If a cover is used, do not install until unit has cooled.

WARNING

Fuel and its vapors are extremely flammable and

explosive  which  could  cause  burns,  fire  or

DO NOT stop engine by moving choke control

to “

START

” position.

Important

: Always ensure that the 

 is in the “

OFF

” position when the engine 

is not in use.

fuel selector 

switch

explosion resulting in death, serious injury

and/or property damage.

If the engine will not be used for a period of two 

weeks or longer, please see the Storage section 

for proper engine and fuel storage.

NOTE

Disconnect

 

the

 

LPG

 

cylinder from the 

generator during transportation.

This  generator  is  equipped  with  an  electronic 

module  which  consumes  battery  power.  When 

the fuel selector switch is turned to the “

GAS

” or 

LPG

” position, the indicator light will become 

RED

 up to 

4 minutes

(before goes off).

Indicator light - Battery Power Saving Mode

The  indicator  light  will  start 

FLASHING

  for 

minutes

  in  the  event  of  any  unwanted shutdown 

such as low oil, running out of fuel(gasoline or LPG), 

or  any other unwanted shutdown. This is a reminder 

that  the  generator is  switching to 

Battery Power 

Saving  Mode.

  The  generator  should  be  checked 

Starting the engine successfully during these 

minutes

 will turn the indicator light 

GREEN

.

Starting the engine unsuccessfully or not attempting 

to start the engine at all during these 

4 minutes

 will 

switch generator to 

Battery Power Saving Mode

 in 

order to conserve and increase the life of battery.
MUST  HAVE 

SOLID  RED  INDICATOR  LIGHT 

TO 

BE ABLE TO START THE GENERATOR. THE GENERATOR 

CANNOT  BE  STARTED  DURING 

BATTERY  POWER 

SAVING MODE

 UNLESS THE FUEL SELECTOR SWITCH 

IS  TURNED  TO  THE  “

OFF

”  POSITION  AND  THEN 

TURNED BACK TO THE “

GAS

” OR “

LPG

” POSITION.

Unwanted Shutdown:

The generator cannot be started during or after 

the 

4 minutes

 of 

FLASHING

 mode unless the fuel 

selector switch is turned to the "

OFF

" position and 

then turned back to the “

GAS

” or “

LPG

” position. 

for any unwanted shutdown.

This generator is equipped with an automatic 

battery  charging  circuit  and  the  battery  will 

receive  a  proper  charge  when  the  engine  is 

running to keep the battery charged.

Low Oil Shutdown

If the engine oil drops below a preset level, an 

oil switch will stop the engine. Check oil level 

with dipstick.

If oil level is between LOW and HIGH mark on 

dipstick:

1.DO NOT try to restart the engine.

2.Contact an Authorized FIRMAN Service Dealer.

3.DO NOT operate engine until oil level is 

   corrected.

If oil level is below LOW mark on dipstick:

1.Add oil to bring level to HIGH mark.

2.Restart engine and if the engine stops again 

   a low oil condition may still exist. DO NOT try 

   to restart the engine.

3.Contact an Authorized FIRMAN Service Dealer.

4.DO NOT operate engine until oil level is 

   corrected.

Do Not Overload Generator

Overloading a generator in excess of its rated 

wattage capacity can result in damage to the 

generator and to connected electrical devices.

To prolong the life of your generator and 

attached devices, follow these steps to add 

electrical load:

1. Start the generator with no electrical load 

    attached.

2. Allow the engine to run for several minutes 

    to stabilize.

3. Plug in and turn on the first item. It is best to 

    attach the item with the largest load first.

4. Allow the engine to stabilize.

5. Plug in and turn on the next item.

6. Allow the engine to stabilize.

7. Repeat steps 5-6 for each additional item.

English                                                                                            

Page 

2

3

 

             

        

Support: [email protected]

Summary of Contents for P03607

Page 1: ...rming any maintenance or service IMPORTANT Record product information to reference when ordering parts or obtaining warranty coverage Serial Number OWNER S MANUAL PORTABLE GENERATOR REMANUFACTURED MOD...

Page 2: ...C E AL 80 EA5 L E AG D 85 0 L L E AE5 3LE40L 0 0A E AL 80 EA5 L E AE LL 0 E5 3L 80 EA5 8L DL L L E 5 3LE40L 35 0L L L 5 E AL8534EL L EE0AKL J0AL I5 3L 0L L L JL 58L 4HE J L L L L L EL I0A8 L 0 0A E AL...

Page 3: ...ces tools and motor loads and is not intended for any other purpose It is important that you read and understand these instructions thoroughly before attempting to start or operate this equipment Save...

Page 4: ...duct downwind and point the engine exhaust away from occupied spaces If you start to feel sick dizzy or weak while using this product shut it off and get to fresh air RIGHT AWAY See a doctor You may h...

Page 5: ...de and downwind far away from windows doors and vents Direct exhaust away from occupied spaces INCORRECT USAGE Do not operate in any of the following locations Near any door window or vent Garage Base...

Page 6: ...and and arm toward engine faster than you can let go which could cause broken bones fractures bruises or sprains resulting in serious injury When starting engine pull cord slowly until resistance is f...

Page 7: ...loads OFF and disconnect from generator before stopping generator DO NOT use generator with electrical cords which are worn frayed bare or otherwise damaged DO NOT operate generator in the rain or we...

Page 8: ...one in your household depends on electrical equipment to live Inform your electrical provider immediately if a loss of power would cause you or anyone in your household to experience a medical emergen...

Page 9: ...or to usage If problems arise when assembling the generator call 1 844 347 6261 F E G H K 1 Before adding wheels tip the generator on its side 2 Slide the axle pin A through the wheel B 3 Slide the ax...

Page 10: ...l Valve 6 Air Filter 7 389cc FIRMAN OHV Engine 8 Recoil Starter 9 10 0 Flat Free Wheel 10 Oil Filler Cap 11 Outlet Cover 12 Control Panel 13 Handle We are always working to improve our products Theref...

Page 11: ...Maximum full load current may be drawn from this 120 240 Volt 30 Amp receptacle Ground Fault Circuit Interrupter conforms to UL 943 and NEC requirements This device protects you against hazardous elec...

Page 12: ...stop the flow of electricity making the lamp shut off The GFCI s indicator light comes off RESET TEST TEST MONTHLY FOLLOW DIRECTIONS RESET BUTTON Receptacle Outlet LED Indicator Light TEST BUTTON Out...

Page 13: ...FIRMAN1 Model Rated AC Voltage Phase Power Factor Voltage Regulator Alternator Type Running Watts Starting Watts Engine Engine Type Displacement Low Oil Shutdown Ignition System Starting System Fuel C...

Page 14: ...te a warning device or stop the engine If generator shuts off and the oil level is within specifications check to see if generator is sitting at an angle that forces oil to shift Place on an even surf...

Page 15: ...ill cap remove cap 2 Slowly add unleaded fuel to fuel tank Be careful not to fill above the red fuel level indicator This allows adequate space for fuel expansion 3 Install fuel cap and let any spille...

Page 16: ...d the regulator won t cause bends or kinks in the hose Spray a soapy water solution one part liquid detergent and one part water to check all connections for leaks before attempting to use generator S...

Page 17: ...he air fuel ratio Other high altitude issues can include hard starting increased fuel consumption and spark plug fouling To alleviate high altitude issues other than the natural power loss FIRMAN can...

Page 18: ...a ground fault circuit interrupter GFCI in any damp or highly conductive area such as metal decking or steel work DO NOT touch bare wires or receptacles DO NOT use generator with electrical cords whic...

Page 19: ...her Keep exhaust pipe clear of foreign objects Keep generator away from open flame Keep generator on a stable and level surface WARNING Surge Protection Voltage fluctuation may impair the proper funct...

Page 20: ...start up to permit engine and generator to stablize StartingtheGenerator RecoilStart LPG 1 Before starting the generator check for loose or missing parts and for any damage which may have occurred du...

Page 21: ...he LPG cylinder in the path of muffler outlet 9 Move the choke lever to the RUN position 11 Allow generator to run at no load for few minutes upon each initial start up to permit engine and generator...

Page 22: ...dicator light will become RED up to 4 minutes before goes off Starting the engine successfully during these 4 minutes will turn the indicator light GREEN 5 Disconnect all electrical loads from the gen...

Page 23: ...G MODE UNLESS THE FUEL SELECTOR SWITCH IS TURNED TO THE OFF POSITION AND THEN TURNED BACK TO THE LPG POSITION 9 Move the choke lever to the RUN position 4 Fully open the LPG cylinder knob 5 Turn the f...

Page 24: ...gle phase 60Hz electrical loads It is better to attach the item with largest load first CAUTION When applying a load do not exceed the maximum wattage rating of the generator when using one or more re...

Page 25: ...THE FUEL SELECTOR SWITCH IS TURNED TO THE OFF POSITION AND THEN TURNED BACK TO THE GAS OR LPG POSITION Unwanted Shutdown The generator cannot be started during or after the 4 minutes of FLASHING mode...

Page 26: ...n indication of a problem with the generator but only a problem with the flow of gas from the LPG cylinder If generator performance seems to be deteriorating at the same time that ice formation is obs...

Page 27: ...commendations Regular maintenance will improve the performance and extend the life of the generator See any authorized dealer for service The generator s warranty does not cover items that have been s...

Page 28: ...horoughly wash exposed areas with soap and water a Drain oil by removing the drain plug and the oil filler cap while the engine is warm Change engine oil every 100 hours for a new engine change oil af...

Page 29: ...c Tightly fasten the cup to main body making sure to avoid fuel leak SCREEN O ring CUP BODY b Remove spark plug using provided wrench Inspect spark plug for damage and clean with a wire brush before r...

Page 30: ...ating environment DO NOT expose the unit to extreme conditions excessive dust dirt moisture or corrosive vapours DO NOT use a garden hose to clean the generator Water can enter the generator through t...

Page 31: ...nductive vacuum siphon shutdown Drain fuel into approved container outdoors away from open flame Be sure engine is cool Do not smoke 4 FUEL STARVATION Start and run the generator until it stops from l...

Page 32: ...et engine switch to ON l position 2 Move fuel shutoff lever to ON l position 3 Fill crankcase to proper level or place generator on level surface 4 Clean or replace air cleaner 5 Fill fuel tank 6 Drai...

Page 33: ...PARTS DIAGRAM AND PARTS LIST P05701 PARTS DIAGRAM English Page 30 Support support arcaugusta com...

Page 34: ...FIRMAN 389cc Engine Parts Diagram English Page 31 Support support arcaugusta com...

Page 35: ...apor Hose Bracket Handle Flange Bolt M8 50 Pin Handle Fuel Tank Assy Grommet Fuel Tank Buffer Washer 336713544 357713529 336713546 336713547 336713549 336713548 336713540 357713530 336713551 357713531...

Page 36: ...20 Gasket Cylinder Head Air Cleaner Holder Nut M6 Stud Intake Gskt Insulator Cover Subassembly Cylinder Head Plate Subassembly Lifter Stopper NO Part Number Description Qty 1 1 1 1 1 3 1 6 1 1 1 1 1 1...

Page 37: ...iVi i i i Vi v i v V i i i i V v i iviV i i i L 7 i i Li i i i v i V i 7 9 7 i i U i U i v i V v L i i i v i i i i i i V i V U i Vi i v i v i i i v V V L i i U i i V V i L VV i v i v V v U V i V i i...

Page 38: ...gine is Designed built and equipped so as to conform with all applicable regulations adopted by the Air Resources Board and US EPA and Free from defects in materials and workmanship that cause the fai...

Page 39: ...ust manifold Catalytic converter Muffler gasket pulse valve 4 Air induction system including Intake pipe manifold Air cleaner 5 Crankcase breather assembly including Breather connection tube 6 Fuel ta...

Page 40: ...P N 357745450 Rev 03 Firman Power Equipment Inc Peoria AZ 85381 www firmangenerators com 8716 West Ludlow Dr Suite 6...

Reviews: