 (N)  0/120 V

Max. load 15 A (resistive load).

The thermostat is intended to be used with 

underfloor heating.

The terminals are suitable for field wiring cables 

of 12 to 22 AWG. 

Technical data

Supply   ........................... 120/240 Vac 50/60 Hz

Load 

 .......................max. 15 A (resistive load)

Power    ................................1.800 W at 120 Vac

               ................................3.120 W at 208 Vac

               ................................3.600 W at 240 Vac

GFCI   ......................... Class A (5 mA trip level)

Temperature range  ........................ +5 to +40°C, 

+41 to +104°F

Français

Le thermostat est un thermostat électronique 

marche/arrêt pour le contrôle de la température 

d’un plancher chauffant par une sonde NTC.  

Le thermostat possède un disjoncteur diffé-

rentiel de fuite à la terre intégré à deux pôles 

(DDFT, classe A). Le thermostat et le disjoncteur 

de fuite à la terre intégré sont conçus pour des 

alimentations à 120-240 V (y compris 208 V) et 

50/60 Hz.

Le thermostat est conçu pour un montage 

affleurant dans un boîtier mural.

Type FLK30

© 2016 OJ Electronics A/S

Reviews: