17
▲
/▼
Supplier passcode, scroll to
select the second three-digit number
ENTER
[F4]
If you entered the correct passcode, the display top line will show
COM
, and the next line will show
P0
, which represents the Closed position set point.
NOTE: Be sure ALL Previous Faults are CLEARED. Otherwise, you will NOT be able to
advance.
8.1.1 Changing from Commission / Adjust Ratio mode to Option Set mode
To enter the Option Set mode, first enter Commission Ratio mode or Adjust Ratio mode (see section
5
“Commissioning The Control" in the PPC6001, and NX6001 manuals) and press the
OPTS
key.
Commission / Adjust Ratio mode > OPTS [F1] > Option Set mode
8.1.2 Changing from Option Set to Commission / Adjust Ratio modes
To change from Option Set mode to Commission Ratio mode, press the
EXIT
key.
Option Set mode
→
EXIT [F1]
→
Commission ratio / Adjust Ratio mode
8.1.3 Exiting from Commission mode
To exit from any Commission mode you must be in the Commission/Adjust Ratio display mode, then
press the key labelled
RUN
and then
EXIT
. For example:
Commission ratio / Adjust Ratio mode > RUN [F4]> EXIT [F4] > Run mode
8.2 Using the Option Set mode
You can set up or adjust the various Option parameters given in section 5.
•
Go into Option Set mode as described in section 8.1.1 above
•
Use the
▲
/▼
UP/DOWN keys to select the Option parameter to be adjusted. The Option
parameter number is shown with a description on the first line, and the value in the second line:
Example at Option parameter =
1.0
and value
5
:
1.0 PowerUp Option
= 5 (0 to 360)
•
Use the
ADJ
and
BACK
keys to toggle between the top row (Option number) and the bottom
row (Option value).
•
Use the
▲
/▼
UP/DOWN keys to set or change the value of the option parameter. When the
correct value is selected, press the
ENTER
key to store the new value.
Repeat the process to select another Option parameter, and set or adjust the values as necessary.
When you have finished, exit from Option Set mode.