19
Capacity
The diagrams for Aero 100 / 125 also apply to the respective sound absorption valves.
Sound absorption (
D
n,e,w)
Model
200 mm
300 mm
400 mm
400 mm with
baffel
Aero 100 dB
40
44
46
48
Aero 125 dB
39
42
45
47
Supplementary data is available in the Flexit brochure and on our website.
Installation
The valve should be installed high on the wall, preferably close to a heat source.
1.
Hole making
The fall outwards should be around 1°.
For Ø100 and Ø125 it is recommended to use a hole making tool to obtain clean edges (Fig. 1 page 21). For Ø160
and sound absorption valves it is recommended to use a compass saw on account of the high torque in the drill
(Fig. 2 page 21).
Recommended hole dimensions in accordance with the table:
Model
Pipe diameter
Hole
Aero 100 Fresh Air Valve
104 mm
110 mm
Aero 125 Fresh Air Valve
124 mm
130 mm
Aero 160 Fresh Air Valve
160 mm
170 mm
*
**
Aero 100 dB
175 mm
185 mm
*
**
Aero 125 dB
195 mm
205 mm
*
* 2 cover plates are supplied, producing greater tolerances for hole making.
** It is possible to install the valve without cover plates but the holes must then be made very precisely.
-
10
20
30
40
50
60
-
10
20
30
40
50
60
70
80
90
100
110
120
Pr
es
su
re
, P
a
-
5
10
15
20
25
30
Opening 25 %
Opening 50 %
Opening 100 %
m
3
/h
l/s
Pr
es
su
re
, P
a
Opening 25 %
Opening 50 %
Opening 100 %
m
3
/h
l/s
10
20
30
40
50
60
0
10
20
30
40
50
60
70
80
90
100 110
120 130
5
10
15
20
25
30
35
-
10
20
30
40
50
60
-
10
20
30
40
50
60
70
80
90
100
m
3
/h
P
re
ss
u
re
,
P
a
-
4
8
12
16
20
24
28
l/s
Opening 25 %
Opening 50 %
Opening 100 %
Capacity Aero 100
Capacity Aero 160
Capacity Aero 125