4/12

FC410BDM

FireClass

5 Verify the correct polarity of wiring before 

connecting the FC410BDM to the 
addressable loop circuit.

Mounting

Fit cover to backbox.

Address settings

The FC410BDM has a default factory set 
address of 255, this must be set to the loop 
address of the device using the FC490ST Loop 
Service Tool. The FC410BDM may be program-
med with the address prior to being installed by
using the internal programming port (see Fig.2
or after being installed by using the program-
ming port on the front cover (see Fig.3).

Note

: Once the address has been programmed, 

take note of the device location and address 
number, to include on site drawings.

Cabling

Cables are to be selected in accordance with the 
system design document and the requirements 
of the applicable standard. Two pairs of connec-
tion terminals (L+ and L-) are provided on the ter-
minal block. These terminals are used for 
connecting the module on to the addressable cir-
cuit. The maximum section of the cable that can 
be connected at any one terminal is 2.5mm

2

The section is calculated based on the characte-
ristics of the cable and the load.
Fig. 4 shows the Fireray 50/100 connected via a 
BTM800 Terminal Module.
Fig. 5 shows the Fireray 50/100 wiring diagram.

Ordering information

FC410BDM:

Beam Detector Module c/w 
Cover

BTM800:

Beam Terminal Module c/w 
Cover

Fireray 50:

5-50 Metres Reflective Beam 
Smoke Detector 12V-24V dc

Fireray 100:

50-100 Metres Reflective 
Beam Smoke Detector 12V-
24V dc

Recycling information

Customers are recommended to dispose of their 
used equipments (panels, detectors, sirens, and 
other devices) in an environmentally sound man-
ner. Potential methods include reuse of parts or 
whole products and recycling of products, com-
ponents, and/or materials.

Waste electrical and electronic 
equipment (WEEE) directive

The manufacturer reserves the right to change 
the technical specifications of this product 
without prior notice.

In the European Union, this label indi-
cates that this product should NOT 
be disposed of with household 
waste. It should be deposited at an 
appropriate facility to enable reco-
very and recycling.

Fixing Instructions  Doc. version 3.0

Summary of Contents for 555.800.766

Page 1: ...ch umdie Sen deeinheit mit Strom zu versorgen Mit dieser Option k nnen lange Kabelverl ufe vermieden werden Das zweite FC410BDM f r die Sendeeinheit ben tigt eine eigene Adresse Es versorgt und berwac...

Page 2: ...bares FC Brandmeldesystem nur zusammen mit dem FC410BDM Umgebungsbedingungen Betriebstemperatur De 10 C bis 55 C Lagertemperatur De 40 C bis 80 C Rel Luftfeuchte max 95 ohne Betauung Abmessungen Geh u...

Page 3: ...con nection terminals exposed The fascia plate is then fitted onto a standard dual gang back box with BESA fittings Features The FC410BDM Beam Detector module is capa ble of monitoring and signalling...

Page 4: ...cable that can be connected at any one terminal is 2 5mm2 The section is calculated based on the characte ristics of the cable and the load Fig 4 shows the Fireray 50 100 connected via a BTM800 Termin...

Page 5: ...pra il PCB lasciando accessibili soli i morsetti per i collegamenti La placca pu essere fissata su scatola dual gang o BESA Caratteristiche Il modulo per rivelatore lineare FC410BDM capace di controll...

Page 6: ...Rivelatore lineare di fumo riflettente 12V 24Vcc Informazioni sul riciclaggio Si consiglia ai clienti di smaltire i dispositivi usati centrali rilevatori sirene accessori elettronici ecc nel rispetto...

Page 7: ...a su vez en una placa de carcasa personalizada con una cubierta de protecci n sobre la PCI de forma que solo quedan al descubierto los terminales de cone xi n Esta placa de carcasa se instala en una...

Page 8: ...el bloque de terminales hay dos pares de terminales de cone xi n L y L Estos terminales se utilizan para realizar la conexi n al m dulo en el circuito direc cionable La secci n m xima de cable que se...

Page 9: ...10BDM fissata al coperchio FC410BDM sin la tapa 1 Programmieranschluss Address setting port Porta di programmazione Puerto de ajuste de la direcci n Fig 3 Kurzschlussisolator Vorderseite FC410BDM Faci...

Page 10: ...z Fireray 50 100 1 Programmieranschluss Address setting port Porta di programmazione Puerto de ajuste de la direcci n 2 FC linearrauchmelder modul Beam detector module Modulo per rivelatore lineare di...

Page 11: ...0 1 Programmieranschluss Address setting port Porta di programmazione Puerto de ajuste de la direcci n 2 FC linearrauchmelder modul Beam detector module Modulo per rivelatore lineare di fumo M dulo de...

Page 12: ...hnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice Tyco Fire Security GmbH Victor von...

Reviews: