TEST PROCEDURES

OPERATIONAL TESTING
To determine the correct operation of the Firex Duct Smoke Detector, ensure power is connected and the green pilot led is illuminated.

The led on the detector head does not flash during the standby mode.  The led on the detector head will be permanently illuminated when
smoke is detected and the head is in alarm.

With the air handling unit shut down, and the clear cover removed, press and hold the test/reset button on the Firex Duct Unit.  The red alarm
led on the circuit board will be illuminated and the alarm relay outputs will change state.  Using a multimeter set to OHMS (or continuity
buzzer function on the meter) place the meter probes on the following terminals and ensure the contacts are closed (continuity) 8, 9-11, 12
when releasing the test/reset button these contacts will open.

The trouble contacts 13, 14, 15 will not change state in the event of a fire alarm, operational or functional testing.  The trouble contacts can be
tested by rotating the Apollo detector head counter-clockwise and removing the detector head.  This action will extinguish the pilot (green) led
and cause the trouble contacts to change state, 13, 14 will be closed (continuity)14, 15 will be open circuit.  Replacing the detector head and
rotating it clockwise until it locks, will cause the green pilot led to be illuminated and the unit will be operational, terminals 13, 14 will be open
circuit and 14, 15 will be closed (continuity).

FUNCTIONAL TESTING
Once operational testing is concluded the unit requires functional testing to determine the correct operation of the detector head.

With the clear cover removed and using the aerosol test smoke Apollo test gas part # 29600-105 or Home Safeguard test gas
part # RW-25S-TG (Obtainable from Air Products & Controls LTD.)  Spray the test gas directly at the detector head from a distance of 12
inches for 2 seconds.

CAUTION

SPRAYING FROM A DISTANCE CLOSER THAN 12 INCHES CAN CAUSE DETECTOR CONTAMINATION.

After 15 to 20 seconds the detector head will go into alarm, illuminating the detector head led and causing the duct unit functions to operate,
relays will change state and the remote accessories if attached will function.

If no test gas is available to conduct the testing, light a piece of clothesline (rope) and blow the flame out, hold the smoldering rope 3 inches
from the detector head and blow across the lit area towards the detector head, the alarm indicator will illuminate within one minute.

Should testing be required for simulated fire conditions, smoke bombs placed in the duct may not be suited for the particular detector head
selected and installed.

S60A Apollo ionization detector 55000-250 utilizes a radio active source as its means of detection and will detect smoke particles of between .1
and 1 micron in size.

S60A Photoelectric Detector 55000 - 350 operates on the principle of light scatter and will detect smoke particles of between 1 and 10 microns
in size.

When purchasing smoke bombs for functional testing, ensure smoke particle sizes comply with the criteria as described above.

MAINTENANCE

Each installation location must be assessed on its own merits.  If the protected area is of a very dirty nature then the Firex Duct units will have
to be checked and cleaned on a Quarterly basis or when cleaning is required.

As a guideline the Apollo detector head should be cleaned every six months or as required.

The best methods of cleaning are to vacuum the detector head thoroughly or to blow the detector head out using compressed air.

Do not use chemicals to clean the detector head housing as this could contaminate the detector head and damage the casing.

Sensing tubes must be inspected and cleaned in accordance with the schedule as determined above, to allow the free flow of air through the
sensing tube.

Form No. MA 2650    11/98 Rev. A.

4

2820 Thatcher Road, Downers Grove, IL 60515
PH: (630) 719-5500  FAX: (630) 719-4400

Summary of Contents for 2650-560

Page 1: ...s the presence of the input power and removal of the detector head THE TROUBLE CONTACTS TERMINALS 13 14 15 ARE SHOWN IN THE NON ENERGIZED CONDITION The trouble contact will not operate in the event of a smoke alarm The Firex Duct Detector models 2650 560 and 2650 561 will operate on one of the following input voltage sources 24V A C 24V D C 115V A C and 230V A C The duct smoke detector units are d...

Page 2: ...de air 5 When installing duct smoke units down stream of filters fires occurring in the filters will be detected but if the filters become blocked insufficient air flow through the duct unit will prevent the correct operation of the duct detector 6 Where possible install duct detectors upstream of air humidifies and downstream of dehumidifiers 7 To prevent false alarms the duct detector should not...

Page 3: ... pressure between the inlet and exhaust tubes The differential pressure between the two tubes should be greater than 0 01 inches of water and less than 1 2 inches of water Model Number Apollo Detector Model Number S60A Ionization Detector 55000 250 S60A Photoelectric Detector 55000 350 POWER REQUIREMENTS QUIESCENT CURRENT ALARM CURRENT 24V AC 35 mA 24V AC 74mA 24V DC 15 mA 24V DC 48mA QUIESCENT CU...

Page 4: ... inches for 2 seconds CAUTION SPRAYING FROM A DISTANCE CLOSER THAN 12 INCHES CAN CAUSE DETECTOR CONTAMINATION After 15 to 20 seconds the detector head will go into alarm illuminating the detector head led and causing the duct unit functions to operate relays will change state and the remote accessories if attached will function If no test gas is available to conduct the testing light a piece of cl...

Page 5: ... will be energized The green led will be illuminated When pressing the test reset button the red Alarm led will be illuminated In the event of a fire alarm certain equipment may have to be shut down A shut down will be achieved by interrupting the supply source to that particular piece of equipment when wired as indicated below EXAMPLE Fan Supply Source 7 9 NC C NO RELAY P P 1 Dedicated INPUT Volt...

Page 6: ...the detector head in alarm will be illuminated all other head leds will be off With multiple units connected a common reset will be achieved by interrupting the supply voltage REMOTE ACCESSORY WIRING Remote accessory terminals 16 to 20 are not supervised and the output voltage will be present when the duct detector is in alarm or the test reset switch is operated For the 0543 0544 accessories with...

Reviews: