3. MEASUREMENT AND REGULATION OF AIR FLOW

 

 
The basic air change rate is adjusted by changing adjustment position a. 

The basic adjustment is 

made by turning the screw spindle, not the cover, by hand.

 The adjustment position is locked by 

tightening the hose clamp carefully. The desired forced exhaust position is set by choosing the 
valve running distance (5, 10, 15, 20 mm). This is done with dip switches on the circuit board 
according to following table. 

NOTE! If the adjustment is changed while the product is 

receiving voltage, the new adjustment is not valid until the voltage has been cut off and 
then switched on.

 

 
 
 
 
 
 
 

 

 

Factory setting of running distance 10mm.

 

 
The running distance must be chosen so that the valve in its open position does not exceed the 
adjustment po 10 mm. The air flow is determined according to the diagram below, the 
pressure difference at the valve and the adjustment position (

Δ

p

m

 and a, Fig. 4).   

 

MEASUREMENT AND ADJUSTMENT DIAGRAMS 

 
 
 
 
 
  
 
 
 
 
 
 

 
 
 
 

The properties of the product include a warm-up run every 24 hours, which the valve 
performs independently of the user. 
The valve is equipped with overheating protection which stops valve operation for two 
minutes due to a continuous back-and-forth run. 

 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

KSOM 

 

Installation and connecting instructions 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

19.11.2009 

Switch 

Running 
distance 

Basic adjustment 

position 

[mm] 

max. [mm] 

OFF OFF 

+5 

ON OFF 

10 

OFF ON 

15 

-5 

ON ON 

20 

-10 