FIRECLASS Fire detection system 

Panel Accessories

Fixing instructions  Doc. version 1.0 

5/12

Installing the PCS800 on a 

FireClass FC702S Panel

To install the PCS800 Ethernet switch on a 
FC702S panel, complete these steps:
1 Mount the fixing elements (refer to item 3 in 

Fig. 5) with the screws provided on to the 
Ethernet switch housing.

2 Fix the Ethernet switch on to the chassis 

studs with nuts and washers (item 2).

3 Fix the Earthing cable (item 5) supplied with 

the switch accessories to the top of the 
Ethernet switch. Secure the cable with a fix-

ing screw (item 4) and connect the other end 
to the housing earthing bar.

4 Connect the DC power supply cable to the 

FC-FI connector. Refer to Table 4. Connect to 
XT6 or XT7, (or both if you require a redundant 
supply) and to the PCS800 connector.

5 If you require a redundant supply, use the 

same terminals on the PMM800 board and 
connect to V2+ and V2-.

6 Plug the DC power supply into the Ethernet 

switch.

7 Connect the Ethernet cabling.

Configuring the POS800-S 

and POS800-M Ethernet 

switches

To configure a POS800-S or a POS800-M Ether-
net switch, complete these steps:

1 Configure the DIP switch on the front of the 

Ethernet switch. Refer to Table 5.

Fig. 5: Installation of the PCS800 to the FireClass 
FC702S panel 
1 – Ethernet  switch
2 – Washers and nuts 
3 – Fixing  elements
4 – Earth cable fixing screw 
5 – Earthing  cable

1

3

2

4

5

2

3

1

3

4

5

CAUTION

Before configuring an Ethernet switch, 
ensure that you disconnect all devices 
that are connected to it (apart from your 
computer).

Redundant 
optical 
connection

Redundant 
metallic 
connection*

Single line 
connection

Ethernet 
switch no.1: 

Position1 - 
OFF. Position 
2,3,4 - ON

Ethernet 
switch no. 1:

Position 1,4 –
OFF. Position 
2,3 – ON

All positions 
OFF

Ethernet 
switch no. 
2,3,...:

Position 1,3 - 
OFF. Position 
2,4 - ON

Ethernet 
Switch no. 
2,3...:

Position 1,3,4 – 
OFF. Position 2 
– ON

-

Table 5: POS800-S/POS800-M configuration
* Supported on port 1 and 2 only

Summary of Contents for FC700 Series

Page 1: ... network is 254 and this is split between all devices repeaters the FC FI board and Ethernet switches For the maximum num ber of LNET GUI repeaters refer to the latest FireClass Express documentation The FireClass PCS800 Ethernet switch provides five 10 100Base T X RJ45 ports that connect it to the FC FI board the primary GUI and addi tional AC DC repeaters The PCS800 does not require additional c...

Page 2: ...ditionally connect the wire from pin 3 on the Ethernet switch to ISOL IN on the FC FI board and from V1 on the Ethernet switch to ISOL IN on the FC FI Refer to Fig 3 Use a minimum 16 0 2 wire not supplied Note Using a volt free relay contact on the Ethernet switch allows the panel to see faults which would otherwise go undetected for example a power port failure or an Ethernet port downlink You ca...

Page 3: ... cage 1 Ethernet switch 2 Slot cage holder 3 Screws 4 Slot cage holes 5 Fibre optic holder 4 1 2 3 1 2 3 4 5 24V Ͳ XT7 ISOL IN ISOL IN 24V Ͳ XT6 Pin 1 Pin 6 Reset buƩon 1 Fig 3 POS800 connectors overview The dashed line indicates optional switch fault monitoring 1 Press the reset button for 10 seconds to restore the switch to the factory default configuration ...

Page 4: ...ch housing 3 Connect the DC power supply to the Ethernet switch connector refer to item 4 in Fig 4 observing the correct polarity If you require a redundant power supply connect a minimum 16 0 2 wire not supplied 4 Connect the other end of the DC supply cable to the PMM800 board Refer to Table 4 5 If you require a redundant supply use the other pins on the same terminals on the PMM800 board and co...

Page 5: ...he PMM800 board and connect to V2 and V2 6 Plug the DC power supply into the Ethernet switch 7 Connect the Ethernet cabling Configuring the POS800 S and POS800 M Ethernet switches To configure a POS800 S or a POS800 M Ether net switch complete these steps 1 Configure the DIP switch on the front of the Ethernet switch Refer to Table 5 Fig 5 Installation of the PCS800 to the FireClass FC702S panel 1...

Page 6: ...dditional switches decrease the final byte of the IP address by 1 for example 192 168 1 252 or 192 168 1 251 The subnet mask is 255 255 255 0 in all instances For the maxi mum number of LNET repeaters refer to the latest of FireClass Express documentation Set the IP address of the LNET repeaters in FireClass Express and avoid conflicts with Ethernet switch IP addresses 6 To configure the fault rel...

Page 7: ... for R M ring master 5 DIP switch setting P F Power fault warning ON for enable OFF for disable R E Ring topology ON for enable OFF for disable R M Ring Master ON for enable OFF for disable R S Ring Select P1 P2L Port 1 and Port 2 P5 P6 Port 5 and Port 6 6 100 base fibre port on SFP Port 6 7 LED for SFP LINK ACT 8 100 base fibre port on SFP Port 5 9 10 100Base T X Ethernet ports 10 LED for Etherne...

Page 8: ...n Ring master Ring Slow blinking Ring enabled topology problem On Ring working normally Fault On Fault relay active Power failure or port failure 10 100Base T X Fast Ethernet ports LNK ACT On Port link up Blinking Data transmitted LINK On Link LED 100Base Fibre port on SFP LINK ACT On Port link up Blinking Data transmitted Table 6 Ethernet switch LED status ...

Page 9: ...lden GUSN102 2x62 5 125 OM1 fibre multi mode Table 7 Recommended cables for the POS800 M Ethernet switch Manufacturer Type Description Tight buffered cables Belden GUMT802 2 x 9 125 G 652D single mode Loose tube cables with jelly filled loose tube Belden GUSN802 2 x 9 125 G 652D single mode Table 8 Recommended cables for the POS800 S Ethernet switch Pig tail type MPN Manufacturer Length OS2 tight ...

Page 10: ...ixing instructions Doc version 1 0 Panel Accessories FIRECLASS Fire detection system Fig 7 Example of Ethernet switches configured in a ring topology ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 Switch 1 Switch 2 Switch 3 ...

Page 11: ...e detection system Panel Accessories Fixing instructions Doc version 1 0 11 12 Panel GUI Ͳ GUI Panel AC repeater 1 GUI TO ADDITIONAL REPEATERS AC repeater 2 ON 1 2 3 4 Fig 8 Wiring example single optical connection ...

Page 12: ...s reserved All specifications and other information shown were current as of document revision date and are subject to change without notice www fireclass net Tyco Fire Security GmbH Victor von Bruns Strasse 21 8212 Neuhausen am Rheinfall Switzerland Panel Accessories FIRECLASS Fire detection system ...

Reviews: