eCO Side - Installation and Maintenance Manual
8
FläktGroup DC_10176GB_20180924_R3
Specifications are subject to alteration without notice
5. ELECTRICAL CONNECTIONS
5.3 MAIN SUPPLY
NY BILD
!
5.1 FUSE PROTECTION
Size
Unit with
Hot water coil
Electrical coil
03
Supply
1 x 230 V
3 x 400 V
Fuse
10 A
10 A
04
Supply
1 x 230 V
3 x 400 V
Fuse
10 A
16 A
06
Supply
1 x 230 V
1 x 230 V
1)
Fuse
10 A
10 A
1)
Duct mounted heater size 06 has sparate supply.
5.2 ELECTRICAL DATA
MOTORS
Size
Power, kW
Current, A
03
0,385 x 2
2,5 x 2
04
0,50 x 2
2,2 x 2
06
0,75 x 2
3,3 x 2
ELECTRICAL POST HEATER
Power, kW
Current, A
Voltage, V
4
10
2 x 400
6
15
2 x 400
9
1)
13
3 x 400
1)
Duct mounted heater size 06 has sparate supply.
Units with built-in electrical heater, main supply 3 x 400V.
Units with hot water coil can be supplied with 1 x 230V.
Units with duct mounted electrical heater can be supplied with 1
x 230V.
Units are not available for 3 x 230V..
The main supply cable must be fitted with an external safety
switch located close to the unit. Connect main supply to terminals
U, V, W, N and PE in the control box.