FIGURE 4. TYPICAL M300 FAULT TOLERANT INITIATING CIRCUIT CONFIGURATION, NFPA STYLE D

1 (-)

2 (+)

MODULE

FROM PANEL OR

(+)

(-)

TO NEXT

(+)

(-)

DEVICE

(+)

(-)

3 (-)
4 (+)

(+) 9

(-) 8

(-) 7

(+) 6

XXX 5

CONTROL

(-)

(+)

(-)

(+)

47K EOL

RESISTOR

A2143-00

UL LISTED EOL RELAY

SHOWN ENERGIZED
A77-716B

XXX - DO NOT

USE TERMINAL 5

TO NEXT CONTROL MODULE OR END

OF LINE RELAY (EOLR); ONE EOLR

REQUIRED PER BRANCH CIRCUIT

MODULE POLARITIES ARE

SHOWN IN ALARM

CONNECT MODULES TO LISTED COMPATIBLE

USE UL LISTED INDICATING APPLIANCES

RESISTIVE: 2 A @ 30 VDC

INDUCTIVE: 1 A @ 30 VDC (.6 PF)

PILOT DUTY: .6 A @ 30 VDC (.35 PF)

MAXIMUM LOAD:

SEE FIRE-LITE PRODUCT

MANUAL FOR

WIRE SPECIFICATIONS

 BRANCH CIRCUIT

3 & 4. BREAK WIRE RUN TO PROVIDE

SUPERVISION OF CONNECTIONS.

DO NOT LOOP WIRE ON TERMINALS

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

(-)

(+)

ISOLATED, REGULATED

POWER SUPPLY, LISTED FOR FIRE

PROTECTION WITH BATTERY BACKUP

(MONITOR LOSS OF PRIMARY POWER)

C304(A)

FIRE-LITE CONTROL PANELS ONLY

INDICATING APPLIANCE CIRCUIT (IAC) - NFPA STYLE W

COMMUNICATION LINE

PREVIOUS DEVICE

EXTERNAL POWER SOURCE MUST BE

POWER LIMITED PER NFPA 70

A78-2282-05

FIGURE 5. TYPICAL C304 INDICATING CIRCUIT CONFIGURATION, NFPA STYLE W

F300-03-01

2

I56-570-05

1 (–)

2 (+)

MODULE

FROM PANEL OR

(+)

(-)

TO NEXT

(+)

(–)

DEVICE

(+)

(–)

MONITOR

CONNECT MODULES TO LISTED COMPATIBLE

(–)9

(+)8

(+)7

(–)6

M300(A)

FIRE-LITE CONTROL PANELS ONLY

PREVIOUS DEVICE

COMMUNICATION LINE

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

EOL RESISTOR 
IS INTERNAL AT
TERMINALS 8 & 9.

ANY NUMBER OF UL LISTED CONTACT CLOSURE

DEVICES MAY BE USE. DO NOT MIX FIRE

ALARM INITIATING, SUPERVISORY, OR

SECURITY DEVICE ON THE SAME MODULE.

INITIATING DEVICE CIRCUIT - NFPA STYLE D

POWER LIMITED: 230 

µ

A MAX @ 12 VDC MAX

IDC INSTALLATION WIRING SHALL NOT

EXCEED 40 OHMS OR 2500 FEET, 12 - 18 AWG.

INSTALL CONTACT CLOSURE DEVICES PER

MANUFACTURER'S INSTALLATION INSTRUCTIONS.

SEE FIRE-LITE PRODUCT

MANUAL FOR  WIRE

SPECIFICATIONS

1 (–)

2 (+)

MODULE

FROM PANEL OR

(+)

(–)

TO NEXT

(+)

(–)

DEVICE

(+)

(–)

MONITOR

CONNECT MODULES TO LISTED COMPATIBLE

SEE FIRE-LITE PRODUCT

MANUAL FOR WIRE SPECIFICATIONS

(–)9

(+)8

(+)7

(–)6

M300(A)

FIRE-LITE CONTROL PANELS ONLY

PREVIOUS DEVICE

COMMUNICATION LINE

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

47 K EOL 
RESISTOR
A2143-00

ANY NUMBER OF UL LISTED CONTACT CLOSURE

DEVICES MAY BE USED. DO NOT MIX FIRE

ALARM INITIATING, SUPERVISORY, OR

SECURITY DEVICES ON THE SAME MODULE.

INITIATING DEVICE CIRCUIT - NFPA STYLE A OR B

POWER LIMITED: 230 

µ

A MAX @ 12 VDC MAX

IDC INSTALLATION WIRING SHALL NOT

EXCEED 40 OHMS OR 2500 FEET, 12 - 18 AWG.

INSTALL CONTACT CLOSURE DEVICES PER

MANUFACTURER'S INSTALLATION INSTRUCTIONS.

A78-2280-05

FIGURE 3. TYPICAL M300 2-WIRE INITIATING CIRCUIT CONFIGURATION, NFPA STYLE A OR B

Summary of Contents for C304(A

Page 1: ... wiring The second mode of switching op eration allows the panel to control one Form C SPDT set of contacts Circuit connections to the contacts are not supervised by the module This mode is enabled by breaking two external tabs on the module I300 A FAULT ISOLATOR MODULES enable part of the communications loop to continue operating when a short circuit oc curs on it An LED indicator blinks in the n...

Page 2: ...ONNECT MODULES TO LISTED COMPATIBLE 9 8 7 6 M300 A FIRE LITE CONTROL PANELS ONLY PREVIOUS DEVICE COMMUNICATION LINE ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED EOL RESISTOR IS INTERNAL AT TERMINALS 8 9 ANY NUMBER OF UL LISTED CONTACT CLOSURE DEVICES MAY BE USE DO NOT MIX FIRE ALARM INITIATING SUPERVISORY OR SECURITY DEVICE ON THE SAME MODULE INITIATING DEVICE CIRCUIT NFPA STYLE D POWER LIMITE...

Page 3: ...70 7 Vrms MAX AMP WIRE SUPERVISION CIRCUIT SPEAKER SWITCHING CIRCUIT NFPA STYLE W SPEAKERS MUST BE LISTED FOR FIRE PROTECTION MAXIMUM LOAD 43 75 WATTS MAX UP TO 70 7 Vrms 35 POWER FACTOR WIRES MUST BE SUPERVISEDD PER NFPA WHEN A 70 7V AUDIO AMPLIFIER IS USED TERMINALS 1 AND 2 ARE POWER LIMITED WHILE TERMINALS 3 9 ARE NONPOWER LIMITED IN THIS CASE THE CB500 BARRIER IS REQUIRED OTHERWISE ALL TERMINA...

Page 4: ...I300 A FAULT ISOLATOR MODULE I300 A SEE FIRE LITE PRODUCT MANUAL FOR WIRE SPECIFICATIONS INSTALLATION WARNINGS AND NOTES Control and isolator modules use a latching relay that can change states if it is subjected to mechanical shocks or jarring As a result although modules are shipped with their relays in the open state the contacts may have closed during shipment Con necting an auxiliary control ...

Reviews: