Man-1082EL_FIRETEC_01
Page 6 of 6
How To
Do This
Display
Comments
Disable sounders
step 1
Mode
Press button till
db is displayed
Disable sounders
step 2
Enter
Press button
Dot flashes to indicate
bells disabled.
General disablement
and Sounder
Fault/Disablement
indicators lit
Enable sounders
step 1
Mode
Press button till
db is displayed
Flashing dot indicates
bells disabled.
Enable sounders
step 2
Enter
Press button
Dot stops flashing to
indicate sounders are
enabled
Activate zone input
delays step 1
Mode
Press button till
Ad is displayed
Activate zone input
delays step 2
Enter
Press button
Dot flashes to indicate
that delays are active
if they have been set
in engineering mode
(refer to operation and
maintenance manual
configuration table)
De-activate zone
input delays
Mode
Press button till
Ad is displayed
Dot stops flashing to
indicate delays have
been de-activated
Return system to
normal
Enable
Control
Turn key and
remove
Leaves only
Alarm/Fault Warning
Silence and Lamp test
buttons operable
For service contact:
Telephone: