![First Alert FA147C Installation Instructions Manual Download Page 2](http://html1.mh-extra.com/html/first-alert/fa147c/fa147c_installation-instructions-manual_2293313002.webp)
ii
RECOMMENDATIONS FOR PROPER PROTECTION
The following recommendations for the location of fire and burglary detection devices
help provide proper coverage for the protected premises.
Recommendations For Smoke And Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the
recommendations contained in the National Fire Protection Association's (NFPA) Standard
#72 noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in
all rooms and areas of the household as follows: For minimum protection a smoke detector
should be installed outside of each separate sleeping area, and on each additional floor of a
multi-floor family living unit, including basements. The installation of
smoke detectors
in
kitchens, attics (finished or unfinished), or in garages is not normally recommended.
For maximum protection the NFPA recommends that you install
heat
or
smoke detectors
in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility
and storage rooms, basements and attached garages.
In addition, we recommend the following:
¥ Install a smoke detector inside every bedroom where a smoker sleeps.
¥ Install a smoke detector inside every bedroom where someone sleeps with the door
partly or completely closed. Smoke could be blocked by the closed door. Also, an alarm in
the hallway outside may not wake up the sleeper if the door is closed.
¥ Install a smoke detector inside bedrooms where electrical appliances (such as portable
heaters, air conditioners or humidifiers) are used.
¥ Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12
meters) long.
¥ Install smoke detectors in any room where an alarm control is located, or in any room
where alarm control connections to an AC source or phone lines are made. If detectors
are not so located, a fire within the room could prevent the control from reporting a fire
or an intrusion.
DINING
KITCHEN
BEDROOM
BEDROOM
BEDROOM
BEDROOM
LIVING ROOM
✪
✪
✪
✪
✪
▲
▲
BEDROOM
BDRM
BDRM
DINING
LIVING ROOM
TV ROOM
KITCHEN
■
■
■
✪
✪
✪
✪
✪
✪
▲
✪
✪
✪
BEDROOM
BEDROOM
TO
BR
■
■
■
■
■
LVNG RM
BASEMENT
KTCHN
▲
▲
.
CLOSED
DOOR
GARAGE
▲
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
THIS CONTROL COMPLIES
WITH NFPA REQUIREMENTS
FOR TEMPORAL PULSE
SOUNDING FOR FIRE
NOTIFICATION APPLIANCES.
Recommendations For Proper Intrusion Protection
For proper intrusion coverage, sensors should be located at every possible point of entry to a
home or commercial premises. This would include any skylights that may be present, and
the upper windows in a multi-level building.
In addition, we recommend that radio backup be used in a security system so that alarm
signals can still be sent to the alarm monitoring station in the event that the telephone lines
are out of order (alarm signals are normally sent over the phone lines, if connected to an
alarm monitoring station).