STRA-04 Room controller. Installation and maintenance manual.
Fläkt Woods
9
Specifications are subject of alteration without further notice.
STRA-04 for Optivent
Parameters
The following parameters are modifiable in the parameter menu FS = factory-set value):
Parameter
number
Description
Values
Unit
FS STRA-04
1
Occupied Heating Setpoint
N/A
°C
22
2
Occupied Cooling Setpoint
N/A
°C
24
3
Standby Neutral Zone
N/A
°C
3
4
Unoccupied Heating Setpoint
N/A
°C
19
5
Unoccupied Cooling Setpoint
N/A
°C
27
6
Frost protection Setpoint
N/A
°C
8
7
P-Band
N/A
°C
10
8
I-Time
N/A
Seconds
300
9
Cooling Changeover difference temperature (Room and
media)
N/A
°C
3
10
Heating Changeover difference temperature (Room and
media)
N/A
°C
4
11
Heating/Cooling Functions
0=Heat, 1=Heat/Heat, 2=Heat or Cool via changeover,
3=Heat/Cool, 4=Heat/Cool with VAV and forced
ventilation, 5=Heat/Cool with VAV, 6=Cool, 7=Cool/Cool,
8=Heat/Cool with UO3, 9=Heat/Cool with Change-Over
4
12
Boost Mode Timer
N/A
Minutes
60
13
P.I.R Delay Off
N/A
Minutes
10
14
P.I.R Delay On
N/A
Minutes
0
15
Connected sensor on AI1
0=internal, 1=external, 2=Change over sensor
0
16
UI1 Signal
0 = Disabled, 1 = Change over sensor digital, 2 =
Change over sensor analogue
2
17
Connected sensor DI1 Input
0=Disabled, 1=Window contact, 3=P.I.R, 4=Change over
sensor
0
18
Connected sensor DI2 input
0=Disabled, 1=Window Contact, 2=Condensation
Sensor, 4=Change over sensor
0
20
Function of UO1 Signal
0=None, 1=Thermal actuator heat, 2= None, 3=Heating
actuator 0...10V, 4= None, 5=On/off actuator heat, 6=
None
1
21
Function of UO2 Signal
0= None 1= None, 2=Thermal actuator Cool, 3=
None, 4=Cooling actuator 0…10V, 5= None, 6=On/off
actuator cool
4
22
Function of UO3 Signal
0=None, 1=Forced Vent Digital, 2=Forced Vent 3 Step
Analog, 3=None, 4=Ordinary Analog output, 5=None,
6=Control of EC-fan
1
24
UO3 output in manual mode
N/A
%
0
28
Actuator type for UO3
0=0-10v, 1=2-10v, 2=10-2v, 3=10-0v
1
29
Heating Modulating Actuator Control
0=0-10v, 1=2-10v, 2=10-2v, 3=10-0v
0
30
Cooling Modulating Actuator Control
0=0-10v, 1=2-10v, 2=10-2v, 3=10-0v
0
31
Heating Thermal Actuator Time
N/A
Seconds
60
32
Cooling Thermal Actuator Time
N/A
Seconds
60
33
Travelling Time for Increase/Decrease Heating Valve
(Not in use)
Seconds
120
34
Travelling Time for Increase/Decrease Cooling Valve
(Not in use)
Seconds
120
35
Increase/Decrease NZ (Not in use)
%
2
36
Heating Valve Periodic Exercise Interval
0=Inactive
Hours
23
37
Cooling Valve Periodic Exercise Interval
0=Inactive
Hours
23
38
Hysteresis for the heating thermostat function
N/A
K
2
39
Hysteresis for the cooling thermostat function
N/A
K
2
40
The minimum heat output in heating mode
N/A
%
0
41
Fan runs on low speed (Not in use)
0
42
Display View
0=Actual Temp Value, 1=Heating Setpoint, 2=Cooling
Setpoint, 3=Average of Heating/Cooling, 4=Only
Setpoint Displacement, 5=CO2, 6=Heating Se
Setpoint Displacement, 7=Cooling Se Setpoint
Displacement, 8=Average of Heating/Cooling Setpoints
+ Setpoint Displacement, 9=Calculated Flow in L/S
0
43
Highest Setpoint Offset Increase
N/A
°C
3
44
Lowest Setpoint Offset Decrease
N/A
°C
3
45
Normal Mode Function
0=Off, 1=Unoccupied, 2=Stand-by, 3=Occupied
3
46
Energy Saving Mode Function
0=Off, 1=Unoccupied
1
47
BMS Operating Mode
0=Off, 1=Unoccupied, 2=Standby, 3=Occupied, 4=Not
Used, 5=No Remote control
5
48
Minimum airflow on cooling UO2 in % of 0-10V.
Parameter is in use when cooling/heating mode with
VAV is selected
N/A
%
0
49
Maximum airflow on cooling UO2 in % of 0-10V.
Parameter is in use when heating/cooling mode with
VAV is selected
N/A
%
0
50
Fan Control (Not in use)
0=No Control, 1=Heating, 2=Cooling, 3=Both
8790 GB 2016.03