5. Press 

1

 to display the following:

6. Press 

down arrow

 key once to display the following:

7. Press 

to display the following:

8. Press 

to program NAC 1 or press 

to program NAC

2.  The following will be displayed (the # symbol will
be replaced by 1 or 2):

9. Press 

to display the following:

10. Press 

down arrow

 key once to display the following:

@@@@SYSTEM@SETUP
1=TROUBLE@REM@@OFF

2=BANNER
3=TIME-DATE

@@@@SYSTEM@SETUP

1=TIMERS

2=NAC
3=RELAYS

@@@@NACS

1=NAC@1
2=NAC@2

@@@@NAC@#

1=ENABLED@@@YES
2=TYPE
3=SILENCEABLE

@@@@@@@NAC@TYPE
1=BELL

2=HORN
3=STROBE

@@@@@@@NAC@TYPE

1=SYNCED@STROBE
2=AUDIBLE

3=SIREN@CIRCUIT

11. Press 

to program the NAC as a synchronized strobe circuit.

The display will return to the following:

12. Press the 

down arrow

 key three time to display the following:

13. Press 

to display the following:

14. Select the type of synchronized circuit according to the
       manufacturer's devices installed on the NAC by pressing the

corresponding number key.  Continue with the programming
of the second NAC if desired.
When all programming is completed, repeatedly press the

ESC 

(Escape) key to store the program information and exit

Programming mode.

@@@@NAC@#

1=ENABLED@@@YES
2=TYPE
3=SILENCEABLE

@@@@@NAC@#
1=SYNC@TYPE

@@@@@NAC@SYNC@TYPE
1=SYSTEM@SENSOR
2=WHEELOCK

3=GENTEX

Summary of Contents for MS-9600

Page 1: ...tions as well as to avoid random activation which could cause a hazardous condition The FACP can be programmed to operate with a variety of manufacturer s devices Important When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and the synchronization feature is selected only the audible devices will be turned off if the Silence key is pressed ...

Page 2: ...EABLE NAC TYPE 1 BELL 2 HORN 3 STROBE NAC TYPE 1 SYNCED STROBE 2 AUDIBLE 3 SIREN CIRCUIT 11 Press 1 to program the NAC as a synchronized strobe circuit The display will return to the following 12 Press the down arrow key three time to display the following 13 Press 1 to display the following 14 Select the type of synchronized circuit according to the manufacturer s devices installed on the NAC by ...

Page 3: ...rol panel keypad will display the following LCD screen 2 Press 1 to display the following 3 Press down arrow key four times to display the following 4 Press 3 to display the following 5 Press 3 to print the detector sensitivity data for all addressable smoke detectors installed on the system Refer to the sample printout on the following page for information on interpreting the data Note If a print...

Page 4: ...amber Drift compensation performs the following functions Allows a smoke detector to retain its original ability to detect actual smoke and resist false alarms even as dirt and dust accumulate Reduces maintenance requirements by allowing the control panel to automatically perform the periodic sensitivity measurements required by NFPA Standard 72 The FACP software also provides filters to remove tr...

Page 5: ...pt to use this feature since it is not yet functional in this product Information on the availability of this feature will be made known on the manufacturer s internet site along with details on how to upgrade existing software 2 Printer Supervision Refer to the 9600 manual page 92 for information on this option Printer supervision when enabled will typically detect the removal of the printer cabl...