background image

1.0 General

1.1 Alpha 2000 HEPA filters shall be extended media

(separator type) (Pureform separatorless type)
filters as manufactured by Flanders.

1.2 Filter sizes, capacities and construction options

shall be as scheduled on the drawings.

1.3 Filters shall be (UL 900 Class 1)(UL586 listed.

2.0 Filter Construction

2.1 The filter pack shall be constructed by pleating a

continuous sheet of non-woven water-resistant
fiberglass media around hemmed-edge corru-
gated aluminum separators. (or) The filter pack
shall be constructed by pleating a continuous
sheet of formed, corrugated medium so that the
pack is self-supporting without the use of spac-
ers of any kind, including separators, tape
strings, adhesives or strips of media.

2.2 The filter pack shall be sealed into a (galvaneal)

409 stainless steel) (304 stainless steel) (parti-
cle board) (fire-retardant particleboard) (fire-
retardant

plywood)

frame

with

a

fire

retardant(polyurethane foam) ( solid urethane)
sealant. (Steel frames shall be 16 ga.)(Wood
frames shall be 3/4” thick.)

2.3 (A 40-durometer closed-cell neoprene gasket)

(Silicone jel in a channel) shall be provided on
one or more sides to seal the filter in the mount-
ing device.

3.0 Performance

3.1 Initial and final resistances shall not exceed the

scheduled values.

3.2 Alpha 2000 HEPA Filters shall have a minimum

efficiency of 99.97% on 0.30 micrometer parti-
cles when tested at rated capacity on a Q-107
Penetrometer in  accordance with IEST-RP-CC-
001.3, Type A.  Measure the upstream and down
stream concentration of these particles with a
light scattering photometer, determine the pene-
tration and calculate the efficiency.

3.3 Alpha 2000 Scan Tested HEPA Filters shall have

a minimum efficiency of 99.99% on 0.30 microm-
eter particles in  accordance with IEST-RP-CC-
001.3, Type C. The scan test shall consist of
challenging the filter with a high concentration of
an approved oil aerosol or PSL Spheres.
Utilizing a photometer or particle counter, the
media pack and the pack- to- frame seal shall be
scanned to insure that there are no leaks greater
than .01% of the upstream concentration at 100
fpm face velocity

Guide Specifications

Alpha 2000 HEPA Filter Dimensions and Capacities

Filter Depth

Filter Size and Frame

Actual Face Size

CFM Capacity at Clean

Weight

(inches)

Depth Designator

(Inches

Pressure Drop, Inches w.g.

(lbs)

.95

1.35

1.75

11-1/2

GG-F

24x24

1500

2000

2500

38

GC-F

24x12

650

920

1180

26

YY-F

23-3/8x23-3/8

1350

1900

2450

37

YUF

23-3/8x11-3/8

610

865

1150

25

GN-F

24x30

1750

2550

3250

45

CC-F`

12x12

290

430

550

14

NOTE:  The pressure drop for fluid seal (Separator or Pureform) and scan tested Pureform

filters will be approximately 15% higher.

REPRESENTED BY:

®

Flanders Filters, Inc.

531 Flanders Filter Road

Washington, NC  27889

Phone: (252) 946-8081

Toll Free: (800) 637-2803

Fax: (252) 946-3425

Website: www.flanderscorp.com

Summary of Contents for FFI Alpha 2000

Page 1: ...tional 250 fpm velocities during the life of the filters The Alpha 2000 99 97 and 99 99 high capacity 24 X 24 X 11 5 filter has a clean pressure drop of 1 0 inch w g at 1500 cfm com pared to standard Alpha Cell filters with a clean pressure drop of 1 50 inch w g at the same air flow Save Replacement Material and Labor Costs Savings are significant with high capacity Alpha 2000 filters They operate...

Page 2: ...upport ing and self separating Pureform Media Pack The Pureform Filter offers many advantages over conventional Separator Style HEPA Filters More usable media area for longer service life because of higher dust holding capacity Reduced cost of ownership because of longer service life Maximum utilization of the media Can handle some harsh environments which may attack aluminum separators Media pack...

Page 3: ...ames Upon request the filter will have a stamp indicating compliance with UL 900 Class 1 UL 586 UL 586 is typically required for Nuclear Grade HEPA Filters Many of the Flanders non Nuclear HEPA Filters meet the requirements of UL 586 To be listed under UL 586 filters must be submitted to Underwriters Laboratories for extensive testing including spot flame and environmental exposure to heated air U...

Page 4: ...efficiency of 99 97 on 0 30 micrometer parti cles when tested at rated capacity on a Q 107 Penetrometer in accordance with IEST RP CC 001 3 Type A Measure the upstream and down stream concentration of these particles with a light scattering photometer determine the pene tration and calculate the efficiency 3 3 Alpha 2000 Scan Tested HEPA Filters shall have a minimum efficiency of 99 99 on 0 30 mic...

Reviews: