
10
BH1- 48R/RGI = 53-1/4"/ 135.25cm
BH1- 48RS = 53-7/16"/ 135,7cm
BH1- 36R/RGI = 41-5/8"/ 105,7cm
(
with
rotisserie motor mounted)
48" Models = 47-7/8"/ 121,6cm
36" Models = 35-7/8"/ 91,12cm
(
without
rotisserie motor mounted)
rotisserie
motor
24-1/4"
10-1/2"
(61.6cm)
(25.4cm)
(64,77cm)
(26,67cm)
(7,6 cm)
grill
exhaust
3" (7,6 cm) (to
non-combustible
construction /
minimum
lid clearance
)
10 "
25-1/2"
Bottom of
support flange
3"
rotisserie
motor
24-1/4"
/ 61,6cm
10-1/2"
/ 26,67cm
26-5/8"/ 67.6cm
26-5/8"/ 67.6cm
grill
exhaust
18" / 45,7cm min.
(to combustible
construction)
10 "/ 25.4cm
25-1/2"/ 64,77cm
22-5/16"/ 56,7cm
22-5/16"/ 56,7cm
2-3/16"
/5,5cm
2-3/16"
/5,5cm
Bottom of
support flange
18" / 45,7cm min.
18" / 45,7cm min.
FIG. 03
INSTALLATION
LOCATING GRILL/BUILT-IN CLEARANCES
Clearances to Non-Combustible Construction*
Clearances to Non-Combustible Construction*:
A minimum of 3” clearance from the back of the grill to non-combustible construction is required for the purpose
of allowing the lid to open fully. It is desirable to allow at least 6” rear and side clearance to non-combustible
construction above the cooking surface for counter space. If you’ll be using the rotisserie option, the space is es-
sential for motor and skewer clearance. The grill can be placed directly adjacent to non-combustible construction
below the cooking surface. (Fig. 03)
WARNING!
Failure to maintain required clearances creates a fire hazard that may result in property damage or serious personal
injury.
WARNING!
The BH1 Grill is designed to function in an open area. Recommended minimum clearances should be maintained
to all surfaces (combustible and noncombustible) for optimum performance. Noncombustible material within the
minimum clearance area could result in discoloration or deterioration.
WARNING!
If a noncombustible material such as stucco is covering a combustible material such as wood, the minimum clear-
ance distance needs to be held to the wood. The presence of a noncombustible material inside the clearance zone
does not eliminate the minimum clearance zone to combustible material.
* DEFINITION OF NONCOMBUSTIBLE MATERIAL
- Material which is not capable of being ignited and burned, such as
materials consisting entirely of, or a combination of, steel, iron, brick tile, concrete, slate, and plaster.
Clearances to Combustible Construction**:
Minimum of 18” (45,7cm) from the sides and rear of grill must be maintained to adjacent vertical combustible
construction, above the counter top level. You should take in account that there is a large volume of heat, and
smoke will exhaust from the rear of the grill. This may discolor or damage unprotected areas (Fig. 04). Do not
install under unprotected combustible construction without using a fire safe ventilation system.
A 18” (45,7cm) minimum clearance must be maintained under the counter top to combustible construction. The
clearance can be modified by a use of an insulated jacket.
Summary of Contents for DCS BH1
Page 2: ......
Page 8: ......
Page 9: ...7 BH1 48R BH1 48RGI BH1 48RS BH1 36R BH1 36RGI GRILL MODELS ...
Page 37: ...35 ...
Page 38: ...36 ...
Page 39: ......
Page 40: ......
Page 47: ...7 MODÈLES DE GRIL BH1 48R BH1 48RGI BH1 48RS BH1 36R BH1 36RGI ...
Page 50: ......
Page 77: ...37 ...
Page 78: ...38 ...
Page 79: ...39 ...