Firetrol FTA2000 Series Installation And Maintenance Manual Download Page 4

 

 

 

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may 

not cause harmful interference, and (2) this device must accept any interference received, including interference that may 
cause undesired operation. 

 
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of 

the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment 

is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if 

not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. 
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be 

required to correct the interference at his own expense. 

“Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to 
operate the equipment.” 
 
Location 

The controller shall be located as close as practical to the motor it controls and shall be within sight of the motor. The 
controller shall be located or protected so that it will not be damaged by water escaping from the pump or pump 
connections. Current carrying parts of the controller shall be not less than 12 in. (305 mm) above the floor level.  
 

Working clearances around the controller shall comply with NFPA 70, National Electrical Code, Article 110 or C22.1, 
Canadian Electrical Code, Article 26.302 or other local codes. 
 

The controller is suitable for use in locations subject to a moderate degree of moisture, such as a damp basement. The pump 
room ambient temperature shall be between 39°F (4°C) and 104°F (40°C).  
 
The standard controller enclosure is rated NEMA 2. It is the installer's responsibility to insure that either the standard 

enclosure meets the ambient conditions or that an enclosure with an appropriate rating has been provided. Controllers must 
be installed inside a building and they are not designed for outside environment. The paint color may change if the controller 
is exposed to ultraviolet rays for a long period of time.  

 
Mounting 
The fire pump controller shall be mounted in a substantial manner on a single incombustible supporting structure. Wall 
mounted controllers shall be attached to the structure or wall using all four (4) mounting ears provided on the controller with 

hardware designed to support the weight of the controller at a height not less than 12 in. (305 mm) above floor level. Floor 

mounted controllers shall be attached to the floor using all holes provided on the mounting feet with hardware designed to 
support the weight of the controller. The mounting feet provide the necessary 12 in. (305 mm) clearance for current carrying 
parts. For seismic applications, the mounting arrangement should be rigid wall and base only. The structural engineer of 

record on the project shall be responsible for anchorage details. 
 
Storage 

If the controller is not installed and energized immediately, Firetrol recommend following the instructions from the chapter 3 

of the NEMA ICS 15 standard. 
 
Wiring and Connections 
Water Connections 

The controller must be connected to the pipe system according to the latest edition of NFPA20 and also to a drain pipe.  The 
water connections are on the left side of the controller.  The connection to the system pressure is a Male ½ NPT.  If a drain 
is present, the connection to the drain is a tapered connection for plastic tubing. 

 
Electrical Wiring 
The electrical wiring between the power source and the fire pump controller shall meet the latest edition of NFPA 20, NFPA 
70 National Electrical Code Article 695 or other local codes. Electrical wiring shall be typically sized to carry at least 125% 
of the full load current (FLC or FLA) of the fire pump motor. 

 

Summary of Contents for FTA2000 Series

Page 1: ...1 INSTALLATION AND MAINTENANCE GUIDE FOR MARKIII MEDIUM VOLTAGE ELECTRIC FIRE PUMP CONTROLLERS MODEL SERIES FTA2000...

Page 2: ...l start automatically on low pressure detection by the pressure sensor when the pressure drops below the cut in threshold MANUAL START The motor can be started by pressing the START push button regard...

Page 3: ...nd the selection of components Except in some cases the controller is also seismic approved and has been tested in accordance with the ICC ES AC156 IBC 2015 CBC 2016 OSHPD Special Seismic Certificatio...

Page 4: ...A 2 It is the installer s responsibility to insure that either the standard enclosure meets the ambient conditions or that an enclosure with an appropriate rating has been provided Controllers must be...

Page 5: ...rigid intermediate or liquid tight flexible metal conduit or Type MI cable and meet the requirements of NFPA 70 National Electrical Code or other local codes The number of conductors required varies...

Page 6: ...ng label is the most important label It must be read carefully to ensure the compatibility between the controller and the installation Verify that the controller is installed securely on the wall or o...

Page 7: ...he panel all in accordance with the specifications in order to minimize interference with other equipment Verify and or install the proper water connections for the water input and the drain They must...

Page 8: ...on then put the circuit breaker disconnecting means in ON position Verify the readings on the controller main screen Once the controller has booted up the First Start Up page appears The controller wi...

Page 9: ...2 L3 and L1 L3 nominal is the same as what is written on the fire pump controllers nameplate The fire pump controller will validate the nominal voltage automatically versus what it has been built for...

Page 10: ...the motor is tunring in the right direction by checking the Check on Normal Power selector box Once the motor rotation has been checked go back to the controller start up page and press the Verify pr...

Page 11: ...r system specifications Cut Out value will default to Cut In plus 10 PSI To manually enter the cut out select the check box besides it and enter the desired value optional When finished press the Serv...

Page 12: ...12 From the Home page verify that the displayed values are correct The First Start up is now completed The controller is fully installed and configured...

Page 13: ...icient and could lose the time after a shutdown Alarm Bell The alarm bell is activated under default faulty conditions stated by the NFPA20 standard Any of these conditions will energize the alarm bel...

Page 14: ...or no weekly test has been conducted During the test the pressure reading will drop to zero but the controller will not see it as a starting request This pressure drop will be recorded in the Pump Cur...

Page 15: ...creen will dim it s brightness to 25 After 10 minutes of inactivity on the Mark III the Black Screen screen saver will activate Its goal is to expand the lifetime of the LCD screen The screen saver wi...

Page 16: ...l drawings logs statistics and configuration For additional information on the History feature refer to the full manual Service Informations on how to reach technical support concerning the commission...

Page 17: ...rk on the Mark III will redirect to the download page A pdf version of the manual can be downloaded on an USB device The language displayed on the Mark III can be selected on this page Download Manual...

Page 18: ...18 Firetrol Inc 1 919 460 5200 3412 Apex Peakway Apex NC 27502...

Reviews: