FireClass Lite 1.0 Product Information Download Page 8

2.2 FireClass Lite Express

FireClass Fire detection system FireClass Panels

8

Product Information and Design Application

 

Doc. version 1.0

The block schematic for the FireClass Lite panel is as shown in 
Fig.

 2.

Fig. 2: Typical Fire Detection and Alarm System using FireClass Lite Fire Alarm Control Panel

FIELD SUPPLY 24V

ALARM RELAY

FAULT RELAY

SOUNDER CIRCUIT 1

SOUNDER CIRCUIT 2

MAINS IN

+

-

24 V

BATTERY

FCNET

REMOTE

BUS

+

-

REPEATER

SERIAL

PORT 1

PRINTER

SERIAL

AR+

AR-

DET

DET

DET*

IB

CP

DIM

RIM

PLANT

DET*

SERIAL

PORT 2

CONFIGURATION

LIM800

CIM

EOL

CONTACT

EOL

AL+

AL-

KEY

DET - ADDRESSABLE DETECTOR

DET* - CONVENTIONAL DETECTOR

IB - ISOLATOR BASE

CP - CALLPOINT

DIM - DETECTOR INPUT MODULE

RIM - R E LAY INTE R FACE MODULE

CIM - CONTACT INPUT MODULE

LIM800 - LINE ISOLATOR

Summary of Contents for Lite 1.0

Page 1: ...Product Information and Design Application 120 515 093 Doc version 1 0 25 April 2012 FireClass Lite FireClass Addressable Fire Alarm Control Panels version 1 0...

Page 2: ...re reserved in particular but not limited to the rights of copying distribution and translation No portion of this documentation including the online help may be reproduced edited copied or distribute...

Page 3: ...iption Panel and Repeater 6 2 2 FireClass Lite Express 6 2 2 1 FIM Connection Details 10 2 3 Summary 11 2 4 Collected Specifications 11 2 4 1 Shock Vibration 11 2 4 2 Dimensions 11 2 4 3 Colour 11 2 4...

Page 4: ...Contents FireClassFiredetectionsystemFireClassPanels 4 Product Information and Design Application Doc version 1 0...

Page 5: ...aining on FireClass based systems is recom mended 1 5 Reference Documents For further information see the following documents that comprise the FireClass main user documentation set Installation and C...

Page 6: ...s Product Information and Design Application guide A 2 5 A power supply unit is fitted as standard It supports 7 Repeaters It has a 32 zone LED display The Autoconfiguration feature restricts the numb...

Page 7: ...ss Product Information and Design Application Doc version 1 0 7 Fig 1 Overall and Fixing Dimensions FireClass Lite 1 Knockouts 20 mm 26x 2 Knockout 25 mm 3 Knockout 20 mm 4 Knockouts 5 Mounting hole 5...

Page 8: ...e Fire Alarm Control Panel FIELD SUPPLY 24V ALARM RELAY FAULT RELAY SOUNDER CIRCUIT 1 SOUNDER CIRCUIT 2 MAINS IN 24 V BATTERY FCNET REMOTE BUS REPEATER SERIAL PORT 1 PRINTER SERIAL AR AR DET DET DET I...

Page 9: ...H RL1 RL2 RL4 RL3 T N O R F R E V OV V C N O R F FA FA A CE FB2 RV1 R R RV2 R R FB3 RL13 IC C C C C 1 C1 C C C 1 1 4 4 X3 IC22 X2 IC21 RL11 B P O O L M A R G O R P A P O O L M A R G O R P IC6 4 B F S1...

Page 10: ...ard connections All terminals accept solid stranded conductors from 0 5 to 2 5 mm2 Fig 4 FIM801 Lite board connection the labels match those on the FIM board 1 Shown in the no alarm position 2 Shown i...

Page 11: ...ircuits loops Points per loop Points per CIE Zones per loop Zones per panel Zone LEDs Batteries FireClass Lite 1 125 125 32 240 32 240 32 2 x 12 Ah Table 2 Numbers of loops zones and points Points can...

Page 12: ...and Humidity Stipu lations 2 4 9 EMC Product family standard EN50130 4 in respect of Con ducted Disturbances Radiated Immunity Electrostatic Dis charge Fast Transients and Slow High Energy EN 61000 6...

Page 13: ...be done IC field repair of the RS232 is not possible Some of the front cover connectors are not present in the FIM801 Lite board Loop expansion is not possible Network connection is not possible The...

Page 14: ...he Internet at www fireclass co uk United Kingdom FIRECLASS Hillcrest Business Park Cinder Bank Dudley West Midlands DY2 9AP United Kingdom FireclassSales tycoint com www fireclass co uk 120 515 093_F...

Reviews: