Appendix A.3
Checking Wiring and Settings
•
No COMS on Modbus RTU side. If the Tx/Rx LEDs are not flashing rapidly then there is a COM
issue. To fix this, check the following:
o
Visual observations of LEDs on MB485ETH-CG (
o
Check baud rate, parity, data bits, stop bits
o
Check Detector ID matches the correct device
o
Verify wiring
o
Verify the device was listed under the Web Configurator Active Profiles (
Section
•
No COMS on Modbus TCP/IP side. To fix, check the following:
o
Visual observations of LEDs on the MB485ETH-CG (
o
Check device address
o
Verify wiring
o
Verify all the Modbus TCP/IP device(s) were listed in the Web Configurator (
•
Field COM problems:
o
Visual observations of LEDs on the MB485ETH-CG (
o
Verify IP Address setting
o
Verify wiring
NOTE: If the problem still exists, a Diagnostic Capture needs to be taken and sent to technical
support. (