Aqualux AG Installation 

 

17

2b 

If installation is into a 

BUILT-IN CANOPY

: Construct the canopy box as per page 7.  

Ensure the holes for the wetback pipework are predrilled into the built-in canopy 
following the instructions in the Aqualux Built-In Canopy conversion kit. Install into 
framework following guides on pages 8-14 as applicable. 

 

Slide the firebox into the opening so that the outer casing return folds are flush 

 

with the finished fire surround. 

 

DUE TO NEW ZEALAND BEING AN EARTHQUAKE PRONE COUNTRY, IT IS 
IMPORTANT TO ANCHOR THE INSERT DOWN IN CASE OF EARTH 
MOVEMENT.  See diagram page 18 showing Typical Insert Installation. 

 

Make pipework connections to the wetback following the guide in Section 6 Wetback 
(page 19) and test.  

 

When installed into Built-in Canopy ensure pipework is sealed as per the instructions 
in the Aqualux Built-in Canopy conversion kit. 

 

Install Flue as per instructions on page 20 and 21 if installing in a masonry fireplace 
or page 8,9,10,11,12, 15 if using a  Built-in fire canopy (zero clearance box). 

 

Now that the firebox and flue are in position, 

place 25mm white kaowool blanket

 

(supplied) on top of casing

 

As this fire sources its combustion air from the chimney cavity/enclosure, the fire 
MUST be sealed around the front between the casing and the masonry or inbuilt 
canopy.  This is achieved by packing the yellow ISB insulation supplied between the 
casing and the masonry or inbuilt canopy at the FRONT ONLY to maximum depth of 
90mm.   

 
 

UNDER NO CIRCUMSTANCES SHOULD THE AIRPORTS ON THE 
SIDE OF THE HEATER BE RESTRICTED.  Refer diagram page 18. 

 
 

The fire sources its combustion air from the chimney cavity, not from the 
room where the fire is installed.  This ventilation air should be drawn down 
the chimney cavity from the air gap set up when the top spacer bracket holds 
the weather collar off from the outer flue casing enabling air to be drawn into 
the chimney cavity.  Failure to ensure this air supply will starve the fire of air 
and lead to poor performance. 

 
 
NOTE:  In the case of some insert fires into existing masonry fireplaces it may be necessary 

to install additional adventitious ventilation into the chimney cavity as per AS/NZ 
2918 3.4.1.2 to assist air flow into the fire..  This ventilation should not be 
taken/drawn from the room that the fire is installed in. 

 

Assemble and fit the fascia as per instructions on page 22. 

Summary of Contents for aqualux AG

Page 1: ...ons must be in accordance with these instructions Consult with the building authority having jurisdiction to determine the need for a permit prior to commencing the installation Failure to follow thes...

Page 2: ...e 15 Cavity Chimney Termination Page 18 Typical Insert Installation Diagram Page 20 Insert Flue System for Masonry Fireplace Page 21 Minimum Height of Flue Outlet PAGE ITEM 3 1 Warnings 4 Firebox Fasc...

Page 3: ...DO NOT USE FLAMMABLE LIQUIDS OR AEROSOLS IN THE VICINITY OF THIS APPLIANCE WHEN IT IS OPERATING Use caution when reloading with fuel Do NOT attempt to load fuel into the heater when the fire inside t...

Page 4: ...Aqualux AG Installation 4...

Page 5: ...LOOR PROTECTOR CONSTRUCTION An Insulated Floor Protector shall be a minimum thickness of 40mm consisting of 20mm of an approved insulation material i e 2 sheets of 10mm micorboard or superlux 10mm til...

Page 6: ...allation 6 3 BUILT IN FIRE CANOPY A Built In Fire Canopy is required if the fire is not being installed into a masonry fire place For Built In Fire Canopy installations see the following pages 6 7 8 9...

Page 7: ...Aqualux AG Installation 7...

Page 8: ...Aqualux AG Installation 8 BUILT IN FIRE CANOPY INSTRUCTONS FOR NON MASONARY INSTALLATION...

Page 9: ...Aqualux AG Installation 9...

Page 10: ...Aqualux AG Installation 10...

Page 11: ...Aqualux AG Installation 11...

Page 12: ...Aqualux AG Installation 12...

Page 13: ...Aqualux AG Installation 13...

Page 14: ...Aqualux AG Installation 14...

Page 15: ...Aqualux AG Installation 15 Built In Fire Canopy Instructions...

Page 16: ...eld is fitted under the mantel MANTEL using BUILT IN FIRE CANOPY FORTE AQUALUX Can NOT have a combustible mantel however if the mantel is made of a non heat sensitive material then the minimum distanc...

Page 17: ...place 25mm white kaowool blanket supplied on top of casing 8 As this fire sources its combustion air from the chimney cavity enclosure the fire MUST be sealed around the front between the casing and t...

Page 18: ...Aqualux AG Installation 18...

Page 19: ...PRIATE REQUIREMENTS OF ALL RELEVANT BUILDING CODES AND BEST PRACTICES For best performance apply the following rules 1 Keep it simple with the shortest and straightest possible pipe run 2 The heater s...

Page 20: ...plate supplied onto the chimney top The chimney plate must be weather sealed with silicone or mortar 4 Install chimney liner on top of the chimney plate 5 Ensure flue pipe is extended over the chimney...

Page 21: ...Aqualux AG Installation 21...

Page 22: ...nd tighten 7 The screw on the bay section may now require adjusting to support canopy 8 Fit upper cast grill on side locaters 9 Fit control knob FORTE AQUALUX 1 Remove screws fixed to lugs on firebox...

Page 23: ...HEWITSONS LIMITED Manufacturers of Lady Kitchener Contessa Coaster Bronte Viking Zealandia Royale Athena Forte Deco Plaza Aqualux 68 Austin Street PO Box 3231 HB Mail Centre Napier 4142 Phone 06 84382...

Reviews: