1.1 

CONDITIONS OF INSTALLATION

In Great Britain :-

It is law that all gas appliances are installed only by a CORGI registered installer in
accordance with these installation instructions and the Gas Safety (Installation and
use) Regulations 1998. Failure to install appliances correctly could lead to prose-
cution. It is in your own interest and that of safety to comply with the law.
The installation must also be in accordance with all relevant parts of the Local and
National Building regulations where appropriate, the Building Regulations
(Scotland Consolidation) issued by the Scottish Development Department, and all
relevant recommendations of the following British Standard Code of Practice.

1.

B.S. 5871.  Part 3. Installation of Gas Fires.

2.

B.S. 5440.: 2000  Parts 1 & 2.  Installation of Flues & Ventilation.

3.

B.S. 6891.  Installation of Gas Pipework.

4.

B.S. 6461.  Part 1.  Installation of Chimneys & Flues.

5.

B.S. 1251.  Open Fireplace Components.

6.

B.S. 715.    Metal Flue pipes for Gas Appliances.

7.

B.S. 1289   Clay Flue blocks and Terminals.

8.

B.S. 7566   Installation of factory-made Chimneys.

In Republic of Ireland :-

For use in I.E. this appliance must be installed in accordance with the rules
in force and used only in a sufficiently ventilated space.  Please consult doc-
ument  I.S. 813 : 1996 Domestic Gas Installation
, issued by the National
Standards Authority of Ireland.

1.2

FLUE AND CHIMNEY SUITABILITY

The appliance is designed for use with conventional brick built chimneys or lined
chimneys and pre – fabricated flues. It is also suitable for use with pre-cast flue
blocks conforming to B.S. 1289 and metal flue boxes conforming to BS 715. All
flues must conform to the following minimum dimensions.

Minimum diameter of circular flues

125 mm 

Minimum effective height of all flue types

3 metres

Minimum cross sectional area of Pre-cast Flues

122.7 cm2

4

Summary of Contents for FRCS3G

Page 1: ...ing spares co Tel 0161 620 6677 STRATA Installation and Maintenance Instructions Hand these instructions to the user Model No s FRCS3G FRCS4G are only for use on Natural Gas G20 at a supply pressure o...

Page 2: ...es 7 1 8 3 Fitting to Pre Cast Flue Installations 8 1 9 Hearth Fitting 8 1 10 Wall Mounting 8 1 11 Spillage Monitoring System 8 Section 2 2 1 Packing Check List 8 2 2 Installation of Fire 8 12 2 3 Gas...

Page 3: ...s Heat Input 6 9 kW Min Gross Heat Input 2 5 kW Cold Pressure 20 0 1 0 mbar 8 0 0 4 in w g Ignition Rotary piezo integral to gas valve Electrode Spark Gap 4 0 mm Weight Packed 20 kg Firebox Dimensions...

Page 4: ...Ventilation 3 B S 6891 Installation of Gas Pipework 4 B S 6461 Part 1 Installation of Chimneys Flues 5 B S 1251 Open Fireplace Components 6 B S 715 Metal Flue pipes for Gas Appliances 7 B S 1289 Clay...

Page 5: ...f the fire and the shelf does not project more than 150 mm If the shelf overhangs more than 150 mm the distance between the fire and the shelf must be increased by 15 mm for every 25 mm of additional...

Page 6: ...cture of the chim ney during or after the smoke pellet test and it is important to check inside upstairs rooms adjacent to the chimney flue Check the chimney pot terminal and gener al condition of the...

Page 7: ...tchment Space 1 8 2 Fitting to Pre Fabricated twin wall metal Flue Boxes The appliance may be fitted to a twin wall metal flue box conforming to the constructional requirements of BS 715 for example t...

Page 8: ...rds from the fire opening 1 10 WALL MOUNTING The fire can be fitted to non combustible walls The base of the fire must be at least 150mm above the floor level with the top of the fire place opening be...

Page 9: ...way See Fig 2 Take care not to scratch the trim b Remove the radiants and their packaging from inside the fire and store in a safe place c Remove the two lower outer case fixing screws See Fig 3 and t...

Page 10: ...Case Fixing Screws f Remove the flue spigot restrictor if the fire if the fire is the to be fitted to a pre cast flue The flue spigot restrictor is attached to the fire back with two screws g Fit the...

Page 11: ...into the open ing the chimney may require attention DO NOT FIT THE FIRE SEEK EXPERT ADVICE Hearth Fitting a The feet must be fitted when hearth fitting Note When the fire is to be fitted onto a very...

Page 12: ...s supplied d Offer the fire to the wall and push the spigot on the rear of the fire through the opening in the closure plate e Fit the 4 screws through the holes in the firebox back panel and tighten...

Page 13: ...the base of the radiants into the radiant support channel b Pull off the control knob c Fit the outer case by hooking rear edge of the case over the retaining lugs at each end of the rear panel d Ens...

Page 14: ...rance of combustion products Fig 6 e If the smoke is not drawn into the flue aperture remove the flue spigot restrictor if fitted and repeat the spillage test If there is an extractor fan fitted in a...

Page 15: ...rate the fire and refer them to the User Book d Inform the User that the Model Number for ordering parts is shown on the Rating plate This is located on the inner face of the rear panel at the left ha...

Page 16: ...ceramic should be checked and if necessary the whole set should be replaced with a genuine replacement set After any servicing work a gas soundness check must always be carried out 4 1 GENERAL ACCESS...

Page 17: ...ket attached to the burner See section 4 3 c Unscrew injector fixing bracket See fig 8 d Unscrew four burner fixing screws See fig 9 e Carefully prise the injector to the right and out of the burner f...

Page 18: ...alve lock nut from the top of the control valve d Unscrew the two control valve panel fixing screws fig 12 and remove valve and panel e Loosen and remove the three gas pipe retaining nuts from the con...

Page 19: ...ther mocouple position is factory set to a tight tolerance Any replacement of parts on the pilot requires a complete new pilot assembly a Loosen the gas pipe nut and remove gas pipe from the pilot Th...

Page 20: ...ts must be carried out by a competent person such as a CORGI registered gas installer The part numbers of the replaceable parts are as follows these are available from your local Flavel stockist whose...

Page 21: ...620 6677 STRATA User Instructions These instructions should be read by the user before operating the appliance and retained for future reference Model No s FRCS3G FRCS4G are for use on Natural Gas G20...

Page 22: ...ss of 150mm No purpose made additional ventilation is normally required for this appliance when installed in G B When installed I E please consult document I S 813 1996 Domestic Gas Installation which...

Page 23: ...is or blockages which must be removed The chimney should also be checked to ensure clearance of flue products We recommend that during the annual service replacement of the Oxypilot is carried out Aft...

Page 24: ...ress position depress slightly again and turn the control anti clockwise to the HIGH position and check for clearance of combustion products as detailed below WARNING If the fire goes out for any reas...

Page 25: ...ics and brush gently with a soft brush To remove the ceramic remove the dress guard as shown in fig 2 Remove the radiants by lifting them slightly then pulling forward as shown below in Fig 3 Fig 3 RE...

Page 26: ...s described in the above section Replacement of any other parts must be carried out by a competent person such as a CORGI registered gas installer The part numbers of the user replaceable parts are as...