![Fisher FSK-124HF Technical & Service Manual Download Page 37](http://html.mh-extra.com/html/fisher/fsk-124hf/fsk-124hf_technical-and-service-manual_2294434037.webp)
2) Remove the installation covers at the four corners.
Wrench off the bolts, loose the rope of the installation covers, and remove them. (Refer to chart 10)
3) Install the panel
a. Align the swing motor on the panel to the tubing joints of the body properly. ( Refer to chart 11)
b. Fix hooks of the panel at swing motor and its opposite sides to the hooks of corresponding water receiver. Then
hang the other two panel hooks onto corresponding hangers of the body.
c. Adjust the four panel hook screws to keep the panel horizontal, and screw them up to the ceiling evenly.
d. Regulate the panel in the direction of the arrow in Chart11(4) slightly to fit the panel's center to the center of
the ceiling's opening. Guarantee that hooks of four corners are fixed well.
e. Keep fastening the screws under the panel hooks, until the thickness of the sponge between the body and the
panel's outlet has been reduced to about 4~6mm. The edge of the panel should contact with the ceiling well.
(Refer to chart 12)
Malfunction described in Chart13 can be caused by inappropriate tightness the screw.
If the gap between the panel and ceiling still exists after fastening the screws, the height of the indoor unit
should be modified again. ( Refer to chart 14-left)
You can modify the height of the indoor unit through the openings on the panel's four corners, if the lift of
the indoor unit and the drainpipe is not influenced (refer to chart 14-right).
4) Hang the air-in grid to the panel, then connect the lead terminator of the swing motor and that of the control
box with corresponding terminators on the body respectively.
5)
Relocate the air-in grid in the procedure of reversed order.
6)
Relocate the installation cover.
a. Fasten the rope of installation cover on the bolt of the installation cover. (Refer to chart 15-left)
b. Press the installation cover into the panel slightly. (Refer to chart 15-right)
Chart 14
Loosen upper nut
Adjust lower nut
Gap not allowed
Chart 13
Leakage
Ceiling
Pollution
Water condensation
Cross-screwdriver
Outlet joint
Tubing joint Hook panel
Swing Motor
Hook-boit
Water- receiver
Chart 11
panel sponge
Chart 12
body
Ceiling
panel
panel foam1
air out
tan
panel foam 2
4-
6m
m
outlet foam
Chart 15
Installation cover,s rope
Tap Screw
Slide the four sliders
in the corresponding
channel when installing
the cover
- 36 -
Summary of Contents for FSK-124HF
Page 9: ...Part 4 Velocity temperature distribution Discharge angle 60º Airflow velocity Temperature 8 ...
Page 10: ...Part 5 Operation Range Ensure the operating temperature is in allowable range 9 ...
Page 42: ...Part 12 Exploded view 1 FSK 124HF Indoor unit 41 ...
Page 45: ...2 FSK 184HF Indoor unit 44 ...
Page 48: ...12 FSK 244HF Indoor unit 47 ...
Page 51: ...13 FSK 364 484HF Indoor unit 50 ...
Page 55: ... 54 54 ...