WIRELESS INTERLINK - WSM-F-NEU and WHM-F-NEU
The WSM-F-NEU and WHM-F-NEU are designed to be wirelessly interlinked with up to 50 products within
the Wi-Safe 2 product range. They are not designed to communicate with wireless alarms from other
ranges or manufacturers. These alarms need to be ‘learned-in’ or interlinked in order to communicate with
each other. If one alarm activates, all other interlinked alarms will also sound.
Wi-Safe 2 eliminates the need for interconnecting wires around a property making future system
modifications easy and cost effective. AC Smoke and Heat alarms will still need a mains supply in
accordance with your local Building Regulations.
IMPORTANT:
Obstructions such as steel reinforcement in concrete could block or impede the wireless
signal. While the wireless range is over 200 m in clear air / clear line of sight, the effective range may be
reduced by walls and other obstructions in the building. It is recommended not to exceed 35 m as the
maximum distance between alarms in a network.
DO NOT:
• Exceed the maximum of 50 alarms interlinked in a network.
• Connect FireAngel alarms to any models produced by another manufacturer.
WIRING KEY
= Live
= Neutral
= Earth
= Wireless Interlink
Mains 230V AC
Power Supply
(from downstairs circuit)
Mains 230V AC
Power Supply
(from upstairs circuit)
×
Line up the arrow on the base plate
with the
sounder on the alarm and gently apply pressure
until the alarm clicks into place. Switch on the
mains electricity supply.
Check that the green LED is on and that the red
LED is flashing once approximately every 45
seconds. The LEDs are located on the front of the
alarm.
HARDWARE INTERCONNECT - SM-F-NEU and HM-F-NEU
For multiple alarm installations use a ‘three core and earth’ style cable between all the alarms to be
interconnected. Connect the interconnect cable between each alarms 'I' terminal. The interconnect wire
(minimum 0.75 mm
2
cable) must be treated as Live, it should be insulated and sheathed.
DO NOT
:
• Exceed the maximum of 30 interconnected alarms on a network.
• Exceed 250 m of connecting wire per circuit.
• Connect FireAngel alarms to any other models produced by another manufacturer.
Mains 230V AC
Power Supply
WIRING KEY
= Live
= Interconnect
= Neutral
= Earth
To other alarms
if fitted
×