Fisher R130/21 Instruction Manual Download Page 5

Types 749B and R130

5

this is by cracking the container valve open for a short 

time to blow out the dirt.  Apply pipe compound to the 

male threads of the pipe.  

 

A relief valve is required downstream of all the 

regulators (except Types 64SR or HSRL) used on 

final-stage service.  Both the Types 64SR and HSRL 

final-stage regulators have an internal relief valve.  The 

internal relief valve opens when downstream pressure 

reaches approximately 125% to 250% above the set 

point for the Type 64SR or 200% to 300% above the 

setpoint for the Type HSRL. 

!

WARNING

Be sure that the changeover manifold  

regulator assembly is supplying the 

correct pressure to the appliance.  

Failure to provide the correct pressure 

to the appliance can result in personal 

injury from fire and or explosion or 

damage downstream equipment.  

 

Figure 3.

  Assembly Drawing

5

3

1

8

5

4

A

A

VIEW A-A

SUPPLY

T80219

749B Series (Type 64 Manifold Regulators)

CHANGEOVER REGULATOR SPRING

RESERVE OUTLET PRESSURE STANDARD 

SETTING AND RANGE

APPROXIMATE SUPPLY

PRESSURE ABOVE RESERVE SETTING

Zinc 

1D7515

6 psi / 0.41 bar

Adjustable Range

3 to 11 psi / 0.21 to 0.76 bar

9 psi / 0.62 bar

Blue

1D6659

5 psi / 0.35 bar

Adjustable Range

5 to 15 psi / 0.35 to 1.0 bar

20 psi / 1.4 bar

R130 Series (Type 67C Manifold Regulators)

Blue

T14058

30 psi / 2.1 bar

Adjustable Range

5 to 40 psi / 0.35 to 2.8 bar

14 psi / 0.97 bar

Table 1.

  Manifold Spring Rates

Summary of Contents for R130/21

Page 1: ...l and service this equipment Things to tell the Gas Customer 1 Point out the regulator s vent to the customer or vent assembly or vent tube and stress that this opening must remain unobstructed at all...

Page 2: ...g 1 475 000 1 R130 21 1 4 inch FNPT 1 4 inch FNPT 45 psig 3 1 bar 30 psig 2 1 bar 1 500 000 1 749B 21 1 2 inch FNPT 1 2 inch FNPT 15 psig 1 0 bar 5 psig 0 35 bar 1 Based on 100 psig 6 9 bar inlet rese...

Page 3: ...or manifold will open and maintain the reserve setting to the second stage regulator which continues to regulate the pressure to the appliance At the time the pressure in the Supply container drops to...

Page 4: ...inspected for any damage that may have occurred Large volumes of gas may discharge through the regulator vent during internal relief valve operation which can result in fire or explosion from accumula...

Page 5: ...ulator assembly is supplying the correct pressure to the appliance Failure to provide the correct pressure to the appliance can result in personal injury from fire and or explosion or damage downstrea...

Page 6: ...To adjust the indicator remove the screw key 6 and the lens key 3 Using a small slotted screw driver turn the adjusting screw clockwise to increase the pressure or Figure 4 Indicator Assembly Drawing...

Page 7: ...ulator each time a gas delivery is made for 1 Improper installation 2 Plugged or frozen vent 3 Wrong regulator or no regulator in the system 4 Internal or external corrosion 5 Age of the regulator 6 A...

Page 8: ...as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability We reserve the right to modify or improve the designs or specification...

Reviews: