BEFORE INSTALLING
This information is included as a quick reference installation
guide. Refer to the appropriate Fire•Lite control panel installation
manual for detailed system information. If the modules will be
installed in an existing operational system, inform the operator
and local authority that the system will be temporarily out of ser-
vice. Disconnect the power to the control panel before installing
the modules. This system contains static sensitive components.
Always ground yourself with a proper wrist strap before handling
any circuits so that static charges are removed from the body. The
module housing should also be grounded.
NOTICE:
This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The CMF-300-6 Six Supervised Control Module is intended for
use in an intelligent alarm system. Each module is intended for
switching applications involving AC or DC which require wiring
supervision. A common SLC input is used for all modules. Each
module has its own address. A pair of rotary code switches is used
to set the address of the first module from 01 to 154. The remain-
ing modules are automatically assigned to the next five higher ad-
dresses. Provisions are included for disabling a maximum of three
unused modules to release the addresses to be used elsewhere.
Each module also has panel controlled green LED indicators. The
panel can cause the LEDs to blink, latch on, or latch off.
In order to synchronize strobes, horn/strobes, and speaker/
strobes, a SYNC-1 accessory card (sold separately) must be used
with the CMF-300-6. See the SYNC-1 installation manual for de-
tails on how to install.
F300-21-00
1
I56-1874-011
Fire•Lite Alarms, Inc. One Fire•Lite Place, Northford, CT 06472 203-484-7161
SPECIFICATIONS
Normal Operating Voltage:
15-32 VDC
Stand-By Current:
2.25 mA
Alarm Current:
35 mA (assumes all six relays have been switched once and all six LEDs solid on)
Temperature Range:
32°F to 120°F (0°C to 49°C)
Humidity:
10 to 93% Non-condensing
Dimensions:
6.8˝H x 5.8˝W x 1.25˝D
Accessories:
CH-6 Chassis; BB-6 Cabinet; BB-2 Cabinet
Wire Gauge:
12-18 AWG
Max. NAC Circuit Line Loss:
4 VDC
Power Rating Per Circuit (Speakers):
63 W @ 70.7 VAC; 50 W @ 25 VAC
Maximum NAC Current Ratings:
For class B wiring systems, 3A; For class A wiring systems, 2A
CMF-300-6 Six Supervised Control Module
Installation and Maintenance Instructions
Each module has terminals for connection to an external supply
circuit for powering devices on its NAC. Each supply must be
power limited and its voltage/current limits must be at or below
those specified. There is a short circuit protection monitor for
each module. This is provided to protect the external power sup-
ply against short circuit conditions on the NAC.
Included:
Shipped on Board:
(1)
Small shunt in Class A/B position
(Shipped in Class B position, remove shunt for Class A)
(6)
Large shunts on Enabled Power Supply Monitor
(6)
Large shunts on Disable Short Circuit Protection
(3)
Large shunts on Sync Generator
(7) 1 × 4
TERMINAL
BLOCKS
(7) 1¼˝ (32mm) STANDOFFS
(15) LARGE
SHUNTS
(4) MACHINE SCREWS
(2) NUTS
(5) SHORT POWER
SUPPLY JUMPERS
(2) SMALL
SHUNTS
(1) LONG POWER SUPPLY JUMPER
(2) EOL RELAY
CONNECTOR
ASSEMBLES
(6) 47K OHM
END OF LINE
RESISTORS
C0202-01
Table 1: Short Circuit Protection - UL 864 9th Edition Requirements
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with requirements in the Standard for
Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific
values or not used at all as indicated below.
Program Feature or Option
Permitted in
UL 864 (Y/N)
Possible Settings
Settings Permitted in UL 864
Disabling short circuit
protection when a single
power supply is shared by
multiple NACs
No
Enable or Disable
short circuit
protection
Enable short circuit protection when a single power
supply is shared by multiple NACs. Short circuit
protection can be disabled only when a power supply
is not shared by multiple NACs.
I56-1874-01