8
6.2 FSMED-124HFPL
Cooling mode
Outdoor temperature (Dry bulb temp)
Indoor Conditions
Pressure
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D
15ºC W
bar 8.3 8.4 8.7 8.8 9.3 9.8
24ºC D
17ºC W
bar 8.5 8.7 9.1 9.3 9.9 10.3
27ºC D
19ºC W
bar 8.7 9.1 9.3 9.7 10.2 10.8
32ºC D
23ºC W
bar 9.1 9.5 9.8 10.3 10.7 11.1
Heating mode
OUTDOOR CONDITIONS
Indoor Conditions
Pressure
12ºC D
11ºC W
7ºC D
6ºC W
0ºC D
-1ºC W
-4ºC D
-6ºC W
-7ºC D
-9ºC W
-15ºC D
-xºC W
15ºC
bar
26.9 25.4 21.7 20.9 19.5 /
18ºC
bar 29.3 26.7 23.3 21.5 20.6 /
20ºC
bar 29.7 28.6 23.7 23.1 21.6 /
22ºC
bar 31.9 39.6 24.9 23.5 22.2 /