Installation and maintenance instructions

 

  

Fläkt Woods PM-Motor

With suPPlied FC 102 FrequenCy Converter

Control Cable

Control cable should be shielded. Keep control cable distance 
min 200 mm from mains and motor cable.

 

Control signals

Fan is started with potential free switch connected between
terminals 12 and 18. The circuit voltage is 24 VDC. AUTO-mode 
should be selected from operation panel.
  Speed reference can be given from with 0…10 V signal 
connected in terminals 53(+) and 55(-). Alarm signal is availa-
ble in relay1 (terminals 01, 02 and 03).
Running indication is available in relay 2 (terminals 04,
05 and 06).

 

single speed operation:

Set constant speed reference (rpm) in parameter 411. 
Only external start signal is needed.

 

two speed operation:

Lower speed reference (rpm) is set in parameter 411 and 
higher speed reference (rpm) in parameter 319. Lower speed 
is activated with start signal (terminals 12-18). Higher speed is 
activated by closing terminals 12-29. Speed controller can be 
controlled via Modbus RTU. RS-485 cable is connected to the 
terminals 68 (P), 69 (N) and 61 (COM). If speed controller is last 
unit in line, it should be terminated by setting switch S801 in 
ON position. Modbus operation is described in speed controller 
operation instructions.
 

start up and funCtional testing

after power up test check motor rotation:

Set speed controller to Hand on mode from operation panel. 
Motor will start to the minimum or speed set in operation panel. 
To change the direction of rotation:
•  Remove power to the speed controller and wait for power to  
 discharge.
•   Reverse the connection of any two of the three motor cables  
  on the motor or frequency converter side of the connection.
  When direction of rotation is right set speed controller to Auto
  on mode. Then speed controller will follow control signals.

parameters

Speed controller parameters are set at the factory providing 
for optimal performance of fan and motor. This includes motor 
parameters, ramp times, starting and stopping methods and 
speed limitations. Changing of these parameters may result 
in unstable operation or motor won’t start. Original parameter 
values can be downloaded from operation panel in case of 
losing them.

 

supply Cable

Mount mains supply to terminals L1, L2 and L3 and ground 
wires to earth terminal and tighten. 

 

short circuit protection:

The speed controller must be protected against shortcircuit to
avoid electrical or fire hazard. The fuses mentioned below are
recommended to use to protect service personnel and equip-
ment in case of an internal failure in the speed controller. Speed
controller provides full short circuit protection in case of a short 
circuit on the motor output.

 

over current protection:

Provide overload protection to avoid fire hazard due to over-
heating of the cables in the installation. The speed controller
is equipped with an internal over-current protection that can
be used for upstream overload protection (UL-applications
excluded). See par. 4-18
Current Limit. Moreover, fuses or circuit breakers can be used 
to provide the over-current protection in the installation. Over-
current protection must always be carried out according to 
national regulations.

 

leakage Current (>3,5ma)

EN/IEC61800-5-1 (Power Drive System Product Standard)
requires special care if the leakage current exceeds 3,5 mA. 
Earth grounding must be reinforced in one of the following 
ways:
•   Earth ground wire of at least 10 mm

2

•   Two separate earth ground wires both complying with the  
  dimensioning rules

 

isolation switch

All speed controllers may be used with an isolated input sour-
ce as well as with ground reference power lines.

 

reCommended pre-fuses

 

motor Cable

Motor and speed controller is delivered with 3,5 m long motor 
cable. If it should be replaced with longer one or disconnected 
at the other end.
Following rules should be meet and considered:
•   Motor cable should be shielded type.
•   Shield should be grounded 360° at both ends of cable.
•  Motor cable should be no longer than 20 meters.
•   Motor is connected to star inside the motor.
•  Phase wires are connected to terminals U1, V1, W1.
•   Terminal connectors are not needed.

Power 0,75

1,5

2,2

3

4

5,5

7,5

11

15

3x380-

400V

UL (A)

10

10

15

15

15

25

25

50

50

IEC (A) 

type gG

10

10

16

16

16

25

25

50

50

Summary of Contents for PM

Page 1: ...ain incoming supplied has been isolated Ensure the impeller is kept stationary before opening and whilst the terminal box is open general Admissible environmental temperature from 15 C up to 40 C with altitudes 1000 m above sea level Mounting IM B3 B5 Drive operating voltage 400 VAC Insulation class F temperature rise to class B TEFC execution IP55 degree of protection for the whole range Reduced ...

Page 2: ...ng and stopping methods and speed limitations Changing of these parameters may result in unstable operation or motor won t start Original parameter values can be downloaded from operation panel in case of losing them Supply cable Mount mains supply to terminals L1 L2 and L3 and ground wires to earth terminal and tighten Short circuit protection The speed controller must be protected against shortc...

Page 3: ...ce Frequency converter Bearings 1 The frequency converter must be disconnected from mains if repair work is to be carried out Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs 2 The STOP RESET key on the LCP of the frequency converter does not disconnect the equipment from mains and is thus not to be used as a safety swit...

Page 4: ... instructions are valid for the GLCP LCP 102 The is divided into four functional groups 1 Graphical display with Status lines 2 Menu keys and indicator lights LEDs selecting mode changing parameters and switching between display functions 3 Navigation keys and indicator lights LEDs 4 Operation keys and indicator lights LEDs Graphical display The LCD display is back lit with a total of 6 alpha nume...

Page 5: ... of display indication during normal operation 130BP045 10 Status Quick Menu Main Menu Alarm Log Status indicates the status of the frequency converter and or the motor 3 dif ferent readouts can be chosen by pressing the Status key 5 line readouts 4 line readouts or Smart Logic Control Use Status for selecting the mode of display or for changing back to Display mode from either the Quick Menu mode...

Page 6: ... vated Hand on Off Auto on Reset Coasting stop inverse NB External stop signals activated by means of control signals or a serial bus will override a start com mand via the LCP Off stops the connected motor The key can be selected as Enabled 1 or Disabled 0 via par 0 41 Off Key on LCP If no external stop function is selected and the Off key is inactive the motor can only be stopped by disconnectin...

Reviews: