Ammeter: Displays the actual current between the charger and the battery in amps. 

 
The battery: The battery will be red if it is in failure and green otherwise. The data shows the actual voltage of the battery 

and the charger in volts. 
 

Engine Speed icon: Will be green when running, read when in overspeed condition and gray otherwise. 

 
Low oil pressure icon: Red when a low-oil pressure alarm condition is active, gray otherwise. When cranking only, the 

status follows the engine output to allow testing the circuit continuity. 

 

High engine tempetaure icon: Red when a high engine temperature alarm condition is active, gray otherwise. 
 

The pressure gauge: It allows for a precise reading of the actual system pressure. The cut-in and cut-out are represented by 
a red and green triangle on the gage, allowing a quick comparison between the actual pressure and the set points.  

 
HOA Indicator: Displays the current mode. Hand, Off, Automatic. 
Shutdown mode: Displays if the shutdown on this controller is Automatic or Manual. 

 
Screen Saver 
After 5 minutes of inactivity on the MarkIII, the screen will dim it's brightness to 25%. After 10 minutes of inactivity on the 
MarkIII, the “Black Screen” screen saver will activate. Its goal is to expand the lifetime of the LCD screen. The screen 

saver will be instantly deactivated if the engine is running or if an alarm is activated. To manually deactivate it, simply 
touch the screen or any membrane button. After deactivation, the screen saver will always redirect to the “Home” page. It 
will also log off any user by resetting the security level to 0 and save any new modifications to the settings. 
 

 
 

Alarms (Menu) 

Configuration > Advanced > Alarms 

For full alarm list and information consult the full manual,

 Digitally available, see “Download manual” in section 9 

 

 

Config (Menu) 

Config 

For additional information about configuration please consult the full manual,

 Digitally available, see “Download 

manual” in section 9

 

 

 

History (Menu) 

History 

 

Alarms 

Configuration

 

History 

Summary of Contents for FTA1100 Series

Page 1: ...1 INSTALLATION AND MAINTENANCE GUIDE FOR MARK III DIESEL ENGINE FIRE PUMP CONTROLLERS MODEL FTA1100...

Page 2: ...2 push button regardless of the system pressure when the Main Selector switch is in the HAND position The Fuel Solenoid Valve will open as soon as a CRANK button is pressed and will remain in this sta...

Page 3: ...ay need to contact factory The equipment manufacturer is not responsible for the specification and performance of anchorage systems The structural engineer of record on the project shall be responsibl...

Page 4: ...ll four 4 mounting ears provided on the controller with hardware designed to support the weight of the controller at a height not less than 12 in 305 mm above floor level Floor mounted controllers sha...

Page 5: ...ller up on its legs for mounting Each leg has 3 holes on the bottom for anchoring to the floor or base plate Note Consult the appropriate job plans to determine controller mounting location Refer to t...

Page 6: ...onnections in accordance with the National Electrical Code local electrical code and any other authority having jurisdic tion 4 Refer to the appropriate field connection drawing for wiring information...

Page 7: ...ry charger 1 and CB2 protects battery charger 2 CB3 protects the control circuit from battery 1 and CB4 protects the control circuit from battery 2 Always follow this procedure when connecting or disc...

Page 8: ...s installed securely to the wall or on the mounting stand optional Verify the Main Selector Switch is in the OFF position This selector switch is also called the HOA and can be placed in 3 positions H...

Page 9: ...lled and tightened Refer to the silkscreen markings on the plastic cover Connect all cables between the engine control panel and the controller engine terminals Identified as U on the IO board diagram...

Page 10: ...10 Activate the disconnect switch if present and all breakers by setting them to the on position The controller will boot up for the first time...

Page 11: ...controller has booted up the First Start Up page appears Press the padlock icon and enter a valid authorization code The controller will automatically detect incomming power and proper battery charge...

Page 12: ...commissioned by an authorized engine representative or service dealer and that the exhaust pipe is connected properly Perform an engine start on both batteries individually by pressing the associated...

Page 13: ...des it and enter the desired value optional When finished press the Service Done button Any errors will be highlighted in red and if forced be logged in the controller s event logs From the Home page...

Page 14: ...ears of service the MarkIII battery may become less efficient and could lose the time after a shutdown Alarm Bell The alarm bell is activated under default faulty conditions stated by the NFPA20 stand...

Page 15: ...he MarkIII s LED extinguishes 3 Wait 10 seconds 4 Turn ON all disconnecting means Pressure Transducer Test The controller will test the pressure transducer at least once a week if no manual run test o...

Page 16: ...n will open a navigation menu on the left side of the screen 1 Go to Home page 2 Go to Alarms page 3 Go to Configuration page 4 Go to History page 5 Go to Service page 6 Go to Download Manuals page 7...

Page 17: ...s the current mode Hand Off Automatic Shutdown mode Displays if the shutdown on this controller is Automatic or Manual Screen Saver After 5 minutes of inactivity on the MarkIII the screen will dim it...

Page 18: ...l drawings logs statistics and configuration For additional information on the History feature refer to the full manual Service Informations on how to reach technical support concerning the commission...

Page 19: ...page A pdf version of the manual can be downloaded on an USB device The language displayed on the MarkIII can be selected on this page Additonnal Technical documentation is available inside the full...

Page 20: ...20 Firetrol Inc 1 919 460 5200 3412 Apex Peakway Apex NC 27502...

Reviews: