1 I56-4097-000
BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably
grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The I300-6 Six Fault Isolator Module provides six equivalent circuits that will
allow a portion of the communications loop to continue operating when a
short circuit occurs on that loop. An amber LED indicator will blink in the
noromal state for each of the six inputs and will latch on during a short circuit
condition. The module will automatically restore the communications loop to
normal condition when the short circuit is removed.
CONTENTS INCLUDE:
(6) 1 × 4 Terminal Blocks
(2) 1¼˝ (32mm) Stand offs
(4) Machine Screws
(2) Nuts
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
FireLite system control panel.
COMPONENTS
Following are descriptions of the I300-6 mounting frameworks. There are two
mounting options for I300-6 modules:
• Up to six I300-6 modules can be installed on a CHS-6 in a CAB-3, CAB-4
or BB-25 cabinet
• One or two I300-6 modules can be installed in a BB-XP cabinet
Chassis
The CHS-6 chassis is used to mount I300-6 modules in a BB-25, CAB-3 or
CAB-4 Series cabinet. It accommodates up to six I300-6 modules in a single
cabinet row three modules wide and two modules deep.
I300-6 Six Fault Isolator Module
SPECIFICATIONS
Normal Operating Voltage:
15-32VDC
Stand-By Current:
2.7 mA
Maximum Current Draw:
102 mA
Temperature Range:
32°F to 120°F (0°C to 49°C)
Humidity:
10 to 93% Non-condensing
Dimensions:
6.8˝H × 5.8˝W × 1.0˝D
Accessories:
CHS-6 Chassis; BB-25 Cabinet; BB-XP Cabinet; CAB-3 Series Cabinets; CAB-4 Series Cabinets
Wire Gauge:
12-18 AWG
FIGURE 1. CHS-6 CHASSIS:
MOUNT WITH
SELF-THREADING SCREWS
TO BACK OF CABINET
The BB-XP cabinet has a built-in chassis that will accommodate one or two
I300-6 modules.
FIGURE 2. BB-XP CABINET:
The front I300-6 module positions of each chassis are offset below the rear
I300-6 module positions so that all of the status indicators are visible.
Cabinets
A BB-25, CAB-3 or CAB-4 Series cabinet will house the CHS-6 chassis with up
to six I300-6 modules installed on it. Refer to cabinet installation documents
for dimensions.
The BB-XP cabinet houses one or two I300-6 modules on the internal chassis
that is part of the cabinet. Refer to cabinet installation documents for dimen-
sions.
I56-4097-000
INSTALLATION AND MAINTENANCE INSTRUCTIONS
C0236-01
C0234-06