Fisher FIELDVUE DVC6200p Instruction Manual Supplement Download Page 16

Instruction Manual Supplement

D103560X012

DVC6200p Digital Valve Controller

November 2014

16

7.  Right click on the device in the right pane and select Open Object, as shown in figure 16.

Figure 16. Open Device in SIMATIC PDM

8.  In the resulting Offline menu screen (shown in figure 17), select the Upload icon, as indicated below, to upload the

device to the database. Click Start. The upload is complete when the tag name appears. Close the Upload PG/PC
dialog screen.

Note

The device must be uploaded to the database using the Upload icon only; do not upload from the drop down menu.

Figure 17. Upload Device to Database

UPLOAD

START UPLOAD

TAG NAME

UPLOAD COMPLETE

OFFLINE

The project is now setup, and you are able to communicate with the DVC6200p. Proceed to Going Online with the
DVC6200p on the next page.

Summary of Contents for FIELDVUE DVC6200p

Page 1: ...bration and tuning using the Guided Setup procedure The procedures covered in this supplement were completed using Siemens SIMATIC Manager PDM 8 1 While the steps taken should remain basically the sam...

Page 2: ...Documents D Fisher FIELDVUE DVC6200 Series Digital Valve Controller quick start guide D103556X012 D Fisher FIELDVUE DVC6200p Digital Valve Controller instruction manual pending All documents are avai...

Page 3: ...ens SIMATIC PDM Refer to figure 1 Figure 1 Connecting the FIELDVUE DVC6200p using EDD for Siemens SIMATIC PDM BACK RAIL PROFIBUS PA POWER SUPPLY DP PA COUPLER 24 VDC SUPPLY VOLTAGE FOR DP PA COUPLER 2...

Page 4: ...are is installed a Go to Set PG PC Interface as shown in figure 2 b Under the Interface click on Select to add the PCI PCMCIA USB type PROFIBUS card installed on the PC c Once the interface or card ap...

Page 5: ...wn in figure 3 If there are other Class 1 or Class 2 masters on the bus then DO NOT select PG PC is the only master on the bus Under Network Parameters select the appropriate Transmission Rate of the...

Page 6: ...tal Valve Controller November 2014 6 3 Click on Diagnostics as shown in figure 4 Figure 4 Diagnostics 4 In the Diagnostics window shown in figure 5 click on Test to check the status of the PROFIBUS ca...

Page 7: ...mmended by the coupler manufacturer 6 To identify the address of the host and any connected device select Read as shown in figure 6 Figure 6 Status Network Diagnostics TEST STATUS READ 7 Any master or...

Page 8: ...aster device is at address 4 Make note of the addresses found during the bus node scan for future reference Note It is not necessary to make any changes to information found in the other tabs 8 Select...

Page 9: ...Instruction Manual Supplement D103560X012 DVC6200p Digital Valve Controller November 2014 9 Figure 8 Loading the EDD File SOURCE DIRECTORY COMPRESSED SOURCE OR NAVIAGATE TO EDD FILE...

Page 10: ...alve Controller November 2014 10 Note Loading the EDD for a specific device such as the DVC6200p on the SIMATIC PDM on a station is only needed once unless a new or updated EDD is required Figure 9 ED...

Page 11: ...WARNING Changes to the instrument setup may cause changes in the output pressure or valve travel Depending on the application these changes may upset process control which may result in personal inju...

Page 12: ...ck on the project in the left hand pane select Insert New Object networks if not already available Figure 11 Adding Networks PROJECT NAME 3 Right click on the networks icon in the right pane and selec...

Page 13: ...upplement D103560X012 DVC6200p Digital Valve Controller November 2014 13 4 Enter the Object name then click on Assign Device Type as shown below Navigate to PROFIBUS DP network and select OK Figure 13...

Page 14: ...ement D103560X012 DVC6200p Digital Valve Controller November 2014 14 5 A new network now appears on the right pane as shown in figure 14 Right click on the network and select Insert New Object Object...

Page 15: ...ndalone station PDM or PA Step7 when PDM is in an integrated environment Click OK Click OK in the resulting screen Note The default address of the DVC6200p is set by the factory to 126 This may need t...

Page 16: ...icon as indicated below to upload the device to the database Click Start The upload is complete when the tag name appears Close the Upload PG PC dialog screen Note The device must be uploaded to the...

Page 17: ...nual Supplement D103560X012 DVC6200p Digital Valve Controller November 2014 17 Going Online with the DVC6200p 1 Click on Device Online to access to open the DVC6200p EDD as shown in figure 18 Figure 1...

Page 18: ...rmation Stroke Valve and Calibration procedures Figure 19 FIELDVUE DVC6200 EDD Overview CHANGE MODE HERE DEVICE STATUS CLICK TO SEE ACTIVE STATUS ALERTS 2 To configure the DVC6200p select Configure Gu...

Page 19: ...to Calibrate and Tune procedure below Figure 21 Select Calibration Type Cancel Performing One Step Local Quick Setup to Calibrate and Tune the DVC6200p Digital Valve Controller Note This calibration...

Page 20: ...blication are presented for informational purposes only and while every effort has been made to ensure their accuracy they are not to be construed as warranties or guarantees express or implied regard...

Reviews: