Fireboy- Xintex FR-1000 Installation Manual Download Page 2

18131 Rev 3.0 
 

 

 
Installation  
 

WARNING!! 

This equipment is NOT intended for use in the following locations and requiring 
exceptional degrees of protection  
 
Locations requiring an exceptional degree of protection means - a location exposed 
to weather, seas, splashing, pressure-directed liquids, or similar moisture 
conditions. These locations include-- 
 

(1)  On deck; 
(2)  A machinery space; 
(3)  A cargo space; 
(4)  A location within a galley or pantry area, laundry, or water closet which 

contains a shower or bath; and 

(5)  Other spaces with similar environmental conditions. 

 

 

1.  The FR-1000/2000 should be mounted in a convenient location, preferably where 

the visual indicators may be readily seen. To install the display, you must first 
remove the screw on bezel. 

2.  Next, drill a 2-

1 /16” diameter hole into the panel. Slip the instrument through the 

hole and secure with the threaded bezel. 

3.  Install the detectors using directions included with each detector.   
4.  Wire the B and Battery 

 leads to an appropriate voltage source (9-

30Vdc) 

5.  On the FR-1000 wire the detector loop to the White and Black wires connected to 

White (Zone +) and Black (Zone 

). See following pages for diagrams. 

6.  The FR-2000 has two zones.  Wire the first zone the same as the FR-1000 and 

the second zone to Blue (Zone +) and Black (Zone -). 

7.  The buzzer comes pre-wired to the mating harness so no additional wiring 

required. 

8.  The pre-wired buzzer may be replaced with an alternative indicator.  The current 

draw of the device must not exceed .75A or 750mA. 
 

 
 
 