Firex FADCM Manual Download Page 7

7

UNDERSTANDING THE ALARM

CONDITION

AC power is present

Standby condition

Smart Quiet™ Low-Battery #1

Smart Quiet™ Low-Battery #2

Fault condition

Local CO condition is detected

Quick Quiet™ CO Reset is
activated

Remote signal is received from
another CO alarm

HORN

Horn beeps once per minute

Horn beeps once per minute

Horn sounds two quick beeps
every minute

Horn sounds 4 short tone 
patterns every 5 seconds

Horn sounds 4 short tone 
patterns every 5 seconds

Push-to-Test

(Local Test Only)

Local CO condition is latched

Alarm does not sound
and lights do not flash
when unit(s) is tested.

NOTE: 

Push and hold

Smart Button for at least
5 to 10 seconds if unit
does not sound!

1. Check that AC power is turned on (GREEN light ON);

check that a good battery is inserted correctly in the
battery compartment; check that the battery door is
tightly closed.

2. Turn off power. Remove alarm from mounting plate

and check that connector plug is securely attached.

3. Clean alarm (see “Cleaning” on page 9).

Interconnected smoke,
heat, or CO alarms do
not sound when Smart
Button is pushed to test
units.

1. Press and hold the Smart Button longer until the

second set of two quick beeps sounds to initiate the
remote test.

2. Check that remote alarms are receiving power and 

functioning properly

3. Alarm interconnect circuit problem. Replace

and retest.

4. On DC (battery powered) interconnected alarms,

remove alarm from mounting bracket and check that
the connector plug is securely attached.

5. On an interconnected series with both AC and AC/DC

powered units, wiring may have been improperly
connected. Have wiring checked by a licensed
electrician. Retest all alarms in the series.

GREEN light is not on.

1. Alarm may be functioning properly on DC (battery)

power if YELLOW light flashes once per minute.

2. Check AC power supply at fuse box or breaker panel.

3. Alarm wiring is improperly connected. Have wiring

checked by a licensed electrician. Retest the alarm.

PROBLEM

SOLUTION

TROUBLESHOOTING 

Press-and-Hold

(Local and Interconnect Tests)

DANGER

Always turn off power at main fuse box or circuit

breaker before taking troubleshooting action.

Local smoke is detected

Horn sounds 3 long tones, 
then pauses, every 4 seconds.

Initiating smoke alarm is latched

Quick Quiet™ False Alarm
Control™ is activated

Remote signal is received from
another smoke or heat alarm

Horn sounds 3 long tones, the
pauses, every 4 seconds

Interconnected CO
alarms sound with
smoke alarms when
Smart Button is pushed
to test units.

Indicates older CO alarms, without Smart Interconnect,
are sharing the same interconnect line and cannot distin-
guish between alarm signals for smoke or CO. Replace
with model COE, COEA or FADCM alarms.

Summary of Contents for FADCM

Page 1: ...uld this occur You must still test the alarm weekly to verify proper horn operation Trigger Alarm Locator TAL Most interconnect tests trigger all alarm horns simultaneously for the duration of the test This unique system alternates between a 10 second ALL ON cycle and a 50 second cycle where only the initiating alarm is sounding Alarm Controlled Interconnect Test In an interconnected system this f...

Page 2: ...red by the California State Fire Marshal Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows a smoke detector installed in each separate sleeping area in the vicinity but outside the bedrooms and heat or smoke detectors in the living rooms dining rooms bedrooms kitchens hallways attics furnace rooms closet...

Page 3: ...rms can only sound their alarms when they detect CO gas They do not sense heat flame or any gas other than carbon monoxide CO This alarm is designed to give audible warning that a dangerously high level of CO is present You must respond immediately to the CO alarm horn Smoke and CO alarms have limitations This alarm is not foolproof and is not war ranted to protect lives or property from fire Smok...

Page 4: ...d 3 Interconnected AC Only and AC DC Alarms 1 Remove the mounting plate Hold the alarm and turn the mounting plate clockwise to separate it from the back of the alarm 2 Hold the mounting plate against the ceiling or wall in the desired position and use a pencil to trace the inside of the mounting slots 3 Use a 3 16 5mm drill bit to drill through the center of the outlines you made in Step 2 4 Inse...

Page 5: ...OT PRESENT FOR ANY REASON AC POWERED SMOKE CO OR HEAT ALARMS WILL NOT OPERATE THIS ALARM SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION S STANDARD 72 National Fire Protection Association One Batterymarch Park Quincy MA 02269 Connect CO and smoke alarms to a single dedicated AC branch circuit If local codes do not permit such a wiring configuration or connection be ...

Page 6: ... a false alarm TO TEMPORARILY SILENCE AN ALARM NOTE These features temporarily quiet alarms but do not disable the sensor When you push the Smart Button during an alarm one of three things will happen 1 All interconnected alarms are silenced This means you pushed the button on the unit that actually triggered alarm Quick Quiet False Alarm Contro l 2 One unit still sounding an alarm the rest are si...

Page 7: ...ving power and functioning properly 3 Alarm interconnect circuit problem Replace and retest 4 On DC battery powered interconnected alarms remove alarm from mounting bracket and check that the connector plug is securely attached 5 On an interconnected series with both AC and AC DC powered units wiring may have been improperly connected Have wiring checked by a licensed electrician Retest all alarms...

Page 8: ...G AND MAINTENANCE Push the Smart Button to temporarily quiet the low battery signal for 10 hours The horn beeps once then two beeps then three beeps pauses and then sounds the full alarm when using the Smart Button to test The alarm is operating properly The Firex patented Horn Ramp Up feature lets you start the test sequence and move away from the unit before the full alarm horn sounds Alarm soun...

Page 9: ...ds the CO poisoning because they stay in the home where CO is present As CO levels rise the symptoms become more extreme At low levels people will suffer headaches and mild nausea At higher levels unconsciousness heart failure and even death can occur The following symptoms are related to CARBON MONOX IDE POISONING and should be discussed with ALL members of the household Mild Exposure Slight head...

Page 10: ...r this combination alarm Doing so will void your warranty If the alarm is not operating properly see Troubleshooting If you must return an alarm under warranty send the alarm in a well padded envelope with postage prepaid a note describing the nature of the difficulty and proof of date of purchase to In U S In Canada Invensys Controls Americas Invensys Controls Americas 28C Leigh Fisher Blvd Servi...

Reviews: