First Aquatherm Series Installation And Application Manual Download Page 11

11

3.  Water  heater  thermostat  not  turned  up  high    

enough.

4.  Water heater thermostat not calibrated properly.

5.  Restricted or improperly installed dip tube in  water     

heater.

6.  Restriction somewhere in heating loop.  Confirm 

that no other check valves or devices have been  

installed in the heating loop except as supplied by 

First Co.

     Note: 

Some water heaters come with a normally 

closed spring-loaded check valve factory installed 

on one of the space heating connections.  Since  

the circulating pump in the 

Aquatherm

®

  

system  

may not be able to open this valve  in addition to  

the 

Aquatherm

®

 

 check valve, this valve should  

be  removed before installation.

7.  Air handler or hot water coil not large enough.

8.  Water heater not large enough.

Hot water circulates through hot water coil during 

cooling cycle:

1.  Check valve may be stuck open allowing "thermo-

syphoning" (circulation) of hot water.  This occurs 

when the hot water pipes are not capped-off dur-

ing  installation,  allowing  foreign  debris  such  as 

solder, insulation, and other building materials to 

enter the piping.  If not completely purged from the 

system, this "debris" can lodge under the check 

valve seat and allow hot water to flow through the 

hot water coil even in the summer.  To solve this 

problem, flush the heating loop several times as 

indicated in the "start-up procedure" on Page 7. 

 

note: Check valve in models made after year 1999 

are located in the pump itself.

CONCLUSION

   

     Always  leave  the  appropriate  literature  and  /  or 

manual with the homeowner and whenever possible 

take the time to explain the operation and advantages 

of the system.

 

 

 

All technical specifications subject

to change without notice.

TROUBLESHOOTING

(Most likely problems and cause)

Important:

    For  system  to  operate  properly 

power

 

should be turned ON and all shut - off valves should 

be OPEN.

Pump does not run:

   These pumps may sometimes 

“stick” due to non - use and fail to start.  Before replacing 

pump: 

1.  Turn off power.  On Grundfos pumps remove large 

screw plug in end of pump motor and turn shaft sev-

eral times with a small screwdriver.  Replace plug and 

start system.  Pump should start.

2.  If pump 

has

 to be replaced, first shut off all isolation 

valves  between  the  water  heater  and  air  handler 

and relieve the city water pressure by opening the 

air purge valve.  Then remove the four  screws that 

attach the pump motor to the pump volute rather than 

un-soldering the entire pump assembly.

Fan motor runs on cooling but not on heating:

 

    Thermostat is wrong type (a gas furnace type ther-

mostat will not bring on the fan motor in the heating 

cycle on certain air handlers).   For correct type of 

thermostat, see “accessories”.

     

Note: 

FWA-HW air handler has a blower delay.

Pump is noisy:

Air may still be in the heating loop.    Re-purge the 

system as described under “start - up procedure".

Water heater T & P valve “weeping”:

This situation usually occurs in those systems located 

in areas where local codes require the installation of 

a “backflow preventer” in the cold water supply line 

to the water heater.  This situation is caused by the 

expansion of the water when heated.  An expansion 

tank may be required to solve this problem.  Contact 

local plumbing authorities for assistance.

Insufficient or no heat:

1.  Air still in heating loop.  Re-purge system.

2.  Inlet and oulet piping connections at the air handler 

may  be  piped  backwards.    (See  "Piping  connec-

tions").

Summary of Contents for Aquatherm Series

Page 1: ...1 FIRST CO P O BOX 270969 DALLAS TEXAS 75227 Ph 214 388 5751 Fax 214 388 2255 www rstco com INSTALLATION AND APPLICATION MANUAL FOR AQUATHERM COMBO HEATERS Aquatherm...

Page 2: ...er 4 Boiler 4 Accessories Thermostat 4 Freeze protector 4 Equipment Sizing Condensing unit 4 Air handler 4 Water heater 5 Installation Duct work 5 Electrical 5 Water piping 6 1 Material 6 2 Solder con...

Page 3: ...appliance that can heat your home as well as provide hot water for domestic purposes Any properly sized water heater for heating and split system type condensing unit for cooling will work with First...

Page 4: ...dinstantaneous waterheaters Pleasecon tact the factory for assistance in selecting the proper equipment for these applications See Page 10 for wiring diagram of multiple air handlers ACCESSORIES Therm...

Page 5: ...115 volt 1phase 60 cycle line voltage and 24 volt control ume sizing guide is satisfactory in most parts of the country minimum requirements 1 5 and 2 ton air handlers minimum 40 gallon 2 5 and 3 ton...

Page 6: ...ons If a back ow preventer is required by code the T P valve on the water heater may tend to drip water because of pressure build up in the water See gures 3 4 5 14 and 15 for typical wiring diagrams...

Page 7: ...ature about 45 minutes DO NOT IGNITE THE WATER HEATER WITHOUT WATER IN THE TANK 4 Purge the air handler s hot water coil and lines The following procedure allows the use of city water pressure to purg...

Page 8: ...8 Conventional Piping Diagram Side Tap 4 Pipe Water Heater Piping FIGURE 8 FIGURE 9...

Page 9: ...9 FIGURE 10...

Page 10: ...W FAN COIL G W R C G W R Y 24V T T 24V BRN G W R C MV MV BOILER T T 4 CONDUCTOR CLASS 2 WIRING 24 VOLT CLASS 2 WIRING 24 VOLT CLASS 2 WIRING PIGTAIL LEADS FOR MOTORIZED VALVE PIGTAIL LEADS FOR MOTORIZ...

Page 11: ...tages of the system All technical speci cations subject to change without notice TROUBLESHOOTING Most likely problems and cause Important For system to operate properly power should be turned ON and a...

Page 12: ...12 Catalog No IAM1010 Replaces IAM309...

Reviews: