Fire-Lite Alarms I300-6 Installation And Maintenance Instructions Download Page 1

 

1 I56-4097-000

BEFORE INSTALLING

If the modules will be installed in an existing operational system, inform the 
operator and local authority that the system will be temporarily out of service. 
Disconnect the power to the control panel before installing the modules. This 
system contains static sensitive components. Always ground yourself with a 
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably 
grounded.

NOTICE: This manual should be left with the owner/user of this equipment.  

GENERAL DESCRIPTION

The I300-6 Six Fault Isolator Module provides six equivalent circuits that will 
allow a portion of the communications loop to continue operating when a 
short circuit occurs on that loop.  An amber LED indicator will blink in the 
noromal state for each of the six inputs and will latch on during a short circuit 
condition.  The module will automatically restore the communications loop to 
normal condition when the short circuit is removed.

CONTENTS INCLUDE:

(6) 1 × 4 Terminal Blocks 
(2) 1¼˝ (32mm) Stand offs
(4) Machine Screws
(2) Nuts

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
FireLite system control panel.  

COMPONENTS

Following are descriptions of the I300-6 mounting frameworks. There are two 
mounting options for   I300-6 modules:

•   Up to six I300-6 modules can be installed on a CHS-6 in a CAB-3, CAB-4 

or BB-25 cabinet

•  One or two I300-6 modules can be installed in a BB-XP cabinet

Chassis 

The CHS-6 chassis is used to mount I300-6 modules in a BB-25, CAB-3 or 
CAB-4 Series cabinet. It accommodates up to six I300-6 modules in a single 
cabinet row three modules wide and two modules deep.

I300-6 Six Fault Isolator Module

SPECIFICATIONS

Normal Operating Voltage: 

15-32VDC

Stand-By Current: 

2.7 mA

Maximum Current Draw: 

102 mA

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10 to 93% Non-condensing

Dimensions: 

6.8˝H × 5.8˝W × 1.0˝D 

Accessories: 

CHS-6 Chassis; BB-25 Cabinet; BB-XP Cabinet; CAB-3 Series Cabinets; CAB-4 Series Cabinets 

Wire Gauge: 

12-18 AWG

FIGURE 1. CHS-6 CHASSIS:

MOUNT WITH

SELF-THREADING SCREWS 

TO BACK OF CABINET

The BB-XP cabinet has a built-in chassis that will accommodate one or two 
I300-6 modules.

FIGURE 2. BB-XP CABINET:

The front I300-6 module positions of each chassis are offset below the rear 
I300-6 module positions so that all of the status indicators are visible.

Cabinets

A BB-25, CAB-3 or CAB-4 Series cabinet will house the CHS-6 chassis with up 
to six I300-6 modules installed on it. Refer to cabinet installation documents 
for dimensions.

The BB-XP cabinet houses one or two I300-6 modules on the internal chassis 
that is part of the cabinet.  Refer to cabinet installation documents for dimen-
sions. 

I56-4097-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

C0236-01

C0234-06

One FireLite Place

Northford, CT 06472

Phone: 203.484.7161 

Summary of Contents for I300-6

Page 1: ...ptions for I300 6 modules Up to six I300 6 modules can be installed on a CHS 6 in a CAB 3 CAB 4 or BB 25 cabinet One or two I300 6 modules can be installed in a BB XP cabinet Chassis The CHS 6 chassis is used to mount I300 6 modules in a BB 25 CAB 3 or CAB 4 Series cabinet It accommodates up to six I300 6 modules in a single cabinet row three modules wide and two modules deep I300 6 Six Fault Isol...

Page 2: ...ng to the instructions in this manual FIGURE 6C INSTALLATION OF I300 6 MODULE IN FRONT CHASSIS INSTALLATION STEPS 1 Cabinet Mounting In a clean dry area mount the backbox using the four holes provided in the back surface of the cabinet FIGURE 3 TYPICAL MOUNTING HOLE LOCATIONS BACKBOX MOUNTING HOLES 2 Chassis Installation The CHS 6 chassis is mounted in the BB 25 CAB 3 or CAB 4 Series cabinets It i...

Page 3: ...MING The I300 6 module operates with the following Fire Alarm Control Panels MS 9050UD MS 9200UDLS MS 9600LS MS 9600UDLS 6 8 5 8 FROM PANEL OR PREVIOUS DEVICE SIGNAL LINE CIRCUIT 32 VDC MAX TWISTED PAIR IS RECOMMENDED TO NEXT DEVICE STATUS INDICATORS FIGURE 7 WIRING AND PROGRAMMING THE I300 6 MODULE C0205 05 WIRING 1 Install module wiring in accordance with the job drawings and appro priate wiring...

Page 4: ...pment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular instal lation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equi...

Reviews: