Fire-Lite CMF-300-6 Installation And Maintenance Instructions Manual Download Page 3

and B operation, DO NOT set the lowest address above 154, as the 
other modules will be assigned to nonexistent addresses. 

NOTE:

 Some panels support extended addressing. In order to set 

the  module  above  address  99  on  compatible  systems,  carefully 
remove the stop on the upper rotary switch (see Figure 7). If the 
panel does not support extended addressing, do not set the lowest 
address above 94.
4.  A  shunt  is  provided  to  disable  a  maximum  of  three  unused 

modules (see Figure 8). Modules are disabled from the highest 
address and work downward. If two modules are disabled, the 
lowest four addresses will be functional, while the highest two 
will be disabled. For example, if the shunt for Address Disable 
is placed on “two” and the base address switch is set to 28, 
the modules will be assigned to 28, 29, 30 and 31, disabling 
the highest two positions.

NOTE:

 In Class A operation, placing the small shunt on “disable 

3˝ will disable all three addresses. Placing the small shunt on “dis-
able 2˝ will disable two out of the three addresses. For example, 
if the address switch is set to 28 and the small shunt is placed on 
“disable 2˝, addresses 30 and 32 will be disabled while address 
28 will be enabled.
5. There is a short circuit protection option for each address. The 

board is shipped with short circuit protection disabled for each 
address represented by six large shunts on the “Disable Short 
Circuit Protection” area. To enable short circuit protection for 
an address, remove the corresponding pins from the “Disable 
Short Circuit Protection” area. When enabled, the module will 
not switch power supply if a short circuit condition exists on a 
notification appliance circuit.

NOTE:

  Power  must  not  be  applied  to  the  unit  when  changing 

functionality of the shunts.

NOTE:

 Place unused shunts on single pin to store on board for 

future use.

NOTE:

  The  power  supply  monitoring 

feature is currently not supported.

NOTE:

 SLC wiring is the top terminal 

block,  notification  appliance/power 
supply is the bottom.

NOTE: 

Whether  in  Class  B  or  Class 

A  wiring,  power  supply  monitoring 
and  short  circuit  protection  must  be 
enabled on the NAC circuits that are sharing a power supply.

NOTE:

  Short  circuit  protection  can  only  be  disabled  if  a  power 

supply is not being shared by multiple NACs.

Figure 8:

ENABLE POWER SUPPLY MONITOR

DISABLE SHORT CIRCUIT PROTECTION

SYNC GENERATOR

SIDE VIEW:

TOP VIEW:

SLC WIRING TERMINAL

NOTIFICATION APPLIANCE/ 
POWER SUPPLY TERMINAL

DISABLE 

1

DISABLE 

2

DISABLE 

3

A/B SELECT

C0228-01

F300-21-00 

I56-1874-011

The steps in Figures 6a and 6b describe and illustrate module in-
stallation when the rear chassis position and the position in front 
of it will be filled. Front position installation is possible only if the 
rear position is filled with a module.

Figure 6a: Installation of CMF-300-6 module in a rear    
 

chassis position, method two

1

 

C0225-00

Step 1:  Insert the bottom edge of the CMF-300-6 module down  

  

into a rear slot of the chassis.

Step 2:  Carefully swing the upper edge of the board towards    

  

the back of the chassis until it touches the short stand  

  

off attached to the chassis.

Step 3:  Align the long standoff with the short standoff and tighten.

Figure 6b: Installation of CMF-300-6 module in front  

 

 

chassis position

2

3

1

C0226-00

Step 1:  Insert the bottom edge of the CMF-300-6 module down  

  

into a front slot of the chassis.

Step 2:  Carefully swing the upper edge of the board towards    

  

the back of the chassis until it touches the 1

1

/

4

˝  

 

  

(31.75mm) standoffs installed on the rear module.

Step 3:   Align two 4-40 screws with the two standoffs and tighten.
Step 4:  Address and wire the modules according to the    

  

instructions in this manual.

WIRING

NOTE:

  All  wiring  must  conform  to  applicable  local  codes,  ordi-

nances, and regulations.
1.  Install module wiring in accordance with the job drawings and 

appropriate wiring diagrams.

2.  All  wiring  to  the  CMF-300-6  is  done  via  terminal  blocks.  In 

order  to  properly  make  electrical  connections  strip  approxi-
mately 

1

/

4

˝ of insulation from the end of wire, sliding the bare 

end of the wire under the clamping plate screw.

3.  Set the address on the modules per the job drawing. Use the 

rotary code switches to set the address of the first module (be-
tween 01 and 154).

In  Class  B  operation,  the  remaining  modules  are  automatically 
assigned  to  the  next  five  higher  addresses.  For  example,  if  the 
base  address  switch  is  set  to  28,  the  next  five  modules  will  be 
addressed to 29, 30, 31, 32, and 33.
In Class A operation, a maximum of three Class A circuits are avail-
able. For example, if the base address switch is set to 28, 30 and 32 
will be automatically assigned to the modules while 29, 31 and 33 
are available to be used for other modules on the SLC. For Class A 

TENS

0

7 8

6

5

4

3

2

1

9

10

11

12

13

14

15

Figure 7:

C0227-00

Summary of Contents for CMF-300-6

Page 1: ...to 49 C Humidity 10 to 93 Non condensing Dimensions 6 8 H x 5 8 W x 1 25 D Accessories CH 6 Chassis BB 6 Cabinet BB 2 Cabinet Wire Gauge 12 18 AWG Max NAC Circuit Line Loss 4 VDC Power Rating Per Cir...

Page 2: ...Lite COMPONENTS Following are descriptions of the CMF 300 6 mounting frame works There are two mounting options for CMF 300 6 modules Up to six CMF 300 6 modules can be installed on a CH 6 in a BB 6...

Page 3: ...ER SUPPLY MONITOR DISABLE SHORT CIRCUIT PROTECTION SYNC GENERATOR SIDE VIEW TOP VIEW SLC WIRING TERMINAL NOTIFICATION APPLIANCE POWER SUPPLY TERMINAL DISABLE 1 DISABLE 2 DISABLE 3 A B SELECT C0228 01...

Page 4: ...pplies EOL relays and notification appliances must be UL listed for fire protection signaling applications WIRING NOTES Power limited circuits must employ type FPL FPLR or FPLP cable as required by Ar...

Page 5: ...0 RED VIO VIO RED BLK BLK 47K NOTE EOL RELAY COIL CONNECTIONS MUST BE MADE USING EOL RELAY CONNECTOR ASSEMBLIES ON T10 T16 IN EVENT THAT ALL NACS ON THE PCB HAVE DEDICATED SUPPLIES Figure 10 Example o...

Page 6: ...CTION MANUAL FOR WIRE REQUIREMENTS POWER LIMITED AND SUPERVISED TOP OF T0 EOLR 1 TYP RED VIO VIO RED BLK BLK Figure 12 Example of Class A Style Z NAC configuration with a single supply shared by 2 NAC...

Page 7: ...2 3 4 5 6 7 8 9 0 7 8 6 5 4 3 2 1 9 10 11 12 13 14 15 EXTERNAL POWER SUPPLY PCB 1 PCB 2 VIEW A A C0233 00 FCC Statement This device complies with part 15 of the FCC Rules Operation is subject to the...