Replacing fuse part ETFF-99-1
NOTE! Safety gloves should be used when replacing the
fuse part.
1. Release the mechanism with the test button (1) – close
the fire damper. Figure 14.
2. Remove the fuse part mounting screw (6). Figure 15.
3. Holding the test button, pull out the complete fuse part
(7). Figure 16.
4. Correctly install the new fuse part and fasten it with the
screw (6).
5. Test the function of the product and reset the fire damp-
er. Turn the handle towards the OPEN position until
the mechanism clicks and the blade locks into OPEN
position. To test the operation of the fuse mechanism,
push the red test button (1) – the spring should close the
blade. Beware of the turning reset handle!
Figure 14.
Figure 15.
Figure 16.
1
6
6
7
6