
6 | Technical data
FISCHER Mess- und Regeltechnik GmbH
12
BA_EN_DS13
6 Technical data
6.1 General Information
Reference conditions (acc. to IEC 61298-1)
Temperature
+15 … +25 °C
Relative humidity
45 … 75 %
Air pressure
86 … 106 kPa
860 … 1060 mbar
Installation position
vertical
6.2 Input variables
Measuring
ranges
Measuring accur-
acy
Allowed static op-
erating pressure
Overpres-
sure
Under-
pressure
0 … 250 mbar
± 6.25 mbar
6 bar
25 bar
- 1 bar
0 … 400 mbar
± 10 mbar
6 bar
0 … 0.6 bar
± 0.015 bar
10 bar
0 … 1 bar
± 0.025 bar
16 bar
0 … 1.6 bar
± 0.04 bar
25 bar
0 … 2.5 bar
± 0.625 bar
25 bar
0 … 4 bar
± 0.1 bar
25 bar
0 … 6 bar
± 0.15 bar
25 bar
0 … 10 bar
± 0.25 bar
25 bar
0 … 16 bar
± 0.4 bar
25 bar
0 … 25 bar
± 0.625 bar
25 bar
-0.6 … 0 bar
± 0.015 bar
10 bar
-1 … 0 bar
± 0.025 bar
16 bar
-1 … +0.6 bar
± 0.04 bar
25 bar
-1 … +1.5 bar
± 0.0625 bar
25 bar
-1 … +3 bar
± 0.1 bar
25 bar
-1 … +5 bar
± 0.15 bar
25 bar
Rated pressure of the measuring
system
25 bar
Test pressure
1.5 times the rated pressure
Zero-point setting
Arranged in the front panel of the scale
Measuring accuracy
± 2.5% of the upper range value
6.3 Output parameters
Switch contacts
1 to 2 micro-switches
Switching function (per contact)
Changeover contact
Switch point setting
Can be set to reference scales from outside
Smallest settable value
5% of the upper range value
Switch hysteresis
2.5% of the upper range value
Per contact
AC
DC
Switching voltage
250 V
30 V
Switching current
5 A
0.4 A
Switching output
250 VA
10 W