18131 Rev 3.0
2
Installation
WARNING!!
This equipment is NOT intended for use in the following locations and requiring
exceptional degrees of protection
Locations requiring an exceptional degree of protection means - a location exposed
to weather, seas, splashing, pressure-directed liquids, or similar moisture
conditions. These locations include--
(1) On deck;
(2) A machinery space;
(3) A cargo space;
(4) A location within a galley or pantry area, laundry, or water closet which
contains a shower or bath; and
(5) Other spaces with similar environmental conditions.
1. The FR-1000/2000 should be mounted in a convenient location, preferably where
the visual indicators may be readily seen. To install the display, you must first
remove the screw on bezel.
2. Next, drill a 2-
1 /16” diameter hole into the panel. Slip the instrument through the
hole and secure with the threaded bezel.
3. Install the detectors using directions included with each detector.
4. Wire the B and Battery
–
leads to an appropriate voltage source (9-
30Vdc)
5. On the FR-1000 wire the detector loop to the White and Black wires connected to
White (Zone +) and Black (Zone
–
). See following pages for diagrams.
6. The FR-2000 has two zones. Wire the first zone the same as the FR-1000 and
the second zone to Blue (Zone +) and Black (Zone -).
7. The buzzer comes pre-wired to the mating harness so no additional wiring
required.
8. The pre-wired buzzer may be replaced with an alternative indicator. The current
draw of the device must not exceed .75A or 750mA.