MS-4424    15153:F1    06/18/97

16

Notes on Style B and Style D field wiring:
1)  The Power Supervision Relay coil leads must be connected to the last detector base 24V screw terminals.
2)   Calculation of the maximum allowable resistance in the 24VDC detector power wiring:

Where:

R

MAX

 is the maximum resistance of the 24V wires.

V

OM

 is the minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts.

N is the total number of detectors on the 24V supply loop.

I

S

 is the detector current in standby.

N

A

 is the number of detectors on the 24V power loop which must function at the same time in alarm.

I

S

 is the detector current in alarm.

I

R

 is the end-of-line relay current.

3.3

4-Wire Smoke Detector Connections

R

MAX

 =              (20.6 - V

OM

)

(N x I

S

) + (N

A

 x I

A

) + (I

R

)

Refer to the Device Compatibility Chart for suitable 4-wire smoke detectors.

24 VDC (+)

Common (-)

IDC(+)

IDC(-)

Red

Black

24 VDC (+)

Common (-)

IDC(+)

IDC(-)

UL-listed 24 VDC

Four-Wire Smoke Detectors

 UL Listed

4.7K, 1/2-Watt

ELR

TB1

1

2

3

4

+       -

TB4

1

2

3

4

      

B+     A+       A-      B-

+24VR

A maximum of 200mA is available from the
+24VDC 4-wire smoke detector power cir-
cuit on TB1 terminals 3 and 4. Any power that
is drawn from the +24VDC Non-Resettable
Power on TB2 terminals 1 and 2 must be
subtracted from available 4-wire detector
power. (see Sections 

"Specifications" and

"Power" ).

IDC  #1

Style B Initiating Device Circuit

Initiating Device Circuits 1, 2, 3,  or 4
can be used.  Style D wiring can also be
employed.

 

Listed

Power

Supervision

Relay

Figure 3.3-1:  Diagram of Connections for a 4-Wire Smoke Detector

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Summary of Contents for MS-4424

Page 1: ...The MS 4424 FIRE ALARM CONTROL PANEL DOCUMENT 15153 ECN97 192 06 18 97 Rev F1 12 Clintonville Road Northford CT 06472 Technical Manuals Online http www tech man com firealarmresources com ...

Page 2: ...p before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instructions in the installation operating and programming manuals These instructions must be followed to avoid damage to the control panel and associated equipment FACP operation and reliability depend upon proper instal...

Page 3: ...hes 12 2 3 Zone Status LEDs 12 2 4 Supervisory 13 2 5 Zone Disable 13 2 6 Last Event Recall 13 3 0 Installation Procedure 14 3 1 General 14 3 2 Initiating Device Circuits 15 3 3 4 Wire Smoke Detector Connections 16 3 4 Output Circuits 17 3 5 Power 19 3 6 Optional Modules 21 3 7 Dip Switch Location and Descriptions 26 Appendix A Battery Calculations 27 Appendix B NFPA Standard Specific Requirements...

Page 4: ...ode UnderwritersLaboratoriesDocuments UL 38 Manually Actuated Signaling Boxes UL217 Smoke Detectors Single and Multiple Station UL228 Door Closers Holders for Fire Alarm Systems UL268 Smoke Detectors for Fire Alarm Systems UL 268A Smoke Detectors for Duct Applications UL346 Waterflow Indicators for Fire Alarm Systems UL464 AudibleSignalingAppliances UL521 Heat Detectors for Fire Alarm Systems UL86...

Page 5: ...transmittermodule 4XTMF Complies withNFPA72 1993AuxiliaryandRemoteStation Fire Alarm Systems Optional volt amp meter module 4XMMF Optional supervised remote annunciator RZA 4XF Requires LED Interface Module 4XLMF Optionaldigitalcommunicator NOTI FIRE911A 911AC Complies with NFPA 72 1993 Central StationandRemoteStationFireAlarmSystems Waterflow Input Option Supervisory Input Option Alarm verificati...

Page 6: ...MS 4424 15153 F1 06 18 97 6 Figure 1 0 1 MS 4424 Installation Diagram Technical Manuals Online http www tech man com firealarmresources com ...

Page 7: ...per option the alarm reverse polarity circuit will open on trouble if no alarm exists LED Interface Module 4XLMF The LED Interface Module supports the RZA 4XF Remote Annunciator module Annunciator wiring is supervised for open conditions by this module The Annunciator Driver Module mounts to the main board occu pying one of the two option connectors Zone Relay Module 4XZMF The Zone Relay module pr...

Page 8: ...e 14 6 ohms Maximum allowable wire resistance between panel and trip coil 3 ohms Municipal Box wiring can leave the building For Remote Station service NFPA 72 1993 Remote Station Fire Alarm Systems Maximum load for each circuit 10 mA Reverse polarity output voltage 24 VDC Remote Alarm and Remote Trouble wiring can leave the building 1 4 Remote Annunciator Remote Annunciator RZA 4XF TheRemoteAnnun...

Page 9: ...two Style Y Z two Style Y only Maximum allowable voltage drop due to wiring 2 VDC Normal Operating Voltage 24 VDC Total current available to all external devices 2 25 amps Maximum signaling current per circuit 1 5 amps End of line resistor 4 7K 1 2 Watt part 71252 UL listed Alarm and Trouble Relays Dry Form C contacts rated 2 0 amps 30 VDC resistive 0 5 amps 30 VAC resistive All relays must be con...

Page 10: ... 06 18 97 10 Cabinet 5 375 Backbox 4 750 Door 16 125 Backbox 16 Door 14 625 Backbox 14 5 Optional Trim Ring TR 4XRF Figure 1 6 1 Cabinet Dimensions Technical Manuals Online http www tech man com firealarmresources com ...

Page 11: ...mperswitch on Zone 4 SystemTrouble Yellow LED that flashes for any trouble condi tion including those associated with option boards Circuit Trouble Yellow LED that flashes for trouble conditions on output circuits notification Alarm Silenced Yellow LED that illuminates steadily when the ALARM SILENCE switch has been pushed after an alarm Power Trouble Yellow LED that flashes for low or discon nect...

Page 12: ...LARMACTIVATE The ALARM ACTIVATE switch may be used to activate Notification Appliance Circuits ALARM ACTIVATE also activates the System Alarmrelay ALARMACTIVATEisalatchingfunction PressingALARM SILENCE silences the notification appliance circuits and System Alarm Relay and lights the Alarm Silenced LED Pressing RESET returns the system to normal SYSTEM RESET The RESET switch breaks power to all in...

Page 13: ...ine makes use of the four panel switches as follows 1 Press and hold in the TONE SILENCE switch 2 With the TONE SILENCE switch held in press in sequence the ALARM SILENCE switch the ALARM ACTIVATE switch and then the RESET switch 3 The Zone 1 Alarm LED will flash 4 To disable Zone 1 press the RESET switch The Zone 1 yellow LED will light to show that the zone is disabled Note The RESET switch togg...

Page 14: ...ng should be in accordance with the National and or Local codes for fire alarm systems UL Power Limited Wiring Requirements Power limited and non power limited circuit wiring must remain separated in the cabinet All power limited circuit wiring must remain at least 0 25 away from any non power limited circuit wiring Furthermore all power limited circuit wiring and non power limited circuit wiring ...

Page 15: ...ummy Load provided on all unused circuits Figure 3 2 1 Example of Initiating Device Circuits Two wire Smoke Detector Manual Pull Station Heat Detector IDC 1 IDC 2 IDC 3 IDC 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 B A A B B A A B B A A B B A A B TB4 Style B Initiating Device Circuit Style D Initiating Device Circuit Normally Open Tamper Switch 4 7K 1 2 Watt part 71252 UL listed Style B Supervisory...

Page 16: ...3 3 4 Wire Smoke Detector Connections RMAX 20 6 VOM N x IS NA x IA IR Refer to the Device Compatibility Chart for suitable 4 wire smoke detectors 24 VDC Common IDC IDC Red Black 24 VDC Common IDC IDC UL listed 24 VDC Four Wire Smoke Detectors UL Listed 4 7K 1 2 Watt ELR TB1 1 2 3 4 TB4 1 2 3 4 B A A B 24VR A maximum of 200mA is available from the 24VDC 4 wire smoke detector power cir cuit on TB1 t...

Page 17: ... jumper must be cut To activate only one Notification Appliance Circuit Circuit 4 cut SUPV1 jumper To disable all Notification Appliance Circuits cut SUPV2 jumper for supervisory conditions Refer to Jumper Configu ration Table See figure below for jumper location If a 4XZMF relay module is used relay 4 will activate for supervisory conditions If a RZA 4XF is used the red LED 4 will annunciate supe...

Page 18: ...l A n e G 1 X X 2 m l A n e G 2 X X 2 m l A n e G 3 X X 2 m l A n e G 4 X X 1 v p u S 1 X X X 1 v p u S 2 X X X 1 v p u S 3 X X X 1 v p u S 4 X 2 v p u S 1 X X X X 2 v p u S 2 X X X X 2 v p u S 3 X X X X 2 v p u S 4 n e G 1 m l A n e G 1 v p u S 2 m l A 1 X n e G 1 m l A n e G 1 v p u S 2 m l A 2 X n e G 1 m l A n e G 1 v p u S 2 m l A 3 X n e G 1 m l A n e G 1 v p u S 2 m l A 4 X e n o N 1 X X X ...

Page 19: ...er before servicing The panel and associated equipment may be damaged by removing and or inserting cards modules or interconnecting cables while this unit is energized Unregulated Power 24 VDC power for inductive type devices such as door holders can be connected to TB1 terminals 1 and 2 1 2 3 4 24VU 24VR 24VNR TB1 This output is not suitable for powering devices requiring filtered regulated DC po...

Page 20: ... 6 amps Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code NEC and or local codes Use 14 AWG or larger wire with 600 volt rating Battery Power Observe polarity when connecting battery Connect battery cable to J9 on the main board using the plug in connector provided See Appendix A for calculation of correct battery rating CAUTION Batteries contain ...

Page 21: ...nal module to enable module supervision J4 J5 J7 J8 OPT1 Jumper Cut to install module on J5 OPT2 Jumper Cut to install module on J8 Cut GEM ALM1 GEN ALM2 and SUPV1 jumpers for Ring by Zone see Section 3 4 TB5 TB1 TB2 TB3 TB4 Notes 1 Optional 4XLMF module for an RZA 4XF Annunciator must be installed on J7 and J8 only 2 4XTMF and 4XZMF modules can be installed in either location Figure 3 6 1 Optiona...

Page 22: ... main board with J1 and or J2 on the option board Insert screws provided into the holes on the top of the stand offs Affix the terminal identification labels provided with the option modules as shown below Stand offs Option Board 4XZMF shown Main Board Figure 3 6 2 Installing Option Modules Part 42050 Technical Manuals Online http www tech man com firealarmresources com ...

Page 23: ...sconnected The System Trouble LED will indicate disconnected and or Open Circuit conditions on the Municipal Box Cutting the TBL jumper will allow the alarm reverse polarity circuit to open on trouble if no alarm exists Note Remote Alarm Remote Trouble and Municipal Box wiring can leave the building Remote Alarm Remote Trouble TBL Jumper Disconnect LED Disconnect Switch Power Limited Circuit Non P...

Page 24: ... Relay 1 Relay 2 Relay 3 Relay 4 Alarm Trouble NO NC C NO NC C 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Relay 1 through 4 will activate with Output 1 through 4 and remain latched unless jumper LATCH is cut Use Disable switch to disconnect the relays NO NC C NO NC C NO NC C NO NC C Cut jumper for non latching silenceable relay operation 1 Skip a set of dry contacts to maintain the 0 25 required...

Page 25: ...nd 1 2 3 4 5 6 7 8 LED Interface Module 4XLMF The wiring of this module must follow the requirements as specified in the General Section UL PowerLimitedWiringRequirements Figure 3 6 3 LED Interface Module 4XLMF Note Make wiring connections with system power off Maximum wire impedance is 50 ohms per wiring connection Technical Manuals Online http www tech man com firealarmresources com ...

Page 26: ...If set Initiating Device Circuit 3 will function as a non silenceable circuit If an alarm occurs on this zone the ALARM SILENCE switch will not silence any activated output circuits Note The Reset key must be depressed after any switch configuration has been made Switch 4 Silence Inhibit Ifselectedandanalarmoccurs theALARM SILENCE switch will not function until 60 secondshavepassedsinceinitiationo...

Page 27: ...c Control Panel 88 mA ControlpanelwithACpoweroff SystemTroubleLED andaudibletroublesounderon If using a 4XZMF Zone Relay Module1 X 8 mA If using a 4XTMF Transmitter Module add 11 mA If using the Reverse Polarity Alarm output add 5 mA If using the Reverse Polarity Trouble output add 5 mA If using a 4XLMF RZA 4XF Driver Annunciator combination 1 1 X 19 mA If using a 4XMMF Meter Module add 1 mA If us...

Page 28: ...mp hour will require a Fire Lite BB 17F or other UL listed battery cabinet Table A 2 Ampere Hour Calculations Standby Battery Current Standby Time Convert the total from Table 1 24 60 or 90 hours to amps and enter here amps X hours Enter 0 25 for 5 minutes in alarm or 0 5 for 10 minutes in alarm Add Standby and Alarm amp hours Select a battery with an equal or greater amp hour rating than the figu...

Page 29: ...Municipal Box This unit must be installed as outlined in Figure B 2 NFPA 72 1993 Remote Station Fire Alarm Systems 4XTMF Transmitter Module for connection to the Fire Lite RS82 9 Remote Station Receiver See Figure B 3 for installation instructions for this unit OR NOTI FIRE911A 911ACDACT orMS 5012 forconnectiontoacompatiblelistedremotestationDACR This unit must be installed as outlined in Figure B...

Page 30: ...y Battery Requirement 24VDC 7Amp Hour Max 3 The 911A was discontinued Effective 10 96 this diagram is for reference only NOTE on STD DACT Place jumper over pins 2 3 marked DACT when employ ing a DACT This directs the control panel to transmit all trouble conditions except AC LOSS STD DACT 27 6 VDC Alarm 911A Supervisory To Central Station RED BLACK Common 24 0 VDC JP1 d r a o b r e h t o M A 1 1 9...

Page 31: ... in length in the same room This application using the NOTI FIRE 911AC is not FM approved STD DACT Alarm Supervisory To Central Station JP1 NOTE on STD DACT Place jumper over pins 2 3 marked DACT when employing a DACT This directs the control panel to transmit all trouble conditions except AC LOSS d r a o b r e h t o M C A 1 1 9 m r a l A 1 3 B T 7 d n a 6 y l l a m r o n n e p o s t c a t n o c 3...

Page 32: ...round Black White Green yellow yellow 1 2 TB2 TB3 TB1 RESET SILENCE MODE ALARM AC POWER TROUBLE SUPERVISORY Primary Active Secondary Active Kissoff J2 J3 Modular Cable P N MCBL 6 Secondary Phone Line Primary Phone Line 1 2 3 4 5 6 7 8 9 10 11 12 13 14 TB TB4 TB3 7 d r a o b r e h t o M 2 1 0 5 S M m r a l A 1 3 B T 2 2 B T 3 3 B T 1 2 B T e l b u o r T 4 3 B T 4 2 B T 6 3 B T 3 2 B T y r o s i v r...

Page 33: ...of sprinkler supervisory or trouble conditions Note Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms 4XTMF Transmitter Module activated polarities shown Municipal Box Circuit Gamewell Model M34 56 Local Energy Municipal Box Note Municipal Box wiring can leave the building Technical Manuals Online http www tech man com firealarmresources com ...

Page 34: ... are power limited and supervised with the exception of the reverse polarity loop Supervision of the loop is the responsibility of the receiver Remote Trouble Remote Alarm 1 2 3 4 4XTMF Transmitter Module activated polarities shown Note Remote Alarm and Remote Trouble wiring can leave the building Fire Lite RS82 9 Remote Station Receiver UL listed Technical Manuals Online http www tech man com fir...

Page 35: ...m C Alarm contact programmed to activate on General Alarm Notes 1 Connection between control panel and the transmitter are supervised by the transmitter 2 Use transformer model ULT STK NO 1000391 listed Class 2 12 V 10 VA See Potter Electric Signal Company Bulletin 748 3 This control panel transmitter arrangement can be employed for NFPA 72 1993 Proprietary Fire Alarm Systems Technical Manuals Onl...

Page 36: ... a t s n i f i s e l u d o m l a n o i t p o V 2 1 r o f K 2 2 V 4 2 r o f K 7 4 R L E y m m u d 2 s d a e l y r e t t a b h t o b e v o m e R 3 e h t t a t i u c r i c e n o t c e n n o c s r a e l c e l b u o r t f I m e l b o r p e h t t n i o p n i p o t e m i t 4 t i u c r i c e c a l p e r r a e l c t n s e o d e l b u o r t f I d r a o b M T X 4 n o D E L w o l l e Y n o M T X 4 1 h c t i w...

Page 37: ...MS 4424 15153 F1 06 18 97 37 NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Page 38: ...MS 4424 15153 F1 06 18 97 38 NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Page 39: ...MS 4424 15153 F1 06 18 97 39 NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Page 40: ...de by Fire Lite with respect to its products Fire Lite does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that Fire Lite is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience transportation damage misuse abuse ac...

Reviews: