BEFORE INSTALLING

This  information  is  included  as  a  quick  reference  installation 
guide. Refer to the appropriate Fire•Lite control panel installation 
manual  for  detailed  system  information.  If  the  modules  will  be 
installed  in  an  existing  operational  system,  inform  the  operator 
and local authority that the system will be temporarily out of ser-
vice. Disconnect the power to the control panel before installing 
the  modules.  This  system  contains  static  sensitive  components. 
Always ground yourself with a proper wrist strap before handling 
any circuits so that static charges are removed from the body. The 
module housing should also be grounded.

NOTICE:

 This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

The  CMF-300-6  Six  Supervised  Control  Module  is  intended  for 
use in an intelligent alarm system. Each module is intended for 
switching applications involving AC or DC which require wiring 
supervision. A common SLC input is used for all modules. Each 
module has its own address. A pair of rotary code switches is used 
to set the address of the first module from 01 to 154. The remain-
ing modules are automatically assigned to the next five higher ad-
dresses. Provisions are included for disabling a maximum of three 
unused  modules  to  release  the  addresses  to  be  used  elsewhere. 
Each module also has panel controlled green LED indicators. The 
panel can cause the LEDs to blink, latch on, or latch off.
In  order  to  synchronize  strobes,  horn/strobes,  and  speaker/
strobes, a SYNC-1 accessory card (sold separately) must be used 
with the CMF-300-6. See the SYNC-1 installation manual for de-
tails on how to install.

F300-21-00 

I56-1874-011 

Fire•Lite Alarms, Inc. One Fire•Lite Place, Northford, CT 06472 203-484-7161

SPECIFICATIONS

Normal Operating Voltage: 

15-32 VDC

Stand-By Current: 

2.25 mA

Alarm Current: 

35 mA (assumes all six relays have been switched once and all six LEDs solid on)

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10 to 93% Non-condensing

Dimensions: 

6.8˝H x 5.8˝W x 1.25˝D

Accessories: 

CH-6 Chassis; BB-6 Cabinet; BB-2 Cabinet

Wire Gauge: 

12-18 AWG

Max. NAC Circuit Line Loss: 

4 VDC

Power Rating Per Circuit (Speakers): 

63 W @ 70.7 VAC; 50 W @ 25 VAC

Maximum NAC Current Ratings: 

For class B wiring systems, 3A; For class A wiring systems, 2A

CMF-300-6 Six Supervised Control Module 

Installation and Maintenance Instructions

Each module has terminals for connection to an external supply 
circuit  for  powering  devices  on  its  NAC.  Each  supply  must  be 
power limited and its voltage/current limits must be at or below 
those  specified.  There  is  a  short  circuit  protection  monitor  for 
each module. This is provided to protect the external power sup-
ply against short circuit conditions on the NAC.

Included:
Shipped on Board:

(1) 

Small shunt in Class A/B position 

 

(Shipped in Class B position, remove shunt for Class A) 

(6) 

Large shunts on Enabled Power Supply Monitor 

(6) 

Large shunts on Disable Short Circuit Protection 

(3) 

Large shunts on Sync Generator

(7) 1 × 4 

TERMINAL 

BLOCKS

(7) 1¼˝ (32mm) STANDOFFS 

(15) LARGE 

SHUNTS

(4) MACHINE SCREWS

(2) NUTS

(5) SHORT POWER 

SUPPLY JUMPERS

(2) SMALL 

SHUNTS

(1) LONG POWER SUPPLY JUMPER

(2) EOL RELAY 

CONNECTOR 

ASSEMBLES

(6) 47K OHM 

END OF LINE 

RESISTORS

C0202-01

Table 1: Short Circuit Protection - UL 864 9th Edition Requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with requirements in the Standard for 

Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific 

values or not used at all as indicated below.

Program Feature or Option

Permitted in  

UL 864 (Y/N)

Possible Settings

Settings Permitted in UL 864

Disabling short circuit 
protection when a single 
power supply is shared by 
multiple NACs

No

Enable or Disable 
short circuit 
protection

Enable short circuit protection when a single power 
supply is shared by multiple NACs.  Short circuit 
protection can be disabled only when a power supply 
is not shared by multiple NACs.

I56-1874-01

1

Summary of Contents for CMF-300-6

Page 1: ...to 49 C Humidity 10 to 93 Non condensing Dimensions 6 8 H x 5 8 W x 1 25 D Accessories CH 6 Chassis BB 6 Cabinet BB 2 Cabinet Wire Gauge 12 18 AWG Max NAC Circuit Line Loss 4 VDC Power Rating Per Cir...

Page 2: ...Lite COMPONENTS Following are descriptions of the CMF 300 6 mounting frame works There are two mounting options for CMF 300 6 modules Up to six CMF 300 6 modules can be installed on a CH 6 in a BB 6...

Page 3: ...ER SUPPLY MONITOR DISABLE SHORT CIRCUIT PROTECTION SYNC GENERATOR SIDE VIEW TOP VIEW SLC WIRING TERMINAL NOTIFICATION APPLIANCE POWER SUPPLY TERMINAL DISABLE 1 DISABLE 2 DISABLE 3 A B SELECT C0228 01...

Page 4: ...pplies EOL relays and notification appliances must be UL listed for fire protection signaling applications WIRING NOTES Power limited circuits must employ type FPL FPLR or FPLP cable as required by Ar...

Page 5: ...0 RED VIO VIO RED BLK BLK 47K NOTE EOL RELAY COIL CONNECTIONS MUST BE MADE USING EOL RELAY CONNECTOR ASSEMBLIES ON T10 T16 IN EVENT THAT ALL NACS ON THE PCB HAVE DEDICATED SUPPLIES Figure 10 Example o...

Page 6: ...CTION MANUAL FOR WIRE REQUIREMENTS POWER LIMITED AND SUPERVISED TOP OF T0 EOLR 1 TYP RED VIO VIO RED BLK BLK Figure 12 Example of Class A Style Z NAC configuration with a single supply shared by 2 NAC...

Page 7: ...2 3 4 5 6 7 8 9 0 7 8 6 5 4 3 2 1 9 10 11 12 13 14 15 EXTERNAL POWER SUPPLY PCB 1 PCB 2 VIEW A A C0233 00 FCC Statement This device complies with part 15 of the FCC Rules Operation is subject to the...

Reviews: