FSC Model No.

 

FS10-CS

TM

 

 

Long Range, Two-Stage, Multi-Spectral 

Quick Response, Digital, Electro-Optical

 

Fire Detector

 

with

 

Card Controller  OPTION 

2FLCS

 

 

for 

AUTOMOTIVE PAINT 

APPLICATIONS 

 

Installation Guide 

and 

Operating Manual

 

 

 

 

Fire Sentry Corporation (FSC)  

 

23311 La Palma Avenue  

 

Tel.:  714-694-2700 

Yorba Linda, California 92887 

Fax:  714-694-2701

 

 

Summary of Contents for FS10-CS

Page 1: ...______________ FSC Model No FS10 CS TM Long Range Two Stage Multi Spectral Quick Response Digital Electro Optical Fire Detector with Card Controller OPTION 2FLCS for AUTOMOTIVE PAINT APPLICATIONS Inst...

Page 2: ...Analysis FireBusI FireBusII FirePic FirePicII FirePicIII FirePix FirePicture FSC Fire Sentry Corporation Fire Sentry Corp FSX All FSX Nomenclature Variations such as FS2 FS2X FS3 FS3X FS4 FS4X FS5 FS5...

Page 3: ...2 1 1 Power 11 2 1 2 Card Controller Installation and Wiring 11 2 2 Detector Views 11 2 3 Wiring Flame Detectors 13 2 4 Mounting Locations 13 2 4 1 Mounting Flame Detectors 13 2 4 2 Mounting Card Con...

Page 4: ...Pre Set Relay Configuration For a spray gun fireball type fire Alert condition is declared within 0 5 seconds In this case both K2 and K3 Signal Relays energize simultaneously and close K2 and K3 Rel...

Page 5: ...field of view is 90 45 horizontal and vertical 1 5 4 Environmental Range The operating and storage temperature ranges of the Detector are from 40 o C to 85 o C 40 o F to 185o F The Detector humidity...

Page 6: ...Card Controller s LEDs to indicate Normal Operation Fire Early Warning FEW Alert Fire Alarm or Fault conditions Communicates externally to an IBM compatible PC desktop or laptop computer through the b...

Page 7: ...ontroller For example if twelve Fire Detectors are required for a particular installation three BMAs of Part No CCBPMA1 4 will be required Each Card Controller is secured to the BMA with two captive s...

Page 8: ...r with Card Controller OPTION 2FLCS INSTALLATION GUIDE and OPERATING MANUAL Fire Sentry Corporation Document No 1527 002 Rev E Copyright 2009 All Rights Reserved Page 8 Figure 1 Backplane Mounting Ass...

Page 9: ...our Flame Detectors each with their four wire cabling and for inputting and looping through 24 VDC electrical power for the Card Controllers For details refer to Table 4 Connector J8 Not used Figure2...

Page 10: ...Connector J2 Provides screw down terminals for four signal relay outputs for a single Card Controller Provides screw down terminals for connecting one Detector with its four wire cabling and for input...

Page 11: ...S 485 or RS 232 which stipulate that the cable shall have minimum 70 Ohm impedance to frequencies greater than 100 kHz The wire resistance shall not exceed 10 Ohms per conductor for the full length of...

Page 12: ...LCS INSTALLATION GUIDE and OPERATING MANUAL Fire Sentry Corporation Document No 1527 002 Rev E Copyright 2009 All Rights Reserved Page 12 2 09 4 66 1 10 0 67 4 38 2 40 NPT 1 50 Figure 4 Flame Detector...

Page 13: ...and ceilings to avoid line of sight blockage 2 4 2 Mounting Card Controllers The Card Controllers are only to be mounted on Card Controller Backplane Mounting Assemblies The Card Controller is not des...

Page 14: ...a Fault condition 5 will occur If Detector switch 2 is set for position 2 3 4 5 or 6 a Fault condition 5 will occur 2 6 FS10 CS Card Controller Option 2FLCS DIP Switch 1 Settings Use a small flathead...

Page 15: ...d the event in the Fault Event History file and de energize the Fault relay Faults generally occur for the following reasons Failure in the wiring such as a severed cable or loose terminations Hardwar...

Page 16: ...Controller yellow LED turns on Detector s temperature operational range is exceeded Re locate the Detector to a cooler area if the Detector is not permanently damaged Yellow Card Controller Fault LED...

Page 17: ...2 Next turn the Detector top cover counter clockwise until the top cover is removed 3 Using a screwdriver turn the three captive screws counter clockwise that secures the black Flame Detector Module...

Page 18: ...lame Detector Connector Pin Outs J1 Connector FLAME DETECTOR Module PIN WIRE COLOR 1 DC Return Not Chassis Earth Ground BLACK 2 Data A RS 485 COMM A GREEN 3 Data B RS 485 COMM B WHITE 4 DC Voltage RED...

Page 19: ...2 A Alert Fire Early Warning 5 K2 B Relay Normally Open DETECTOR 1 6 K3 A Alert Fire Early Warning 7 K3 B Relay Normally Open 8 K4 A Fire Alarm Relay 9 K4 B 10 Not Used 11 K1 N C 12 K1 COMMON Fault Re...

Page 20: ...ght 2009 All Rights Reserved Page 20 6 K3 A Alert Fire Early Warning 7 K3 B Relay Normally Open 8 K4 A Fire Alarm Relay 9 K4 B 10 Not Used 11 K1 N C 12 K1 COMMON Fault Relay 13 K1 N O 14 K2 A Alert Fi...

Page 21: ...DATA B 4 DETECTOR Voltage In 5 DETECTOR Voltage Return 6 DATA A DETECTOR 2 7 DATA B 8 DETECTOR Voltage In 9 DETECTOR Voltage Return 10 DATA A DETECTOR 3 11 DATA B 12 DETECTOR Voltage In 13 DETECTOR Vo...

Page 22: ...ne Relay Connectors Flame Detectors 1 and 2 1 K1 N C 2 K1 COMMON Fault Relay 3 K1 N O 4 K2 A Alert Fire Early Warning 5 K2 B Relay Normally Open DETECTOR 1 6 K3 A Alert Fire Early Warning 7 K3 B Relay...

Page 23: ...A DETECTOR 1 3 DATA B 4 DETECTOR Voltage In 5 DETECTOR Voltage Return 6 DATA A DETECTOR 2 7 DATA B 8 DETECTOR Voltage In 9 PIN NOT USED 10 PIN NOT USED 11 PIN NOT USED 12 PIN NOT USED 13 PIN NOT USED...

Page 24: ...sed 6 K1 N C 7 K1 COMMON Fault Relay 8 K1 N O 9 K2 A Alert Fire Early Warning 10 K2 B Relay Normally Open 11 K3 A Alert Fire Early Warning 12 K3 B Relay Normally Open 13 K4 A Fire Alarm Relay 14 K4 B...

Page 25: ...rs and BMAs are NOT required if the FS System 10 Wall Mounted Controller is used Each BMA is a rectangular printed circuit board with removable external wiring connector s Each plug in Card Controller...

Page 26: ...le Covers Part No EXPL 1 This extension is used to install or remove the FS System 10 Disposable Protective Coversin hard to reach areas The pole extends in three sections to a length of 11 feet 6 6 A...

Page 27: ...gh Temp Fault 16 Humidity Range 5 Internal Problem 17 Location 5 Manual Testing 5 Replacement 17 Temperature Range 5 Wiring 13 Explosion proof 5 Fault 15 Detector 17 Relay 15 Field of View 5 FirePic 4...