background image

EQKC COMBI COOLER

FläktGroup 

DC_8931GB   20180202_R0

We reserve the right to make changes without prior notice

Installation and maintenance instructions

 

9

COOLING UNIT

Inspecting the sight glasses

The unit has two sight glasses, one mounted between the con-
denser coil and subcooling coil, and the other downstream
of the subcooling coil.
The purpose of the first sight glass is to check whether gas is 
entering the subcooler. If this is the case, the subcooler will 
not operate optimally and will just act as an extension of the 
condenser coil. It is difficult to avoid a small amount of gas, but 
large amounts can be an indication that there is too little refri-
gerant in the system.
Because the amount is adjusted at the factory, this means that 
there is a risk of leakage in the refrigerant circuit.

Checking subcooling

Subcooling can be checked by measuring the temperature
difference between the inlet and outlet of the subcooling coil.

Superheating

The correct degree of superheating is important for optimum
and reliable operation. If superheating is too great, the hot 
vapour downstream of the compressor will get unnecessarily 
hot. If superheating is insufficient there is a risk of liquid leaking 
into the compressor. This can result in compressor damage.

Condensation temperature

At times the condensation temperature can be quite high,
almost 60 °C. This is normal. The system is designed for such 
temperatures.

Inspection

The function of the cooling unit can be tested by checking
the temperature difference with the control unit.
This check can also be carried out during maintenance in
order to check the cleanliness/performance of the heat
exchangers in the system.

AFTER STARTUP, CHECK THE FOLLOWING:

•   Operating flows
•  Flow to the supply air coil and main circuit correct
•   Information to personnel undertaken

FUNCTION

The compressors are connected in three cooling stages.
The outgoing water temperature depends on whether there is 
a risk of condensation in the chilled beams or not. See Page 9 
for a description of the control unit.
The air handling unit can be used for both supply air and extract 
air control. The cooling unit must be interlocked by the extract 
air fan and main pump (and any outdoor thermostat). It is im-

eQ size

Power model

Nominal power 

with water at 

18/12

014

1

21

2

29

3

34

018

1

26

2

34

3

43

023

1

36

2

46

1

55

032

1

55

2

69

3

80

041

1

69

2

86

3

101

portant that the compressors stop if the extract air fan stops. 
The cooling unit is also internally interlocked by a flow switch 
in the water circuit and the pump for the supply air coil.
Because of the location of the condenser coil, the cooling re-
covery function cannot operate in the unit while the cooling unit 
is in operation.

Overriding the chilled beam circuit valve

If the heating load on the chilled beam circuit exceeds the 
design cooling power, the valve for the outgoing water tem-
perature to the chilled beam circuit will be overridden, so as
to prioritize the supply air coil. This is to ensure that the supply 
air coil can dehumidify air when required. If this function is
not used in the integrated control unit, it must be added to
the controller that replaces it.

Capacity regulation

The capacity of each circuit is regulated individually. If the
pressure is too high, one or both of the compressors will be
shut down. This is to maintain as high a cooling power as
possible and to prevent a shutdown that would require a
manual reset. The compressors are restarted in sequence.

Water-cooled condenser

A water-cooled condenser can be ordered as an option.
If the condenser heat cannot be released to the extract air,
the condenser temperature will rise. In that case the water-
cooled condenser is automatically engaged at 60 °C to
reduce the temperature.

COOLING UNIT

Summary of Contents for EQKC 014

Page 1: ...303 2008 and the necessary protective equipment The necessary protective equipment should include safety goggles and gloves Automatic start Open and lock the cooling unit s main circuit breaker before starting any work Do NOT tread on the unit Use only original spare parts Disregarding any of the above points can lead to a serious safety risk and the withdrawal of the guarantee product liability W...

Page 2: ...2006 LIFTING AND TRANSPORT The unit can be lifted by its lifting eyes if its weight does not exceed 1 050 kg If the unit weighs more than 1 050 kg it must be lifted by a forklift truck from below using the specified holes Lifting the unit other than by using the specified holes can cause the unit to overturn due to the offset centre of gravity Requirements related to the floor The floor must be le...

Page 3: ...dication CP51 Operation Signal for slow valve closure Summation alarm Cooler alarm Unit interlocked by CP51 1 2 1 2 3 3 1 2 1 2 1 2 1 2 1 0 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 External Combi Cooler BMS Unit GH53 Room conden sation sensor GT53 Chilled beam water temperature sensor SV53 Chilled beam water valve actuator 1 G G0 G G0 Y G G0 Y Q11 Q12 2 3 4 1 2 3 1 2 3 1 2 3 4 1 2 3 1 2 3 24 V AC Gnd 0 10 V ...

Page 4: ...trol system eQ Control system Combi Cooler Styrsystem Combi Cooler ALARM 0 10 V Summation Alarm CP51 Operation 52 51 57 56 60 59 58 64 63 Styrsystem eQ Supply air coil actuator GO AR GO GP3 4 Z GO AC YR YH 24 VAC GO G START START NO C YC Alt Control signal heating HEATING Ventilställdon värme eQ Styrlåda M Y G0 G Y G0 G M Interlocking 61 62 Valve actuator heating Control box eQ ...

Page 5: ...ut the power to the entire cooling unit When performing work on the cooling unit always open and lock the main circuit breaker ELECTRICAL DATA FUSE PROTECTION AND AMOUNT OF REFRIGERANT This product contains fluorinated greenhouse gas R134A with a GWP factor of 1430 Refrigerant quantity 5 2 22 8 kg corresponding to 7 4 32 6 tonnes of CO2 equivalent Choice of cable The choice of cable depends on the...

Page 6: ...insu lation must be diffusion tight It must be possible to access bleed valves and drain valves following insulation Filter max gauge 500 μm It is essential that the water is free of impurities If not the heat transfer in the heat exchangers will be reduced as they get dirty In the worst case the exchanger can be permanently damaged The filter should be mounted on the water circuit s inlet to the ...

Page 7: ...ribution between the supply air and the chilled beam circuit The flow is both adjusted and measured with the STAD valve located inside the Combi Cooler The right flow over the supply air coil is available in the unit documentation The technical sales support division at FläktGroup has to be contacted if the unit documentation is not supplied at delivery It s summer case that the flow is adjusted f...

Page 8: ...ISSIONING Checklist BEFORE STARTUP CHECK THE FOLLOWING General Transport damage installation site good lighting level surface etc Condensation drain Oil level in compressors Runoff from the water filled condenser Refrigerant circuit Leakage of refrigerant leakage of compressor oil Crankcase heater in operation Electrical connection and control checking for loose cables Phase sequence and post tigh...

Page 9: ...rmation to personnel undertaken FUNCTION The compressors are connected in three cooling stages The outgoing water temperature depends on whether there is a risk of condensation in the chilled beams or not See Page 9 for a description of the control unit The air handling unit can be used for both supply air and extract air control The cooling unit must be interlocked by the extract air fan and main...

Page 10: ... main circuit should be approximately 12 C irrespective of how many compressors are in operation In normal operation the setpoint of the water to the chilled beam circuit is 15 C as standard Setpoint offset risk of condensation The compressors are controlled by the water temperature down stream of the evaporators The temperature in the main circuit must be approximately 6 C otherwise there is a ri...

Page 11: ...ut water temperature from cooling circuit 2 Screen 3 BeamWater In 15 2 Input water temperature to the chilled beam circuit Valve signal 085 Control signal to the chilled beam valve 0 100 0 10V Forced closing The text is displayed in the event of the forced closure of the chilled beam valve Screen 4 Setpoints when Normal running The setpoints applicable during normal operation i e when the condensa...

Page 12: ...s tripped 1 WaterTemp Alarm Ouput Temp circuit 1 is less than 3 C Reset the alarm relay 2 WaterTemp Alarm Ouput Temp circuit 2 is less than 3 C Reset the alarm relay 1 WatTemp Stop 300 KM1 stopped for 5 min if the temp in circuit 1 is less than 4 C 2 WatTemp Stop 300 KM2 stopped for 5 min if the temp in circuit 2 is less than 4 C 1 Capacity Alarm KM1 s Capacity switch has tripped Alarm locked for ...

Page 13: ...at least once a year Check the following 1 Evaporation condensation temperature Leakage inspection every 12 months in accordance with EU requirements 2 Hot vapour temperature 3 Expansion valve superheating of suction vapour 4 Safety equipment pressure switch trip function 5 Cooling capacity 6 Automation and control equipment functional inspection 7 Electrical equipment post tightening power connec...