Maintenance
LQQA Humidifier, for circulated water
Time relay TR1 has been preset for
normal operation. If the time requi-
red for emptying has to be increased
due to humidification over a long
period, this can be done as follows:
1. Select Function 12
2. Select the Range
3. Select Time
– If Range has red digits, Time
shows tenths of Range
– If Range has black digits, Time
shows thirtieths of Range
.
Example: Size 64, Δx>8 gram.
Set a time of 240 sec.
– Select a Range of 300 sec.
(black digits)
– Select a Time of 24
(black digits)
Table 2. Presetting the time relay
Table 3. Presetting time relay TR1
Size
Time required for emptying
Normal operation preset
value
High humidification over a
long period
Δx >8 gram Δx >5 gram
90%
60%
90%
60%
60
62
64
30
60
60
0
0
30
30
90
240
0
0
120
71
73
60
90
30
60
180
240
90
120
80
82
84
90
90
120
60
60
60
180
240
300
120
120
120
Range
Time
ETR4–69–A
Function
1s
1.5 .5
12
M
A1~+
15
B1
A2~-
18
16
Rel
Power
TR1
Fig. 6
Seconds
0
Range
1 s
Time
0
10
10 s
10 red
20
30 s
20 black
30
30 s
30 black
40
100 s
4 red
50
100 s
5 red
60
100 s
6 red
70
100 s
7 red
80
100 s
8 red
90
100 s
9 red
100
100 s
10 red
120
300 s
12 black
180
300 s
18 black
240
300 s
24 black
300
300 s
30 black
Q1
K1
R1
NR3
NR2
NR1
TR1
Components inside the control box
Fig. 7