AIR TREATMENT

9191 GB 2015.09.29

AIR COMFORT

flÄkt woods pm-motor

WITH SUPPLIED FC 102 FREQUENCY CONVERTER

» INSTALLATION AND MAINTENANCE INSTRUCTIONS

installation

 

warning!

The motor is designed exclusively for
operation with the supplied speed control 
(frequency converter).
Direct on-line connection to the mains is not 
possible for PM-motors.

warning!

Risk of electric shock:
Motor terminals may still be live if the impeller
is rotating, even when the main incoming
supplied has been isolated.
Ensure the impeller is kept stationary before 
opening and whilst the terminal box is open.

general

•  Admissible environmental temperature: from -15 °C up to
  +40 °C, with altitudes 1000 m above sea level
•  Mounting: IM B3, B5
•  Drive operating voltage: 400 VAC
•  Insulation class: "F"; temperature rise to class B
  (TEFC execution)
•  IP55 degree of protection for the whole range
•  Reduced dimensions
•  Rare earth permanent magnets

Speed controller and motor shall be installed by a qualified
electrician with adequate knowledge how to install speed-
controlled drive systems (frequency inverters) and EMC safety.
All cabling must comply with national and local regulations on 
cable cross-sections and ambient temperature.

Summary of Contents for PM

Page 1: ...ain incoming supplied has been isolated Ensure the impeller is kept stationary before opening and whilst the terminal box is open general Admissible environmental temperature from 15 C up to 40 C with altitudes 1000 m above sea level Mounting IM B3 B5 Drive operating voltage 400 VAC Insulation class F temperature rise to class B TEFC execution IP55 degree of protection for the whole range Reduced ...

Page 2: ...ng and stopping methods and speed limitations Changing of these parameters may result in unstable operation or motor won t start Original parameter values can be downloaded from operation panel in case of losing them Supply cable Mount mains supply to terminals L1 L2 and L3 and ground wires to earth terminal and tighten Short circuit protection The speed controller must be protected against shortc...

Page 3: ...ce Frequency converter Bearings 1 The frequency converter must be disconnected from mains if repair work is to be carried out Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs 2 The STOP RESET key on the LCP of the frequency converter does not disconnect the equipment from mains and is thus not to be used as a safety swit...

Page 4: ... instructions are valid for the GLCP LCP 102 The is divided into four functional groups 1 Graphical display with Status lines 2 Menu keys and indicator lights LEDs selecting mode changing parameters and switching between display functions 3 Navigation keys and indicator lights LEDs 4 Operation keys and indicator lights LEDs Graphical display The LCD display is back lit with a total of 6 alpha nume...

Page 5: ... of display indication during normal operation 130BP045 10 Status Quick Menu Main Menu Alarm Log Status indicates the status of the frequency converter and or the motor 3 dif ferent readouts can be chosen by pressing the Status key 5 line readouts 4 line readouts or Smart Logic Control Use Status for selecting the mode of display or for changing back to Display mode from either the Quick Menu mode...

Page 6: ... vated Hand on Off Auto on Reset Coasting stop inverse NB External stop signals activated by means of control signals or a serial bus will override a start com mand via the LCP Off stops the connected motor The key can be selected as Enabled 1 or Disabled 0 via par 0 41 Off Key on LCP If no external stop function is selected and the Off key is inactive the motor can only be stopped by disconnectin...