OPERATING INSTRUCTIONS
Technical Data
Gas Type:
Propane
Maximum Inlet Pressure
: 16bar
Nominal Outlet Pressure
: 30/37mbar
Capacity
: 1.5kg/h
Temperature Limitation
: -20
℃
to 50
℃
Inlet connection
: Quick connection G59
Outlet connection
: Non thread hose connection
Reference standard
: EN 12864
T
he pressure regulator and hose assembly supplied with the appliance must be
used.
•
The installation must conform to local codes, or in the absence of local
codes, with the standard for the storage and handling of liquid petroleum
gases.
•
A dented, rusted or damaged tank may be hazardous and should be checked
by your tank supplier. Never use a tank with a damaged valve connection.
•
The tank must be arranged to provide for vapor withdrawal from the
operating cylinder.
•
Never connect an unregulated tank to the heater.
•
The tank must have a connection device compatible with the connection for
the appliance.
• Do not store a spare LP-gas
cylinder under or near this
appliance.
T gÐgµ¿Ú¿Ág¿UÓ_gµ¿LgÓ_
80 percent full.
• Place the dust cap on the
cylinder valve outlet whenever
the cylinder is not in use. Only
install the type of dust cap
on the cylinder valve that is
provided with the cylinder
valve. Other types of caps or
plugs may result in leakage of
propane.
10
•
For use outdoors or in amply ventilated areas.
•
An amply ventilated area must have a minimum of 25 % of the surface area
open.
•
The surface area is the sum of the walls surface. (See figure)